Brand: Schneider Electric
Schneider Electric SR3XT43BD Zelio 4 I/O analogue I/O Module
Description
SR3XT43BD: analogue I/O extension module, 2 inputs and 2 outputs
The SR3XT43BD is a Schneider Electric Zelio Logic analogue extension module with two analogue inputs and two analogue outputs, powered from 24 V DC according to its description. Where the discrete modules only know on and off, this unit lets a Zelio Logic smart relay read a 0–10 V signal, a 0–20 mA loop or a Pt 100 sensor and drive 0–10 V outputs, which turns a relay panel into a small closed-loop controller. Seven Star LLC supplies the SR3XT43BD in Oman and the GCC as an independent supplier based in Muscat.
The XT43 in the reference lines up with 4 channels in total (2 in, 2 out) and the BD suffix with the 24 V DC supply; this is our reading of the datasheet, not a published ordering table, so verify the reference on your drawing.
Technical specifications of the SR3XT43BD
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / SR3XT43BD |
| Range | Zelio Logic |
| Product type | Analogue I/O extension module |
| Analogue inputs | 2: 0–10 V, 0–20 mA or Pt 100 (three-wire, IEC 751) −25 to 125 °C |
| Input resolution | 10 bits on the input range |
| Maximum permissible voltage / current | 30 V / 30 mA permanent |
| Input impedance | 18 kΩ (0–10 V), 247 Ω (0–20 mA) |
| Analogue outputs | 2: 0–10 V, 10 bits, resistive load, up to 10 mA, short-circuit protected |
| Step size (LSB) | 9.8 mV (0–10 V), 20 µA (0–20 mA), 0.15 °C (Pt 100) |
| Conversion error | ±1 % of full scale (0–10 V and 0–20 mA, 25 and 55 °C); ±1.5 °C (Pt 100) |
| Repeat accuracy | < ±0.3 °C (Pt 100 at 25 °C); ≤ ±1 % (voltage and current) |
| Cable length | 10 m with screened cable (inputs and outputs) |
| Net weight | 0.11 kg |
| Protection | IP20 terminal block, IP40 front panel |
| Operating temperature | −20 to 55 °C |
| Storage temperature | −40 to 70 °C |
| Relative humidity | 95 % without condensation or dripping water |
| Operating altitude | 2000 m |
| Warranty | 18 months |
| Certifications listed | GOST, UL, C-Tick, CSA |
Analogue channels of the SR3XT43BD
The two inputs are common-mode and each accepts one of three signal types: 0–10 V (10-bit, 18 kΩ input impedance, 9.8 mV per step), 0–20 mA (247 Ω input impedance, 20 µA per step) or a three-wire Pt 100 probe to IEC 751 over −25 to 125 °C with 0.15 °C steps. The datasheet states a conversion error of ±1 % of full scale for the voltage and current ranges and ±1.5 °C for Pt 100, at both 25 and 55 °C, and a Pt 100 repeat accuracy better than ±0.3 °C at 25 °C. The input circuit is protected against reverse polarity; the maximum permissible values are 30 V and a permanent 30 mA.
The two outputs are 0–10 V with 10-bit resolution, intended for resistive loads of up to 10 mA and protected against short circuits, which is enough to drive a drive speed reference or a damper actuator input but not a low-impedance load. Signal cabling should be screened and limited to the 10 m given in the datasheet for both inputs and outputs.
Permitted input combinations
The datasheet lists five allowed combinations for the two input channels, shown below as numbers of 0–10 V, 0–20 mA and Pt 100 inputs.
| 0–10 V | 0–20 mA | Pt 100 |
|---|---|---|
| 2 | 0 | 0 |
| 1 | 1 | 0 |
| 0 | 2 | 0 |
| 1 | 0 | 1 |
| 0 | 1 | 1 |
Two Pt 100 probes on one module are therefore not an option; plan temperature channels with that in mind.
Where the SR3XT43BD sits among Zelio Logic extension modules
Discrete extensions in the same series add on/off channels only: SR3XT61BD (4 inputs, 2 relays), SR3XT101BD (6 inputs, 4 relays) and SR3XT141BD (8 inputs, 6 relays) on 24 V DC, with SR3XT61FU, SR3XT101FU and SR3XT141FU as their 100–240 V AC counterparts. The SR3XT43BD is the only analogue-capable member in this group, and it belongs with 24 V DC base units; its datasheet connection diagram shows the module wired beside a DC-supplied smart relay.
| Module | Function | Channels |
|---|---|---|
| SR3XT43BD | Analogue | 2 in / 2 out |
| SR3XT61BD | Discrete, 24 V DC | 4 in / 2 relay |
| SR3XT101BD | Discrete, 24 V DC | 6 in / 4 relay |
| SR3XT141BD | Discrete, 24 V DC | 8 in / 6 relay |
Installation and commissioning of the SR3XT43BD
Wire the analogue lines with screened cable, grounding the screen at one end as your site practice dictates, and keep them away from relay-output wiring that carries inductive loads. Test the module with a calibrator or a known resistance box before connecting the process: apply 0, 5 and 10 V, or 4, 12 and 20 mA, and compare the value shown by the smart relay with the injected signal. For Pt 100, check the three-wire compensation by measuring lead resistance. Because each channel is a mix-and-match choice, record the channel assignment in the panel documents so that a replacement module is configured identically.
