Brand: Pepperl+Fuchs
Pepperl+Fuchs NJ5-18GM-N M18 NAMUR Inductive Sensor, 5 mm
Description
Pepperl+Fuchs NJ5-18GM-N overview
The Pepperl+Fuchs NJ5-18GM-N is a cylindrical M18 x 1 inductive sensor from Pepperl+Fuchs with a NAMUR output, a rated operating distance of 5 mm and flush installation. It has a stainless steel housing, a PBT sensing face and a 2 m PVC cable, and it can be used up to SIL 2 according to IEC 61508.
The datasheet released on 17 September 2025 shows a normally closed switching function, a nominal voltage of 8.2 V with an internal resistance of about 1 kilohm and a switching frequency up to 500 Hz. ATEX approval is given for equipment protection levels Ga, Gb and Da under PTB 00 ATEX 2048 X, and the sensor also carries a marine approval from DNV GL.
Key features of the Pepperl+Fuchs NJ5-18GM-N
- M18 x 1 stainless steel housing with PBT sensing face
- Rated operating distance 5 mm, flush installation
- NAMUR 2-wire output, normally closed
- Usable up to SIL 2 according to IEC 61508
- Switching frequency 0 to 500 Hz, hysteresis 3 percent
- ATEX approval for Ga, Gb and Da under PTB 00 ATEX 2048 X
- Ambient temperature from minus 25 to 100 degrees C
- IP66 / IP67 protection with a 2 m PVC cable
NJ5-18GM-N technical specifications
The values below are taken from the manufacturer datasheet of the NJ5-18GM-N, release date 2025-09-17. Always confirm the current datasheet and the certificates before final engineering.
| Parameter | Value |
|---|---|
| Model | NJ5-18GM-N, inductive sensor |
| Switching function / output | Normally closed (NC), NAMUR, 2-wire |
| Rated operating distance sn | 5 mm |
| Assured operating distance sa | 0 to 4.05 mm |
| Installation | Flush |
| Reduction factors | rAl 0.21; rCu 0.18; r304 0.63 |
| Nominal voltage | 8.2 V (Ri about 1 kilohm) |
| Operating voltage | 5 to 25 V |
| Switching frequency / hysteresis | 0 to 500 Hz / 3 percent |
| Current consumption | At least 3 mA target not detected; up to 1 mA target detected |
| Functional safety | SIL 2; MTTFd 4566 a; mission time 20 a; DC 0 percent |
| Ambient temperature | Minus 25 to 100 degrees C |
| Housing / sensing face | Stainless steel 1.4305 / AISI 303 / PBT |
| Protection | IP66 / IP67 |
| Cable | PVC, 6 mm diameter, 0.75 mm2, length 2 m |
| Thread | M18 x 1 |
Always read the certificates and instruction manuals before using the sensor in a hazardous area, because the permitted amplifier, cable and temperature class depend on the exact approval.
Typical applications in oil and gas, utilities, water and manufacturing
NAMUR inductive sensors detect valve stem position, damper position, coupling and gear presence and rotating-machine targets in areas where explosive atmospheres may occur. The NJ5-18GM-N is used in such duties on emergency shutdown valves, actuators, conveyors and packaged units in oil and gas, power and water installations in Oman and the GCC.
Because a NAMUR sensor has no electronics that can ignite a gas and works with a certified switch amplifier, it is the standard choice for limit switching in hazardous areas. Maintenance teams also like inductive sensors because they have no moving parts and tolerate dirt, oil and vibration better than mechanical limit switches.
Selection and compatibility notes for NJ5-18GM-N
Match the sensor to the amplifier. A NAMUR sensor must be connected to an intrinsically safe switch amplifier such as a K-System module, and the entity data of the sensor in the certificate must be compatible with the amplifier. Do not connect it to a standard PLC input.
Check the sensing range against the target material. The reduction factors in the datasheet show how the operating distance falls for aluminium, copper and stainless steel compared with mild steel, and the mounting type, flush or non-flush, decides how much free space is needed around the sensing face.
Installation and commissioning of the NJ5-18GM-N
Before mounting the NJ5-18GM-N, check the free space around the sensing face, the mounting hole or bracket and the cable or connector route. Tighten the fixing nuts only to the torque recommended for the housing so that the thread and the sensing face are not damaged, keep cables away from power wiring where possible, and fit the sensor so that the target passes at a repeatable distance well inside the assured operating distance.
