Schneider Electric LC1D32P7 32 A TeSys Deca Contactor

Description

LC1D32P7 at a glance: 32 A frame, 230 V AC control

The LC1D32P7 is a Schneider Electric TeSys Deca contactor that the datasheet describes as TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 32 A – 230 V AC 50/60 Hz coil. The 32 A reference shares the 85 x 45 x 92 mm housing with the 25 A and 38 A versions, so panel layouts do not change when the AC-3 rating steps up; the datasheet gives 32 A in AC-3 and 50 A in AC-1. Seven Star LLC supplies the LC1D32P7 in Oman and the GCC as an independent supplier based in Muscat.

Three parts make up LC1D32P7: the LC1D family prefix, the size marker 32 for the 32 A class, and the suffix P7 that identifies the coil. The control-voltage line of the datasheet reads 230 V AC 50/60 Hz; the pole configuration is 3 NO and the range is listed as TeSys Deca Advanced.

Weight is 0.375 kg and mechanical durability is 15 million cycles, the same as its smaller neighbour, while the AC-3 electrical durability is stated at 1.65 million cycles at 32 A.

Technical specifications of the LC1D32P7

Parameter Specification
Manufacturer / part number Schneider Electric / LC1D32P7
Description TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 32 A – 230 V AC 50/60 Hz coil
Range TeSys Deca Advanced
Device short name LC1D
Poles / contact composition 3P / 3 NO
Contactor application Resistive load; Motor control
Utilisation categories AC-3; AC-3e; AC-1
Rated operational voltage Power circuit: <= 690 V AC 25 to 400 Hz; Power circuit: <= 300 V DC
Rated operational current AC-3 (≤440 V) 32 A (below 60 °C)
Rated operational current AC-1 50 A at up to 440 V AC (below 60 °C)
Control circuit voltage 230 V AC 50/60 Hz
Rated breaking capacity 550 A at 440 V for power circuit
Associated gG fuse, coordination type 1 / type 2 63 A / 63 A
Rated insulation voltage Ui / impulse Uimp 690 V / 6 kV
Mechanical durability 15 Mcycles
Electrical durability 1.65 million cycles at 32 A in AC-3 and 1.4 million cycles at 50 A in AC-1 (Ue up to 440 V)
Coil technology Without built-in suppressor module
Inrush / hold-in power (50 Hz) 70 VA / 7 VA
Operating time 4 to 19 ms opening; 12 to 22 ms closing
Auxiliary contacts 1 NO + 1 NC
Mounting Rail; Plate
Ingress protection IP20 front face conforming to IEC 60529
Ambient temperature around the device -40 to 60 °C
Dimensions H x W x D 85 mm x 45 mm x 92 mm
Net weight 0.375 kg
Certifications listed UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme

AC-3, AC-4 and AC-1 ratings of the LC1D32P7

Supply voltage (AC, 50/60 Hz) Motor power in AC-3 (kW)
220/230 V 7.5 kW
380/400 V 15 kW
415/440 V 15 kW
500 V 18.5 kW
660/690 V 18.5 kW

Because AC-3 describes ordinary starting and stopping, the datasheet converts the 32 A rating into the motor powers above for each supply voltage. At 380/400 V the LC1D32P7 is listed for 15 kW. For heavier duty such as inching or plugging the AC-4 category applies and the datasheet lists 7.5 kW at 400 V, which is lower because those duties wear the contacts faster. The same device is rated 50 A in AC-1, the category for resistive loads such as heaters, so it can switch a higher current when the load is not a motor.

Powering the 230 V AC coil of the LC1D32P7

Inrush is 70 VA at 50 Hz (70 VA at 60 Hz) and hold-in is 7 VA (7.5 VA at 60 Hz). Dividing by the coil voltage gives roughly 0.30 A on closing and 0.03 A when held; these are calculated approximations for sizing the control transformer or PLC interposing relay, not datasheet figures. The datasheet gives closing in 12 to 22 ms and opening in 4 to 19 ms.

The coil of the LC1D32P7 is rated 230 V AC at 50/60 Hz. That fits a 230 V control supply, close to the nominal single-phase level on 400 V three-phase systems, so the coil can usually be fed straight from a phase-neutral circuit.

According to the datasheet the contactor operates between 0.8 and 1.1 times Uc at 50 Hz, which for this coil is about 184 V to 253 V, and between 0.85 and 1.1 times Uc at 60 Hz (195.5 V to 253 V). Drop-out occurs between 0.3 and 0.6 times Uc, about 69 V to 138 V, which is the range to remember when a weak control supply makes the contactor chatter instead of opening cleanly.

The coil is described as without built-in suppressor module, so inductive switching of the coil can disturb sensitive electronics on the same control circuit unless a suppressor is added separately; check accessory compatibility with the supplier before ordering one.

Fuses, durability and auxiliary contact of the LC1D32P7

The auxiliary block built into the LC1D32P7 is 1 NO + 1 NC; the datasheet notes the contacts are mechanically linked and that the NC is a mirror contact to IEC 60947-4-1, so it can be used in a safety circuit to prove that the main contacts have opened. The signalling circuit is specified for a minimum of 17 V and 5 mA.

