Schneider Electric LC1DT200A6LSE 200 A 4P Contactor
Description
What the LC1DT200A6LSE is and how its four-pole body is arranged
The LC1DT200A6LSE is a Schneider Electric four-pole TeSys Deca contactor, listed in the datasheet as Contactor Deca 200A 4P 200-500V ACDC Lug. It carries 200 A in AC-1 at up to 440 V and uses a 200 to 500 V AC/DC coil with lugs-ring or bars power terminals. Seven Star LLC supplies the LC1DT200A6LSE in Oman and the GCC as an independent supplier based in Muscat.
The reference reads as LC1D (TeSys Deca), T200 (the four-pole 200 A body, as the datasheet title 4P(4NO), 200 A confirms) and A6LSE. Within it, LSE is the coil group, here 200-500 V AC/DC, and the presence of A6 marks the connection variant: the datasheet title for this reference ends with lugs-ring or bars.
The body measures 152 mm x 134 mm x 155 mm and weighs 2.6 kg, plate mounting only, which makes it a panel-wall device rather than a rail contactor.
Technical specifications of the LC1DT200A6LSE
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / LC1DT200A6LSE |
| Description | Contactor Deca 200A 4P 200-500V ACDC Lug |
| Range | TeSys Deca Advanced |
| Poles / contact composition | 4P / 4 NO |
| Contactor application | Resistive load |
| Utilisation categories | AC-3; AC-3e; AC-1; AC-4; DC-1; DC-3; DC-5 |
| Rated operational voltage | Power circuit: <= 1000 V AC 16.67 to 400 Hz; Power circuit: <= 300 V DC |
| Rated operational current AC-1 | 200 A (below 60 °C) at up to 440 V AC |
| Control circuit voltage | 200 to 500 V AC 50/60 Hz; 200 to 500 V DC |
| Control circuit type | AC at 50/60 Hz; DC |
| Rated breaking capacity | 1100 A at 440 V for power circuit |
| Associated gG fuse (power / control) | 315 A / 0.5 A |
| Rated impulse withstand | 8 kV |
| Mechanical durability | 8 Mcycles |
| Electrical durability | 0.38 Mcycles 200 A AC-1 at Ue <= 440 V |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Inrush / hold-in power | 170 VA (120 W) / 16.5 VA (5.1 W) |
| Operating time | 10 to 80 ms opening; 20 to 90 ms closing |
| Power connection | Power circuit: lugs-ring terminals – external diameter: 25 mm; Power circuit: bars 1 – busbar cross section: 5 x 25 mm; Power circuit: bars 2 – busbar cross section: 5 x 25 mm |
| Mounting | Plate |
| Ambient temperature around the device | -40 to 60 °C operation |
| Dimensions H x W x D | 152 mm x 134 mm x 155 mm |
| Net weight | 2.6 kg |
| Certifications listed | CB Scheme; CCC cULus; CE; UKCA; EU-RO-MR by DNV-GL |
Load categories and motor ratings of the LC1DT200A6LSE
| Supply voltage (AC) | Motor power in AC-3 (kW) |
|---|---|
| 230 V | 30 kW |
| 400 V | 55 kW |
| 415 V | 59 kW |
| 440 V | 59 kW |
| 500 V | 75 kW |
| 690 V | 80 kW |
| 1000 V | 65 kW |
The datasheet lists utilisation categories AC-3; AC-3e; AC-1; AC-4; DC-1; DC-3; DC-5. The contactor application field reads resistive load, and the headline rating is 200 A in AC-1, so the natural use is heaters, resistive banks and distribution switching rather than frequent motor starting. As a motor contactor the datasheet still gives 55 kW at 400 V in AC-3, 75 kW at 500 V and 80 kW at 690 V.
Four normally open poles allow a three-phase load with a switched neutral, or two circuits switched together. The DC categories DC-1, DC-3 and DC-5 are listed, with the power circuit rated up to 300 V DC. DC switching needs the contact configuration and series wiring from the manufacturer’s tables, so do not assume the 200 A AC rating carries over unchanged.
