Schneider Electric TM221ME16RG M221 16 I/O Ethernet PLC

Description

TM221ME16RG: Modicon M221 16-I/O relay controller with Ethernet

The TM221ME16RG combines the compact 16-point M221 relay controller with a built-in 10/100 Ethernet port. It offers eight 24 V DC inputs, eight normally open relay outputs rated 2 A, two 0–10 V analogue inputs, one RJ45 serial line, USB and Ethernet, all in a 70 mm wide housing with pluggable spring terminals.

Its twin on the I/O side is TM221M16RG; the difference is the communication block. TM221ME16RG gives up the second serial port and gains an Ethernet RJ45 that runs Modbus TCP and EtherNet/IP adapter services, so it can join a plant network directly. Seven Star LLC supplies the TM221ME16RG in Oman and the GCC as an independent supplier based in Muscat.

Ethernet capabilities of the TM221ME16RG

The Ethernet port is 10BASE-T/100BASE-TX over copper cable up to 100 m. The datasheet lists these services: EtherNet/IP adapter, Modbus TCP client, Modbus TCP server, Modbus TCP slave device and DHCP client. Front LEDs show Ethernet link (yellow) and activity (green).

A server function lets a SCADA system or HMI read and write controller data without a gateway, while the client function allows the controller to poll a meter, drive or remote I/O. The datasheet does not list a web server or OPC UA on this model, so do not specify those features for it.

Technical specifications of the TM221ME16RG

Parameter Specification
Manufacturer / part number Schneider Electric / TM221ME16RG
Range of product Modicon M221
Product type Logic controller
Rated supply voltage 24 V DC, limits 20.4–28.8 V
Inrush current 35 A
Discrete inputs 8, IEC 61131-2 Type 1, 24 V DC sink or source
Analogue inputs 2 at 0–10 V, 10 bit
Discrete outputs 8 relay, normally open, 2 A, 5–125 V DC or 5–250 V AC
Power consumption 4.3 W at 24 V with no expansion; 23.3 W with maximum expansion
Ethernet 1 port 10BASE-T/100BASE-TX, RJ45, 100 m copper cable
Ethernet services EtherNet/IP adapter; Modbus TCP client, server and slave device; DHCP client
Expansion capability 7 TM3 modules (local I/O) or 14 (remote I/O architecture)
Application memory 256 kB RAM for application and data (10000 instructions); 256 kB flash backup
Execution time 0.2 µs per Boolean instruction; 0.3 ms per 1 K instructions (event and periodic task)
Real-time clock Built in, drift 30 s/month or less at 25 °C
Backup battery BR2032 or CR2032X lithium, 1 year at 25 °C
Optional storage 2 GB SD card
PID regulation Up to 14 simultaneous loops
Connections 1 mini-B USB; serial 1 RJ45 RS232/RS485; 1 Ethernet RJ45
Mounting 35 mm DIN rail (TH35-15 or TH35-7.5) or panel with fixing kit
Dimensions (W x H x D) 70 x 90 x 70 mm
Net weight 0.264 kg
Operating temperature −10 to 55 °C horizontal; −10 to 35 °C vertical
Storage temperature −25 to 70 °C
Humidity 10–95 % without condensation
Protection IP20 with protective cover in place
Shock resistance 98 m/s² for 11 ms
Certifications listed cULus, cULus HazLoc, CE, UKCA, RCM, EAC, ABS, LR, DNV-GL

Relay outputs and inputs of the TM221ME16RG

The eight relay outputs are normally open, 2 A, for 5–125 V DC or 5–250 V AC, with 7 A maximum per common and a response of 10 ms in both directions. The minimum load is 1 mA at 5 V DC. The eight inputs are Type 1 at 24 V DC, sink or source, and four of them are fast inputs for counting up to 100 kHz.

The relay life tables cover AC-12, AC-14, AC-15, DC-12 and DC-13 duties, for example 300000 cycles at 24 V DC and 16 W resistive. Use these when sizing the load rather than assuming the 20 million mechanical figure.

Where the TM221ME16RG suits Oman and GCC projects

A network-ready small controller is useful where each skid must report to a central system: remote pumping stations, desalination dosing skids, ventilation plants and utility buildings. The relay outputs make local wiring simple, and the Ethernet port removes the need for a serial gateway.

