Pepperl+Fuchs KFD2-SL2-Ex1 overview

The Pepperl+Fuchs KFD2-SL2-Ex1 is a one-channel isolated barrier from the K-System of Pepperl+Fuchs that supplies power to solenoids, LEDs and audible alarms located in a hazardous area. It is controlled by a logic signal on the control side, and at full load 11.7 V at 45 mA is available for the hazardous area application.

The datasheet released on 17 January 2022 describes a non-polarized logic input with a 1-signal of 16 to 30 V DC and a 0-signal of 0 to 5 V DC and an input current of about 3 mA. A line fault is detected when the field impedance is above 10 kilohm for lead breakage or below 50 ohm for short circuits, and a fault is signalled by LEDs and a separate collective error message output. The safety integrity level is up to SIL 2.

Key features of the Pepperl+Fuchs KFD2-SL2-Ex1

  • Powers solenoids, LEDs and audible alarms in hazardous areas
  • Output up to 45 mA at at least 11.7 V DC
  • Non-polarized logic input, 16 to 30 V DC for 1-signal
  • Line fault detection for lead breakage and short circuit
  • Fault indication by LEDs and collective error message
  • Up to SIL 2 according to IEC/EN 61508
  • Powered from 20 to 30 V DC via Power Rail or terminals 14 and 15
  • Housing type B2, 20 mm wide

KFD2-SL2-Ex1 technical specifications

The values below are taken from the manufacturer datasheet of the KFD2-SL2-Ex1, release date 2022-01-17. Always confirm the current datasheet and the certificates before final engineering.

Parameter Value
Model KFD2-SL2-Ex1, Solenoid Driver, 1-channel isolated barrier
Signal type Digital output
Safety integrity SIL 2
Supply 20 to 30 V DC, Power Rail or terminals 14+, 15-
Power consumption Up to 1.7 W at 45 mA output current
Input Terminals 7, 8; about 3 mA at 24 V DC; 1-signal 16 to 30 V DC; 0-signal 0 to 5 V DC
Output terminals 1+, 2- or 3-
Internal resistance Ri 272 ohm
Output current / voltage Up to 45 mA / at least 11.7 V
Open loop voltage At least 24 V
Energized / de-energized delay Up to 20 ms / up to 20 ms
Ambient temperature Minus 20 to 60 degrees C
Dimensions / mass 20 x 119 x 115 mm (W x H x D), housing type B2 / about 150 g

The hazardous-area parameters are listed per terminal pair in the datasheet. Use the entity values of the exact terminals you wire, and refer to the certificate for the permitted cable parameters of your installation.

Typical applications in oil and gas, utilities, water and manufacturing

Solenoid valves, beacons and audible alarms in Zone 1 and Zone 2 areas need a limited amount of power delivered safely from the control room. The KFD2-SL2-Ex1 provides that power in response to a logic signal, which makes it a common choice on wellhead panels, tank farm valves, loading arms and burner or boiler skids across Oman and the GCC.

In water and wastewater works and manufacturing plants the same driver switches intrinsically safe solenoids on pneumatic actuators and process valves. Because the logic input is isolated from the field circuit, a PLC digital output card can drive the module directly without extra interposing relays.

Selection and compatibility notes for KFD2-SL2-Ex1

Match the solenoid to the output of the KFD2-SL2-Ex1. The datasheet gives the available voltage and current and the internal resistance, so check the coil data of your intrinsically safe solenoid, its certified entity parameters and the cable length before you order. A coil that needs more power than the module can supply will not pull in reliably.

Also check the logic side. The input is specified with defined 1-signal and 0-signal voltage ranges, so confirm that your control system output falls inside them. When replacing an older driver, compare the terminal numbers, the supply method and any fault output so that the KFD2-SL2-Ex1 fits the existing cabinet wiring.

Installation and commissioning of the KFD2-SL2-Ex1

Before mounting the KFD2-SL2-Ex1, confirm the field device and cable parameters against the entity values in the datasheet and the certificate, and decide whether the module will be powered from a Power Rail, a termination board or its own supply terminals. Mount it in a clean, ventilated cabinet in the safe area, keep hazardous-area and safe-area wiring physically separated and labelled, and respect the spacing and marking required by your site rules for intrinsically safe circuits.

Wire the KFD2-SL2-Ex1 only to the terminal assignment printed in the wiring diagram, tighten the screws and check that no strands are left outside the clamp. After applying the supply, check the power indication, then simulate the field signal and prove the complete loop from field to control system before the plant is handed over. Record the as-found readings so that later loop checks of the KFD2-SL2-Ex1 can be compared with the commissioning values.