Control supply, inrush and coil limits of the LC1DT200A6LSE
The coil accepts 200 to 500 V AC 50/60 Hz; 200 to 500 V DC, which suits high control voltages, including 380 V to 415 V phase-to-phase AC control and 220 V DC, when the coil is fed straight from the supply. Operating limits are 0.8 times the minimum Uc to 1.1 times the maximum Uc, so for this version the contactor should be fed between about 160 V and 550 V; drop-out is at or below 0.1 Uc maximum, which means the coil releases only when the control voltage has collapsed almost to zero.
Inrush is 170 VA or 120 W and hold-in 16.5 VA or 5.1 W, with heat dissipation of 3 W at 20 °C. The datasheet gives closing in 20 to 90 ms and opening in 10 to 80 ms; that opening range is wide, so interlocks that rely on very fast drop-out need a time margin. The coil carries a built-in bidirectional peak limiting diode suppressor, which reduces switching surges. Control-circuit protection is stated as 0.5 A gG, a figure that differs between the coil ranges of this series.
As a sizing aid, dividing the DC power figures by voltage gives roughly 0.55 A inrush and 0.023 A hold-in at 220 V DC, and 0.30 A and 0.013 A at 400 V. These are calculated approximations, not datasheet values. With control voltages this high, the coil circuit needs line-voltage insulation practices and fusing.
Terminal style and cabling for the LC1DT200A6LSE
This is the lug version. The datasheet gives ring lugs of up to 25 mm external diameter and bars of 5 x 25 mm, with a tightening torque of 12 N.m on the M8 hexagonal screw head (13 mm). That is the right choice for heavy cable terminations with crimped lugs or for busbar-fed panels, and the body is 134 mm wide and 2.6 kg.
Control wiring is the same on both versions: screw clamp terminals up to 4 mm² flexible, tightened at 1.7 N.m. The LC1DT200A6LSE is plate mounted. Check that the power cable bend radius and the busbar or lug spacing are compatible with the enclosure before choosing the style.
Fuse sizing, contact life and certifications for the LC1DT200A6LSE
The datasheet recommends a 315 A gG fuse at up to 690 V on the power circuit. The rated breaking capacity is 1100 A at 440 V for power circuit and the 10 s short-time withstand current is 1280 A. Impulse withstand is 8 kV and the insulation voltage 1000 V for the power circuit.
Mechanical durability is 8 Mcycles and electrical durability 0.38 Mcycles 200 A AC-1 at Ue <= 440 V. Maximum operating rate is 2400 cycles per hour at 60 °C, lower than the 3600 of the smaller LC1D frames. The certifications listed are CB Scheme; CCC cULus; CE; UKCA; EU-RO-MR by DNV-GL; check which approval the project needs against this exact reference.
The datasheet gives the ambient range around the device as -40 to 60 °C operation and an operating altitude of up to 3000 m without derating; the front face is IP20 front face conforming to IEC 60529.
The LC1DT200 family: where the LC1DT200A6LSE fits and what to send
The same four-pole 200 A contactor is offered in four coil ranges and, in the references we handle, two terminal styles. The table lists those relatives of the LC1DT200A6LSE; the power circuit rating is identical and the choice is made on control voltage and cable termination.
| Reference | Coil range | Power terminals | Width | Weight |
|---|---|---|---|---|
| LC1DT200A6BNE | 24 to 60 V AC/DC | Lugs / bars | 134 mm | 2.6 kg |
| LC1DT200A6EHE | 48 to 130 V AC/DC | Lugs / bars | 134 mm | 2.6 kg |
| LC1DT200A6KUE | 100 to 250 V AC/DC | Lugs / bars | 134 mm | 2.6 kg |
| LC1DT200A6LSE | 200 to 500 V AC/DC | Lugs / bars | 134 mm | 2.6 kg |
| LC1DT200ABNE | 24 to 60 V AC/DC | EverLink connector | 132 mm | 3 kg |
| LC1DT200AEHE | 48 to 130 V AC/DC | EverLink connector | 132 mm | 3 kg |
| LC1DT200AKUE | 100 to 250 V AC/DC | EverLink connector | 132 mm | 3 kg |
If the control supply is 200 to 500 V the LC1DT200A6LSE is the match. For other control voltages, look at LC1DT200A6BNE, LC1DT200A6EHE, LC1DT200A6KUE and related references; for the other connection style swap the A6 marking. Confirm each against its own datasheet.
