Schneider Electric A9V44263 Vigi iC60 2P 63 A 300 mA

Description

A9V44263: Vigi iC60 2P 63 A 300 mA add-on block

The A9V44263 is a Schneider Electric Acti9 Vigi iC60 add-on residual current device in a two-pole version, rated 63 A with 300 mA sensitivity and Type AC detection. It is not a stand-alone breaker. It is clipped to the side of a compatible iC60 miniature circuit-breaker and joined to it by screws, so the breaker keeps its overload and short-circuit duty while the block supplies the earth-leakage function. Seven Star LLC supplies the A9V44263 in Oman and the GCC as an independent supplier based in Muscat.

Reading the title of A9V44263: 2P is the number of poles, 63A is the rated current, 300mA is the leakage threshold and AC type is the waveform class. The datasheet places the device in the outgoer position of a board, with voltage-independent tripping and a trip indicator on the front. It is a natural match for a single-phase circuit where phase and neutral are both switched, which is the pole count this reference is built around.

Technical specifications of the A9V44263

Parameter Specification
Manufacturer / part number Schneider Electric / A9V44263
Range Acti9 Vigi iC60 (add-on residual current device)
Poles 2P
Rated current [In] 63 A
Earth-leakage sensitivity 300 mA, instantaneous
Protection type Type AC
Network AC, 50/60 Hz
Rated operational voltage 230–415 V AC 50/60 Hz (EN/IEC 61009-1 and 61009-2-1)
Rated insulation voltage [Ui] 500 V AC
Rated impulse withstand [Uimp] 6 kV
Tripping technology Voltage independent
Local signalling Trip indicator
Mounting Clip-on, DIN rail, screw connection to the MCB
Width / height / depth / 91 / 73.5 mm
Net weight 0.165 kg
Bottom terminals Tunnel type: 35 mm² rigid, 25 mm² flexible, with or without cable end
Stripping length / torque 14 mm / 3.5 N.m
Protection degree IP20; IP40 in a modular enclosure
Operating / storage temperature -5–60 °C / -40–85 °C
Warranty 18 months

How the A9V44263 protects: residual current basics

A residual current device compares the current leaving through the live conductors with the current returning. If the difference exceeds the threshold, some current is leaving by another route, typically through an insulation fault to earth or a person, and the device opens the circuit. The A9V44263 uses a 300 mA threshold with no deliberate delay, and the datasheet describes its tripping as independent of the supply voltage.

A 300 mA setting is a level normally chosen to limit fire risk and equipment damage on a feeder, not to protect people from direct contact, which is the job of a 30 mA device. In a graded design the block may sit upstream of finer devices on the final circuits, but the grading and the delay needed for selectivity must be worked out in the design. Type AC covers sinusoidal residual current, so loads that can create pulsating DC leakage need a different type.

Installation and testing of A9V44263

Mount the paired breaker on the DIN rail, clip the block on and tighten the screw connection between the two. The bottom terminals take a 14 mm strip length and a tightening torque of 3.5 N.m, which should be applied with a calibrated driver. The datasheet lists a trip indicator on the front, and the visual state helps when you inspect a board after a fault.

After installation, operate the device with the local test arrangement and record the result in the commissioning file. A residual current device that has not been exercised is an unknown quantity. Periodic checking by the operator is a normal part of maintenance, and the interval should follow the site procedure.

Selection checklist and RFQ details for A9V44263

Datasheets & Documents
  • PDF Datasheet Schneider Electric A9V44263 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric A9V44263 Vigi iC60 2P 63 A 300 mA

Answers from our engineering team on installation, compatibility and integration.

01What does the A9V44263 add to an iC60 breaker?
It adds earth-leakage protection to a compatible two-pole iC60 breaker. It is a clip-on 63 A block with 300 mA sensitivity and Type AC detection, connected to the breaker by screws.
02What is the leakage setting of the A9V44263?
The datasheet lists 300 mA with instantaneous tripping and Type AC. Tripping is voltage independent, and a trip indicator is shown on the front.
03Which breakers can the A9V44263 be fitted to?
The datasheet lists iC60 single terminal breakers up to 63 A, Disbo iC60N/H up to 63 A, iC60L MA up to 40 A and Reflex iC60 up to 63 A. The pole count must match.
04What are the dimensions of the A9V44263?
The datasheet gives mm wide, 91 mm high and 73.5 mm deep, weight 0.165 kg.
05What operating temperature applies to the A9V44263?
Operation is rated from -5 to 60 °C and storage from -40 to 85 °C, with IP20 protection or IP40 in a modular enclosure.