For short-circuit protection the datasheet pairs the LC1D32P7 with a 63 A gG fuse at up to 690 V for coordination type 1 and 63 A gG for type 2. Type 2 is the stricter level: the contactor must remain usable after a fault, with at most light welds that can be separated. The rated breaking capacity is 550 A at 440 V for power circuit and the short-time withstand current is listed as 60 A 40 °C – 10 min for power circuit for the power circuit.

Contact life is stated as 15 Mcycles mechanically and, electrically, 1.65 million cycles at 32 A in AC-3 and 1.4 million cycles at 50 A in AC-1 (Ue up to 440 V). The maximum operating rate is 3600 cyc/h at 60 °C. For functional-safety calculations the datasheet gives a B10d of 1,369,863 cycles at nominal load and 20,000,000 cycles at mechanical load, per EN/ISO 13849-1.

LC1D32P7 compared with the neighbouring LC1D ratings

The same coil letters appear on the 25 A and 38 A references, so a plant that standardises on one control voltage can keep one coil code across three current ratings. Other coil versions of the same frame that we handle are LC1D32B7, LC1D32F7, LC1D32M7, LC1D32U7; they carry the same power circuit and differ only in the coil voltage.

Frame AC-3 current AC-3 kW at 380/400 V AC-1 current Body H x W x D Net weight Mechanical life
LC1D25.. 25 A 11 kW 40 A 85 x 45 x 92 mm 0.37 kg 15 Mcycles
LC1D32 (this frame) 32 A 15 kW 50 A 85 x 45 x 92 mm 0.375 kg 15 Mcycles
LC1D38.. 38 A 18.5 kW 50 A 85 x 45 x 92 mm 0.38 kg 15 Mcycles

The 15 kW rating at 380/400 V places it in the range of circulation pumps, supply and exhaust fans, screw compressors of modest size and mixer drives.

Before you order the LC1D32P7

Before asking for a quote, settle three things. First the load: the LC1D32P7 carries 32 A in AC-3 and 50 A in AC-1, so compare your motor full-load current at the actual supply voltage. Second the control voltage, which is 230 V AC here. Third the panel: 85 mm x 45 mm x 92 mm and 0.375 kg, rail or plate mounting.

Add to the RFQ the part number, quantity, the overload relay and fuse you plan to use, any auxiliary blocks, and whether this is a replacement. With that we can confirm availability and lead time quickly.

Keeping the LC1D32P7 in service

Maintenance on the LC1D32P7 is mostly observation: discolouration, a buzzing coil, loose power terminals or dust on the armature face. In a hot and dusty plant room, vacuum rather than blow compressed air into the unit. Re-torque the power terminals to 2.5 N.m at the first scheduled outage, keep a spare coil-compatible contactor for critical motors and note that IP degree is IP20 front face conforming to IEC 60529, so the enclosure provides the real protection.

Field use of the LC1D32P7 across the region

For OEM skid builders exporting to the GCC, a 230 V AC coil on a 32 A contactor keeps spares uniform across machines. Panel builders in the region also use the LC1D32P7 for motor control centres where a standard contactor frame simplifies spare-part stocking.

In Oman and the GCC the LC1D32P7 is typically found in MCC buckets and local starter panels for water and desalination pumps, HVAC fans and cooling-water circuits. Summer panel temperatures make the ambient limit in the datasheet relevant: operation is listed from -40 to 60 °C, with derating between 60 and 70 °C. The 15 kW class matches the pump and fan motors found on utility and building services.

Documents and quotation

A datasheet for the LC1D32P7 is attached on this page, listing the electrical, mechanical and environmental data used above. Send us the part number, quantity and application and we will confirm availability and a quotation.

Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.

Other Models in the Se Lc1d 32 Range

Seven Star LLC supplies models from the Se Lc1d 32 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric LC1D32B7 32 A TeSys Deca ContactorContactors & Overload RelaysView details
Schneider Electric LC1D32F7 32 A TeSys Deca ContactorContactors & Overload RelaysView details
Schneider Electric LC1D32M7 32 A TeSys Deca ContactorContactors & Overload RelaysView details
Schneider Electric LC1D32P7 32 A TeSys Deca ContactorContactors & Overload RelaysYou are viewing this model
Schneider Electric LC1D32U7 32 A TeSys Deca ContactorContactors & Overload RelaysView details
Datasheets & Documents
  • PDF Datasheet Schneider Electric LC1D32P7 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric LC1D32P7 32 A TeSys Deca

Answers from our engineering team on installation, compatibility and integration.

01What is the rated current of the LC1D32P7?
The datasheet lists 32 A in AC-3 and 50 A in AC-1 at up to 440 V AC, both for operation below 60 °C.
02What coil does the LC1D32P7 use?
The control circuit voltage is 230 V AC 50/60 Hz. It is an AC coil for 50/60 Hz without a built-in suppressor module.
03Does the LC1D32P7 have auxiliary contacts?
The datasheet lists 1 NO + 1 NC, mechanically linked, with the NC acting as a mirror contact to IEC 60947-4-1.
04What ambient temperature is allowed for the LC1D32P7?
The permissible ambient around the device is -40 to 60 °C. Operating altitude is 0 to 3000 m.
05Which certifications does the LC1D32P7 list?
The datasheet lists UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme. Always confirm the approval needed by your project against the exact reference.