Schneider Electric TM221C40T Modicon M221 40 I/O Controller

Description

TM221C40T: Modicon M221 40-I/O transistor logic controller

The TM221C40T is the larger transistor-output member of the Modicon M221 compact family: 40 built-in points made up of 24 digital inputs, 16 transistor outputs and 2 analogue inputs (0–10 V), in a case 160 mm wide. It is aimed at machines and process skids that need a full set of field signals without adding expansion modules.

Compared with the 24-point TM221C24T, TM221C40T adds ten inputs and six outputs while keeping the same processing, communication and motion features. It has no Ethernet port, so connection to SCADA or an HMI is by RJ45 serial (RS485, or RS232/RS485 on serial 2) or by USB. Seven Star LLC offers the this unit in Oman and the GCC as an independent supplier in Muscat.

Counting, pulse outputs and regulation in the TM221C40T

Four of the inputs are fast inputs for high-speed counting at 100 kHz and 32 bits, in single-phase, pulse/direction or A/B mode. The two fast outputs on Q0 and Q1 provide PWM, pulse-train and frequency-generator functions at up to 100 kHz, with two pulse/direction axes and one CW/CCW axis available for positioning. Q2 and Q3 reach 5 kHz, while Q4 to Q15 are limited to 0.1 kHz.

On top of that the controller supports adjustable PID regulation with up to 14 loops at once, which is enough for small temperature, pressure or level loops without a dedicated regulator.

Technical specifications of the TM221C40T

Parameter Specification
Manufacturer / part number Schneider Electric / TM221C40T
Range of product Modicon M221
Product type Logic controller
Rated supply voltage 24 V DC, limits 20.4–28.8 V
Inrush current 35 A
Discrete inputs 24 (4 of them fast), IEC 61131-2 Type 1, 24 V DC sink or source
Analogue inputs 2 at 0–10 V, 10 bit
Discrete outputs 16 transistor, 24 V DC, 0.5 A each, source logic (2 fast)
Power consumption 4.1 W at 24 V with no expansion; 16 W with maximum expansion
Expansion capability 7 TM3 modules (local I/O) or 14 (remote I/O architecture)
Application memory 256 kB RAM for application and data (10000 instructions); 256 kB flash backup
Execution time 0.2 µs per Boolean instruction; 0.3 ms per 1 K instructions (event and periodic task)
Real-time clock Built in, drift 30 s/month or less at 25 °C
Backup battery BR2032 or CR2032X lithium, 1 year at 25 °C
Optional storage 2 GB SD card
PID regulation Up to 14 simultaneous loops
Connections 1 mini-B USB; serial 1 RJ45 RS485; serial 2 RJ45 RS232/RS485
Mounting 35 mm DIN rail (TH35-15 or TH35-7.5) or panel with fixing kit
Dimensions (W x H x D) 160 x 90 x 70 mm
Net weight 0.456 kg
Operating temperature −10 to 55 °C horizontal; −10 to 35 °C vertical
Storage temperature −25 to 70 °C
Humidity 10–95 % without condensation
Protection IP20 with protective cover in place
Shock resistance 147 m/s² for 11 ms
Certifications listed cULus, cULus HazLoc, CE, UKCA, RCM, EAC, ABS, LR, DNV-GL

The TM221C40T compared with its M221 siblings

Bold marks the reference on this page.

Reference I/O Output type Width Communication
TM221C24T 24 (14 in / 10 transistor out) Transistor source, 0.5 A 110 mm Two serial ports
TM221C40T 40 (24 in / 16 transistor out) Transistor source, 0.5 A 160 mm Two serial ports
TM221M16RG 16 (8 in / 8 relay out) Relay 2 A, spring terminals 70 mm Two serial ports
TM221ME16RG 16 (8 in / 8 relay out) Relay 2 A, spring terminals 70 mm One serial port + Ethernet

Choosing the TM221C40T and sending an RFQ

Use these checks before ordering:

  • count real I/O and keep at least a few spare points; the TM221C40T has 24 inputs and 16 outputs
  • confirm that Ethernet is not required, because only serial and USB are fitted
  • check the total current on each output common against the 4 A limit
  • decide how many TM3 modules or cartridges will be added later
  • verify the supply: 24 V DC, 20.4 to 28.8 V

For an RFQ, send the quantity, destination, cabinet temperature, mounting orientation and the software version used by your programmers.

