Brand: Schneider Electric
Schneider Electric LC1D50AP7 50 A TeSys Deca Contactor
Description
What the LC1D50AP7 is and how the reference reads
The LC1D50AP7 is a Schneider Electric TeSys Deca contactor that the datasheet describes as TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 50 A – 230 V AC 50/60 Hz coil. The 50 A reference uses the same 122 x 55 x 120 mm housing as the 40 A and 65 A versions, with a net weight of 0.855 kg, and is rated 50 A in AC-3 and 80 A in AC-1. Seven Star LLC supplies the LC1D50AP7 in Oman and the GCC as an independent supplier based in Muscat.
The code breaks down as LC1D (three-pole TeSys Deca contactor), 50A (the 50 A frame) and P7 (the coil version). The coil row of the datasheet states 230 V AC 50/60 Hz, which is how the suffix should be understood for this reference.
Rated at 22 kW at 380/400 V, it is the mid-point of the three medium-frame ratings. Its AC-1 rating of 80 A equals that of the 65 A reference, so for pure resistive duty the choice between them is a matter of availability rather than capability.
Technical specifications of the LC1D50AP7
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / LC1D50AP7 |
| Description | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 50 A – 230 V AC 50/60 Hz coil |
| Range | TeSys Deca Advanced |
| Device short name | LC1D |
| Poles / contact composition | 3P / 3 NO |
| Contactor application | Motor control; Resistive load |
| Utilisation categories | AC-3; AC-3e; AC-1; AC-4 |
| Rated operational voltage | Power circuit: <= 690 V AC 25 to 400 Hz; Power circuit: <= 300 V DC |
| Rated operational current AC-3 (≤440 V) | 50 A (below 60 °C) |
| Rated operational current AC-1 | 80 A at up to 440 V AC (below 60 °C) |
| Control circuit voltage | 230 V AC 50/60 Hz |
| Rated breaking capacity | 900 A at 440 V for power circuit |
| Associated gG fuse, coordination type 1 / type 2 | 100 A / 100 A |
| Rated insulation voltage Ui / impulse Uimp | 690 V / 6 kV |
| Mechanical durability | 6 Mcycles |
| Electrical durability | 1.45 million cycles at 50 A in AC-3 and 1.1 million cycles at 80 A in AC-1 (Ue up to 440 V) |
| Coil technology | Without built-in suppressor module |
| Inrush / hold-in power (50 Hz) | 160 VA / 15 VA |
| Operating time | 4 to 19 ms opening; 12 to 26 ms closing |
| Auxiliary contacts | 1 NO + 1 NC |
| Mounting | Plate; Rail |
| Ingress protection | IP20 front face conforming to IEC 60529 |
| Ambient temperature around the device | -40 to 60 °C |
| Dimensions H x W x D | 122 mm x 55 mm x 120 mm |
| Net weight | 0.855 kg |
| Certifications listed | CCC; UL; CB Scheme; CSA; CE; UKCA; Marine; EAC |
What the LC1D50AP7 can start: AC-3 motor power by voltage
| Supply voltage (AC, 50/60 Hz) | Motor power in AC-3 (kW) |
|---|---|
| 220/230 V | 15 kW |
| 380/400 V | 22 kW |
| 415 V | 25 kW |
| 440 V | 30 kW |
| 500 V | 30 kW |
| 660/690 V | 33 kW |
The table covers direct-on-line starting duty; the datasheet converts the 50 A rating into the motor powers above for each supply voltage. At 380/400 V the LC1D50AP7 is listed for 22 kW. For heavier duty such as inching or plugging the AC-4 category applies and the datasheet lists 11 kW at 400 V, which is lower because those duties wear the contacts faster. The same device is rated 80 A in AC-1, the category for resistive loads such as heaters, so it can switch a higher current when the load is not a motor.
Control voltage behaviour of the LC1D50AP7 on a 230 V AC supply
According to the datasheet the contactor operates between 0.8 and 1.1 times Uc at 50 Hz, which for this coil is about 184 V to 253 V, and between 0.85 and 1.1 times Uc at 60 Hz (195.5 V to 253 V). Drop-out occurs between 0.3 and 0.6 times Uc, about 69 V to 138 V, which is the range to remember when a weak control supply makes the contactor chatter instead of opening cleanly.
The coil of the LC1D50AP7 is rated 230 V AC at 50/60 Hz. That fits a 230 V control supply, close to the nominal single-phase level on 400 V three-phase systems, so the coil can usually be fed straight from a phase-neutral circuit.
Inrush is 160 VA at 50 Hz (140 VA at 60 Hz) and hold-in is 15 VA (13 VA at 60 Hz). Dividing by the coil voltage gives roughly 0.70 A on closing and 0.07 A when held; these are calculated approximations for sizing the control transformer or PLC interposing relay, not datasheet figures. The datasheet gives closing in 12 to 26 ms and opening in 4 to 19 ms.
The coil is described as without built-in suppressor module, so inductive switching of the coil can disturb sensitive electronics on the same control circuit unless a suppressor is added separately; check accessory compatibility with the supplier before ordering one.
Short-circuit data and contact life for the LC1D50AP7
Contact life is stated as 6 Mcycles mechanically and, electrically, 1.45 million cycles at 50 A in AC-3 and 1.1 million cycles at 80 A in AC-1 (Ue up to 440 V). The maximum operating rate is 3600 cyc/h at 60 °C. For functional-safety calculations the datasheet gives a B10d of 1,369,863 cycles at nominal load and 20,000,000 cycles at mechanical load, per EN/ISO 13849-1.