Spare practice: keep one SR3XT43BD on the shelf if analogue control is critical, stored within the −40 to 70 °C range.
Selection checklist for the SR3XT43BD
- List the analogue signals: how many are 0–10 V, 0–20 mA or Pt 100, and check them against the five permitted combinations.
- Confirm the base unit runs on 24 V DC.
- Check output load: 10 mA maximum per 0–10 V output, resistive.
- Check the sensor distance: 10 m with screened cable.
- Decide whether ±1 % of full scale suits your control accuracy.
Environmental limits and mounting
The module operates from −20 to 55 °C and is stored from −40 to 70 °C, at up to 95 % humidity without condensation or dripping water and altitudes up to 2000 m (3048 m for transport). Protection is IP20 at the terminal block and IP40 at the front, pollution degree 2. It weighs 0.11 kg and mounts on a 35 mm DIN rail or with retractable screw lugs, per the datasheet drawings. Terminals accept 0.25–2.5 mm² conductors at 0.5 N.m torque. In Oman and the Gulf the practical consequences are a ventilated cabinet and short, screened analogue runs kept away from contactor wiring.
Typical uses of the SR3XT43BD in Oman and the GCC
This unit suits temperature and pressure loops that are too small for a PLC: chilled-water supply temperature, pump pressure from a 4–20 mA transmitter (read as 0–20 mA), tank temperature with a Pt 100 and a variable-speed command on a 0–10 V output. In the Gulf, cooling and ventilation control is the obvious fit, because ambient temperatures keep the loop active most of the year. Utilities, desalination sub-systems and facilities contractors use small analogue extensions to retrofit older relay panels with a modest process-control function.
Information to send with an RFQ for the SR3XT43BD
- Exact reference SR3XT43BD and quantity.
- Base unit reference and its supply voltage.
- Load types on the outputs and any surge suppression fitted.
- Delivery location and project deadline.
Documents and quotation
The manufacturer datasheet for the SR3XT43BD is attached on this page and includes the dimension drawings and connection diagrams. Check the revision date against your project requirements.
Send us the reference SR3XT43BD, quantity and delivery location and Seven Star LLC will reply to your RFQ. We supply as an independent supplier based in Muscat.
Other Models in the Se Zelio Sr3xt Range
Seven Star LLC supplies models from the Se Zelio Sr3xt range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric SR3XT101BD Zelio 10 I/O discrete I/O Module | Logic Controllers | View details |
| Schneider Electric SR3XT101FU Zelio 10 I/O discrete I/O Module | Logic Controllers | View details |
| Schneider Electric SR3XT141BD Zelio 14 I/O discrete I/O Module | Logic Controllers | View details |
| Schneider Electric SR3XT141FU Zelio 14 I/O discrete I/O Module | Logic Controllers | View details |
| Schneider Electric SR3XT43BD Zelio 4 I/O analogue I/O Module | Logic Controllers | You are viewing this model |
| Schneider Electric SR3XT61BD Zelio 6 I/O discrete I/O Module | Logic Controllers | View details |
| Schneider Electric SR3XT61FU Zelio 6 I/O discrete I/O Module | Logic Controllers | View details |
Datasheets & Documents
- Datasheet Schneider Electric SR3XT43BD Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric SR3XT43BD Zelio 4 I/O analogue
Answers from our engineering team on installation, compatibility and integration.
01What signals can the SR3XT43BD read?
Two inputs, each configurable for 0-10 V, 0-20 mA or a three-wire Pt 100 probe (-25 to 125 degC), with 10-bit resolution.
02What outputs does the SR3XT43BD provide?
Two 0-10 V analogue outputs with 10-bit resolution, resistive load up to 10 mA, short-circuit protected.
03How accurate is the SR3XT43BD?
The datasheet gives a conversion error of +/-1 % of full scale for voltage and current ranges and +/-1.5 degC for Pt 100, at 25 and 55 degC.
04Can the SR3XT43BD take two Pt 100 probes?
No. The datasheet lists five permitted combinations of the two inputs, and two Pt 100 probes is not among them; one Pt 100 plus one voltage or current input is.
05How long can the signal cables be on the SR3XT43BD?
The datasheet gives 10 m with screened cable for both the inputs and the outputs.