Maintenance and service life

The KFD2-SL2-Ex1 has no serviceable parts, so maintenance is mostly inspection. During planned shutdowns, check terminals for looseness and corrosion, verify the supply voltage at the module, and repeat the loop check that was recorded at commissioning. In coastal and humid locations such as Muscat, Sohar and Duqm, a clean, dry and sealed cabinet greatly extends the life of any electronic interface.

If a loop drifts out of tolerance or the unit shows no power indication with a healthy supply, replace the module instead of attempting a repair, and keep the replacement documentation in the loop folder. Certified intrinsically safe equipment must not be modified, and any change to cabling, load or field device should be re-assessed against the KFD2-SL2-Ex1 entity parameters before it returns to service.

Related products and ordering notes

Customers who ask for the KFD2-SL2-Ex1 often need neighbouring models or accessories from the same system, such as other K-System isolated barriers, the Power Rail and power feed modules, KFA6 power supplies and the matching NAMUR sensors. If you are standardising a cabinet or a spare parts list on one family, send us the loop list or the equipment list and we can quote the matching items together.

When you send an enquiry for the KFD2-SL2-Ex1, quote the full part number exactly as printed on the nameplate, the quantity and the intended application. If you are replacing an installed unit, a photograph of the nameplate helps us confirm the exact variant you need. We can arrange a quotation with delivery to Oman and across the GCC.

Frequently asked questions about KFD2-SL2-Ex1

The KFD2-SL2-Ex1 is a SIL 2 capable solenoid driver supplying up to 45 mA at at least 11.7 V DC with a logic input, line fault detection and a 20 mm wide housing.

Documents and quotation

A copy of the manufacturer datasheet for the KFD2-SL2-Ex1 is attached to this page for your engineering review. To request a quotation, send the RFQ with the part number KFD2-SL2-Ex1, the quantity, the delivery location and any certification or documentation requirements, and we will reply with availability and lead time. Please check the specification against your loop or system requirements before ordering.

Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with Pepperl+Fuchs. Product names and part numbers are used only to identify the item you ask for.

Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.

Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.

Pepperl+Fuchs company profile

Founded 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs
Headquarters Mannheim, Germany
Ownership Privately owned (Pepperl+Fuchs SE)
Origins Radio repair workshop that began making replacement transformers
Product families Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures

Milestones

  • 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
  • 1958: The first proximity switch is developed (some company sources say 1959).

Pepperl+Fuchs product families on this page

On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.

Where Pepperl+Fuchs equipment is used

Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.

Pepperl+Fuchs products we list

Family Examples
Isolator & Barrier HiD2030 SMART Transmitter Power Supply w…, KFD2-SR2-Ex2.W K-System Isolated Switch…, KFD2-UT2-Ex2 Universal Temperature Conve…
Industrial Computers Tab-Ex 05 DZ1 WWAN Hazardous Area Tablet, Smart-Ex® 03 DZ2 smartphone for Zone 2/2…
Inductive Proximity Sensors NJ2-12GK-SN NAMUR Inductive Sensor
Power Modules PS1000-A6-24.20 Power Supply 24 VDC 20 A
Photoelectric Sensors R101 Retro-Reflective Photoelectric Sensor
Laser Distance, LiDAR & Radar Sensors R2000 2-D LiDAR Laser Scanner

Ordering Pepperl+Fuchs parts: what we need

Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.

Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.

FAQ

Questions about the Pepperl+Fuchs KFD2-SL2-Ex1 Solenoid Driver

Answers from our engineering team on installation, compatibility and integration.

01What does the KFD2-SL2-Ex1 power?
It powers solenoids, LEDs and audible alarms in a hazardous area, with up to 45 mA at at least 11.7 V DC.
02How is the KFD2-SL2-Ex1 controlled?
By a non-polarized logic signal, with 16 to 30 V DC as 1-signal and 0 to 5 V DC as 0-signal, drawing about 3 mA.
03Does it detect line faults?
Yes, lead breakage above 10 kilohm and short circuits below 50 ohm are detected and signalled by LEDs and the collective error message.
04Which documents are available for the KFD2-SL2-Ex1?
The manufacturer datasheet is attached to this page, and certificates or manuals can be requested together with your RFQ for the KFD2-SL2-Ex1.
05How do I order the KFD2-SL2-Ex1?
Send an RFQ with the part number KFD2-SL2-Ex1, the quantity and the delivery location in Oman or the GCC, and Seven Star LLC will reply with availability and lead time.