The auxiliary block built into the LC1D50AP7 is 1 NO + 1 NC; the datasheet notes the contacts are mechanically linked and that the NC is a mirror contact to IEC 60947-4-1, so it can be used in a safety circuit to prove that the main contacts have opened. The signalling circuit is specified for a minimum of 17 V and 5 mA.
For short-circuit protection the datasheet pairs the LC1D50AP7 with a 100 A gG fuse at up to 690 V for coordination type 1 and 100 A gG for type 2. Type 2 is the stricter level: the contactor must remain usable after a fault, with at most light welds that can be separated. The rated breaking capacity is 900 A at 440 V for power circuit and the short-time withstand current is listed as 400 A 40 °C – 10 s for the power circuit.
Frame comparison around the LC1D50AP7
Other coil versions of the same frame that we handle are LC1D50AB7, LC1D50AF7, LC1D50AU7; they carry the same power circuit and differ only in the coil voltage. Because the dimensions match the neighbouring ratings, an uprate from 50 A to 65 A inside the same cabinet normally needs no mounting changes, but the power terminals and overload relay must be rechecked.
| Frame | AC-3 current | AC-3 kW at 380/400 V | AC-1 current | Body H x W x D | Net weight | Mechanical life |
|---|---|---|---|---|---|---|
| LC1D40A.. | 40 A | 18.5 kW | 60 A | 122 x 55 x 120 mm | 0.85 kg | 6 Mcycles |
| LC1D50A (this frame) | 50 A | 22 kW | 80 A | 122 x 55 x 120 mm | 0.855 kg | 6 Mcycles |
| LC1D65A.. | 65 A | 30 kW | 80 A | 122 x 55 x 120 mm | 0.86 kg | 6 Mcycles |
Typical loads are 22 kW pumps, medium compressors, cooling-tower fans and conveyor drives.
Choosing the LC1D50AP7: checklist and RFQ details
| Question | What the datasheet tells you |
|---|---|
| Which load? | 50 A AC-3, 80 A AC-1 |
| Which control supply? | 230 V AC (limits above) |
| How much room? | 122 mm x 55 mm x 120 mm, 0.855 kg |
| How is it protected? | 100 A gG type 1 / 100 A type 2 |
| What else is needed? | Overload relay, auxiliary blocks, quantity |
When you send an RFQ, include the part number, quantity, control voltage, the motor or load data, and whether you want the unit for a new panel or to replace an installed LC1D contactor.
Commissioning the LC1D50AP7 step by step
Commissioning starts with the control circuit. Energise the 230 V AC coil at the supply you will actually have in service, and confirm that the contactor closes at the lower operating limit of about 184 V and drops out cleanly. Then check the power-terminal torque of 2.5, 5, 8 N.m, measure phase rotation to the motor, and test the overload relay trip circuit. Ambient around the device is listed as -40 to 60 °C, so confirm the panel temperature during summer load.
Where the LC1D50AP7 earns its place in Gulf plants
Oil and gas facilities, power stations and petrochemical plants use contactors of this size for auxiliary drives: lube-oil pumps, ventilation, dosing, sump and transfer pumps. The LC1D50AP7 suits designs that need a 230 V AC control voltage and a compact body. The datasheet lists marine and other certifications for the reference (see the table), but confirm the approval required by the project against the exact reference.
For OEM skid builders exporting to the GCC, a 230 V AC coil on a 50 A contactor keeps spares uniform across machines. Panel builders in the region also use the LC1D50AP7 for motor control centres where a standard contactor frame simplifies spare-part stocking.
Documents and quotation
A datasheet for the LC1D50AP7 is attached on this page, listing the electrical, mechanical and environmental data used above. Send us the part number, quantity and application and we will confirm availability and a quotation.
Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.
Other Models in the Se Lc1d 50 Range
Seven Star LLC supplies models from the Se Lc1d 50 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric LC1D50AB7 50 A TeSys Deca Contactor | Contactors & Overload Relays | View details |
| Schneider Electric LC1D50AF7 50 A TeSys Deca Contactor | Contactors & Overload Relays | View details |
| Schneider Electric LC1D50AP7 50 A TeSys Deca Contactor | Contactors & Overload Relays | You are viewing this model |
Datasheets & Documents
- Datasheet Schneider Electric LC1D50AP7 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric LC1D50AP7 50 A TeSys Deca
Answers from our engineering team on installation, compatibility and integration.
01What is the rated current of the LC1D50AP7?
The datasheet lists 50 A in AC-3 and 80 A in AC-1 at up to 440 V AC, both for operation below 60 °C.
02What coil does the LC1D50AP7 use?
The control circuit voltage is 230 V AC 50/60 Hz. It is an AC coil for 50/60 Hz without a built-in suppressor module.
03What are the dimensions and weight of the LC1D50AP7?
The datasheet gives 122 mm high, 55 mm wide and 120 mm deep, with a net weight of 0.855 kg.
04How is the LC1D50AP7 mounted?
The datasheet lists mounting on plate or rail. Power and control terminals are accessible from the front with the protective cover fitted.
05What is the electrical life of the LC1D50AP7?
The datasheet states 1.45 million cycles at 50 A in AC-3 and 1.1 million cycles at 80 A in AC-1 (Ue up to 440 V) and a mechanical durability of 6 Mcycles. Real life depends on the load category and switching rate.