What the 40 points of the TM221C40T are used for

With 24 inputs, an operator can wire pushbuttons, selector switches, limit switches, proximity sensors and thermal-trip contacts for several drives on one controller. The sixteen transistor outputs are source type at 24 V DC and 0.5 A, so they drive pilot relays, solenoid coils and lamps; heavier loads should go through interposing relays.

The datasheet quotes a maximum current per output common of 4 A for this model, which is lower than the 5 A of the 24-point version. When you group many loads on one common, add up the currents rather than relying on the individual 0.5 A rating.

Supply, power budget and bus feed of the TM221C40T

Supply is 24 V DC with a permitted range of 20.4 to 28.8 V, and the inrush current is 35 A. The datasheet lists 4.1 W without expansion and 16 W with the maximum number of expansion modules. The built-in supply for the expansion bus is 0.52 A at 5 V and 0.3 A at 24 V, a little more 24 V capacity than the smaller transistor model offers.

Add the expansion-module consumption from their own datasheets to the controller figure when sizing the 24 V power supply for a rack with several modules.

Mounting and wiring the TM221C40T

The unit is 160 mm wide, 90 mm high and 70 mm deep and weighs 0.456 kg. It fits a TH35-15 or TH35-7.5 DIN rail, or a panel with the fixing kit. Inputs and outputs use removable screw terminal blocks, and the analogue inputs use a four-terminal connector.

Keep the layout inside the datasheet cable limits: 30 m unshielded for standard inputs and outputs, 10 m shielded for fast inputs, 3 m shielded for fast outputs and 1 m for analogue inputs. The case is IP20 only with its protective cover fitted, so use an enclosure with dust control for outdoor or desert-edge sites.

Approvals and environment of the TM221C40T

The datasheet lists IEC 61131-2, UL 508, CSA C22.2 No. 213, IACS E10 and ANSI/ISA 12-12-01 among its standards, and the certifications include cULus, cULus HazLoc, CE, UKCA, RCM, EAC, ABS, LR and DNV-GL. The environmental line states ordinary and hazardous locations; read the approval details before relying on that for a classified area.

Operation is rated from −10 to 55 °C horizontal and −10 to 35 °C vertical, with 10 to 95 % humidity without condensation and an altitude up to 2000 m. Immunity to micro-breaks is 10 ms, which matters on weak site supplies.

Documents and quotation

The Schneider Electric datasheet for the this unit is attached on this page, so you can compare the listed values with your design before ordering. Pay attention to the output common current rating there.

To request a quotation for the TM221C40T, send the quantity, delivery destination and any project reference through the RFQ form. Seven Star LLC supplies Schneider Electric automation products in Oman and the GCC as an independent supplier based in Muscat, and we confirm stock status and lead time against your request.

Other Models in the Se M221 Compact Range

Seven Star LLC supplies models from the Se M221 Compact range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric TM221C24T Modicon M221 24 I/O ControllerLogic ControllersView details
Schneider Electric TM221C40T Modicon M221 40 I/O ControllerLogic ControllersYou are viewing this model
Schneider Electric TM221M16RG Modicon M221 16 I/O Relay PLCLogic ControllersView details
Schneider Electric TM221ME16RG M221 16 I/O Ethernet PLCLogic ControllersView details
Datasheets & Documents
  • PDF Datasheet Schneider Electric TM221C40T Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric TM221C40T Modicon M221 40 I/O

Answers from our engineering team on installation, compatibility and integration.

01How many I/O points does the TM221C40T have?
40 in total: 24 digital inputs (4 fast), 16 transistor outputs (2 fast) and 2 analogue inputs at 0–10 V with 10-bit resolution.
02What is the output current per common on the TM221C40T?
Each transistor output is rated 0.5 A and the datasheet gives 4 A maximum per output common.
03Which communication ports does the TM221C40T have?
A mini-B USB 2.0 port, serial 1 (RJ45, RS485) and serial 2 (RJ45, RS232/RS485), running Modbus master/slave or SoMachine-Network. There is no Ethernet port.
04What power does the TM221C40T consume?
4.1 W at 24 V without expansion modules and 16 W with the maximum number of expansion modules, with an inrush current of 35 A.
05How wide is the TM221C40T?
160 mm wide by 90 mm high by 70 mm deep, weighing 0.456 kg, for DIN-rail or panel mounting.