Cabinet planning still follows the datasheet: −10 to 55 °C in a horizontal position, −10 to 35 °C vertical, 10 to 95 % humidity without condensation. Approvals listed are cULus, cULus HazLoc, CE, UKCA, RCM, EAC, ABS, LR and DNV-GL.

Serial and USB on the TM221ME16RG

Serial 1 is an RJ45 connector that supports RS232 or RS485, with a 5 V supply of up to 200 mA available on the connector. Transmission rates are 1.2 to 115.2 kbit/s, with 115.2 kbit/s as the default and cable lengths of 15 m for RS485 and 3 m for RS232. USB is a mini-B 2.0 port for the programming terminal.

Because only one serial port is fitted, a design that needs both a Modbus RTU drive network and a separate serial HMI should be checked carefully; the two-serial-port version without Ethernet is TM221M16RG.

Power and capacity of the TM221ME16RG

The controller consumes 4.3 W at 24 V without expansion and 23.3 W with the maximum number of modules. It supports up to seven local TM3 expansion modules, or fourteen with the remote architecture, and supplies the bus with 0.52 A at 5 V and 0.46 A at 24 V. Inrush current is 35 A.

Memory is 256 kB RAM for the application and 256 kB flash for backup, with the optional 2 GB SD card and a one-year BR2032 or CR2032X battery for the clock.

The TM221ME16RG compared with the other M221 references

Bold marks this page.

Reference I/O Output type Width Communication
TM221C24T 24 (14 in / 10 transistor out) Transistor source, 0.5 A 110 mm Two serial ports
TM221C40T 40 (24 in / 16 transistor out) Transistor source, 0.5 A 160 mm Two serial ports
TM221M16RG 16 (8 in / 8 relay out) Relay 2 A, spring terminals 70 mm Two serial ports
TM221ME16RG 16 (8 in / 8 relay out) Relay 2 A, spring terminals 70 mm One serial port + Ethernet

Selection and RFQ checklist for the TM221ME16RG

Before you request a quotation, check:

  • that one serial port plus Ethernet matches your network plan
  • the IP addressing and protocol (Modbus TCP or EtherNet/IP adapter) used by the supervisory system
  • relay loads against the 2 A and 7 A limits
  • the number of TM3 modules and cartridges to be added
  • mounting orientation and cabinet temperature

Send these details along with the quantity and delivery location.

Documents and quotation

The Schneider Electric datasheet for the this unit is attached on this page, so you can compare the listed values with your design before ordering. The Ethernet service list is in the same document.

To request a quotation for the TM221ME16RG, send the quantity, delivery destination and any project reference through the RFQ form. Seven Star LLC supplies Schneider Electric automation products in Oman and the GCC as an independent supplier based in Muscat, and we confirm stock status and lead time against your request.

Other Models in the Se M221 Compact Range

Seven Star LLC supplies models from the Se M221 Compact range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric TM221C24T Modicon M221 24 I/O ControllerLogic ControllersView details
Schneider Electric TM221C40T Modicon M221 40 I/O ControllerLogic ControllersView details
Schneider Electric TM221M16RG Modicon M221 16 I/O Relay PLCLogic ControllersView details
Schneider Electric TM221ME16RG M221 16 I/O Ethernet PLCLogic ControllersYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Schneider Electric TM221ME16RG Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric TM221ME16RG M221 16 I/O Ethernet

Answers from our engineering team on installation, compatibility and integration.

01What is the difference between the TM221ME16RG and TM221M16RG?
Both have 8 inputs and 8 relay outputs. The TM221ME16RG has one serial port plus a 10/100 Ethernet port, while the TM221M16RG has two serial ports and no Ethernet.
02Which Ethernet services does the TM221ME16RG list?
EtherNet/IP adapter, Modbus TCP client, Modbus TCP server, Modbus TCP slave device and DHCP client, on a 10BASE-T/100BASE-TX port.
03What relay rating does the TM221ME16RG have?
Eight normally open relays at 2 A for 5–125 V DC or 5–250 V AC, with a maximum of 7 A per common.
04How many expansion modules can the TM221ME16RG use?
Up to 7 TM3 modules locally or 14 using the remote architecture, with 0.52 A at 5 V and 0.46 A at 24 V available on the bus.
05How much power does the TM221ME16RG need?
4.3 W at 24 V without expansion modules and 23.3 W with the maximum number of modules; supply range 20.4 to 28.8 V DC.