Checklist for the RFQ:
- Load: resistive or distribution load up to 200 A AC-1, or a motor up to 55 kW at 400 V AC-3 as in the datasheet; DC duty only after checking the manufacturer’s DC tables.
- Control voltage: 200 to 500 V AC/DC for this reference, with the 0.8 to 1.1 operating window.
- Terminals: ring lugs up to 25 mm or 5 x 25 mm bars; plate mounting, 152 mm x 134 mm x 155 mm.
- Protection: 315 A gG on the power circuit and 0.5 A gG on the control circuit.
- Quantity, new or replacement, and the cable or busbar size you plan to use, sent together with the part number.
Installation and commissioning of the LC1DT200A6LSE
Fix the LC1DT200A6LSE on a rigid plate with the clearances of the installation sheet; the body is 152 mm x 134 mm x 155 mm. Torque the power terminals to 12 N.m, check that no stray strands or lugs touch neighbouring poles and fit the protective cover supplied with the unit.
The datasheet lists lug or bar power terminals and plate mounting only; allow room for the cable bend and for the control wiring above the coil.
Typical applications of the LC1DT200A6LSE in Oman and the GCC
Four-pole 200 A contactors of this type are used for heater banks, process heating, large lighting and distribution circuits, switchgear changeover and heavy motor feeders in oil and gas, power and water facilities across Oman and the GCC.
With operation listed from -40 to 60 °C and up to 3000 m, the LC1DT200A6LSE fits outdoor-grade cabinets that see high summer temperatures, as long as the enclosure keeps dust and humidity out; the front face itself is only IP20.
Documents and quotation
A datasheet for the LC1DT200A6LSE is attached on this page, listing the electrical, mechanical and environmental data used above. Send us the part number, quantity and application and we will confirm availability and a quotation.
Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.
Other Models in the Se Lc1dt200 Range
Seven Star LLC supplies models from the Se Lc1dt200 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric LC1DT200A6BNE 200 A 4P Contactor | Contactors & Overload Relays | View details |
| Schneider Electric LC1DT200A6EHE 200 A 4P Contactor | Contactors & Overload Relays | View details |
| Schneider Electric LC1DT200A6KUE 200 A 4P Contactor | Contactors & Overload Relays | View details |
| Schneider Electric LC1DT200A6LSE 200 A 4P Contactor | Contactors & Overload Relays | You are viewing this model |
Datasheets & Documents
- Datasheet Schneider Electric LC1DT200A6LSE Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric LC1DT200A6LSE 200 A 4P Contactor
Answers from our engineering team on installation, compatibility and integration.
01What is the rated current of the LC1DT200A6LSE?
The datasheet lists 200 A in AC-1 at up to 440 V AC below 60 °C; the AC-3 motor rating is 55 kW at 400 V.
02What coil does the LC1DT200A6LSE use?
The control circuit voltage is 200 to 500 V AC 50/60 Hz; 200 to 500 V DC. The coil is built for AC or DC control with a built-in peak limiting diode suppressor.
03How is the LC1DT200A6LSE mounted?
The datasheet lists mounting on plate. Power and control terminals are accessible from the front with the protective cover fitted.
04What is the electrical life of the LC1DT200A6LSE?
The datasheet states 0.38 Mcycles 200 A AC-1 at Ue up to 440 V and a mechanical durability of 8 Mcycles. Real life depends on the load category and switching rate.
05What fuse protects the LC1DT200A6LSE?
The datasheet gives 315 A gG at up to 690 V on the power circuit. Follow the coordination table for the motor and overload relay in use.


















Reviews