Connect the NJ5-18GM-N according to the connection diagram of the datasheet, then move the target through the sensing zone and watch the switching state at the input of the amplifier or controller. Record the switching distance at commissioning, so that later checks can show whether the NJ5-18GM-N has drifted or the target has moved.
Maintenance and service life
The NJ5-18GM-N has no serviceable parts. During planned shutdowns, inspect the housing, the cable or connector and the mounting for damage, loosened nuts and build-up of metal chips or dirt on the sensing face, and repeat the switching distance check recorded at commissioning. In coastal and humid locations such as Muscat, Sohar and Duqm, check cable glands and connector seals for corrosion.
If the NJ5-18GM-N stops switching or switches erratically, check the supply, the wiring and the target position before replacing it. Replace a damaged sensor instead of repairing it, and keep the replacement documentation in the loop folder. Certified equipment must not be modified, and any change of cable or amplifier should be re-assessed against the sensor data.
Related products and ordering notes
Customers who ask for the NJ5-18GM-N often need neighbouring models or accessories from the same system, such as other NAMUR and PNP inductive sensors of neighbouring sizes, K-System switch amplifiers, mounting brackets and connector cables. If you are standardising a cabinet or a spare parts list on one family, send us the loop list or the equipment list and we can quote the matching items together.
When you send an enquiry for the NJ5-18GM-N, quote the full part number exactly as printed on the nameplate, the quantity and the intended application. If you are replacing an installed unit, a photograph of the nameplate helps us confirm the exact variant you need. We can arrange a quotation with delivery to Oman and across the GCC.
Frequently asked questions about NJ5-18GM-N
The NJ5-18GM-N is an M18 stainless steel NAMUR inductive sensor with 5 mm flush operating distance, SIL 2 suitability, ATEX approval and a 2 m PVC cable.
Documents and quotation
A copy of the manufacturer datasheet for the NJ5-18GM-N is attached to this page for your engineering review. To request a quotation, send the RFQ with the part number NJ5-18GM-N, the quantity, the delivery location and any certification or documentation requirements, and we will reply with availability and lead time. Please check the specification against your loop or system requirements before ordering.
Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with Pepperl+Fuchs. Product names and part numbers are used only to identify the item you ask for.
Datasheets & Documents
- Datasheet NJ5-18GM-N Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.
Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.
Pepperl+Fuchs company profile
| Founded | 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs |
|---|---|
| Headquarters | Mannheim, Germany |
| Ownership | Privately owned (Pepperl+Fuchs SE) |
| Origins | Radio repair workshop that began making replacement transformers |
| Product families | Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures |
Milestones
- 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
- 1958: The first proximity switch is developed (some company sources say 1959).
Pepperl+Fuchs product families on this page
On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.
Where Pepperl+Fuchs equipment is used
Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.
Pepperl+Fuchs products we list
Ordering Pepperl+Fuchs parts: what we need
Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.
Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.
Browse Pepperl+Fuchs products by category: Sensors & Transmitters, Industrial Computer, Isolator & Barrier, Power Modules.
FAQ
Questions about the Pepperl+Fuchs NJ5-18GM-N M18 NAMUR Inductive
Answers from our engineering team on installation, compatibility and integration.
01What type of output does the NJ5-18GM-N have?
It has a 2-wire NAMUR output with a normally closed function, intended for connection to an intrinsically safe switch amplifier.
02What is the sensing distance of the NJ5-18GM-N?
The rated operating distance is 5 mm with flush installation, and the assured operating distance is 0 to 4.05 mm.
03Can it be used in hazardous areas?
The datasheet lists ATEX approval for Ga, Gb and Da under PTB 00 ATEX 2048 X, and the instruction manuals and certificates must be followed for any installation.
04Which documents are available for the NJ5-18GM-N?
The manufacturer datasheet is attached to this page, and certificates or manuals can be requested together with your RFQ for the NJ5-18GM-N.
05How do I order the NJ5-18GM-N?
Send an RFQ with the part number NJ5-18GM-N, the quantity and the delivery location in Oman or the GCC, and Seven Star LLC will reply with availability and lead time.


















Reviews