Brand:

Pepperl+Fuchs KFD2-EB2 Power Feed Module for Power Rail

Description

KFD2-EB2 power feed module for the K-System Power Rail

The KFD2-EB2 supplies the Universal Power Rail of the K-System with 24 V DC at up to 4 A and monitors the rail for faults. Every isolator clipped onto the rail takes its supply from it, and the module reports a collective fault from any connected device through a relay output. It is the supply and diagnostic heart of a rail-based isolator installation.

Seven Star LLC supplies the KFD2-EB2 in Oman and the GCC as an independent supplier in Muscat. The following sections explain what the module does, how it is rated and what to check when sizing a rail.

KFD2-EB2 designation

The KFD2-EB2 is a type designation of the Pepperl+Fuchs K-System, named in the datasheet as a power feed module, an interface for the Power Rail. The 20 mm housing holds a replaceable 5 AT fuse and two terminal groups for supply input. The datasheet states that the module is compatible with all versions of the Power Rail.

From a safety point of view, the module has no dangerous failures; the safe state of the supplied isolators is the de-energized state, so the module does not influence the SIL calculation of the loops on the rail.

Technical specifications of the KFD2-EB2

Parameter Specification
Manufacturer / part number Pepperl+Fuchs / KFD2-EB2
Function Power feed module for Power Rail with collective fault relay
Supply input 20 … 30 V DC, terminals 11+, 12- or 8+, 9-
Output to rail Max. 4 A; output voltage Ui ≥ rated voltage Ur = Ui – 0.6 V
Fuse 5 AT / 250 V AC; recommended utilization max. 80 %
Power dissipation ≤ 1 W
Fault signal relay NO contact (reversible by switch S1 to NC); 30 V AC / 2 A / cos φ ≥ 0.7; 40 V DC / 2 A
Delay approx. 20 ms energized / de-energized
Indicators Green LED power, red LED fault
Ambient temperature -40 … 70 °C
Hazardous-area marking II 3G Ex ec nC IIC T4 Gc, certificate UL 22 ATEX 2853 X; IECEx UL 16.0051X
Other approvals listed FM 22 US 0031 X, UL E106378, CSA 1051840
Housing Type B2, 20 x 119 x 115 mm, approx. 100 g, 35 mm DIN rail, IP20

How the KFD2-EB2 feeds and monitors the rail

The module takes 24 V DC from the plant supply, passes it through a replaceable fuse to the three-conductor rail insert, and so supplies every connected isolator through the rail contacts. Two of the three conductors carry the supply, the third carries the collective error signal. Each isolator on the rail can pull this line low when it detects a fault, such as a lead break, and the feed module converts that into a relay contact for the control system.

The relay can be configured for normally-open or normally-closed operation with switch S1. A green LED shows power and a red LED lights during a fault. The maximum rated operating voltage of the isolators on the rail must not be exceeded by the supply.

The 4 A output limit means that the total current of all modules on the rail must be added up. With the 80 % utilization recommendation for the fuse, the practical design limit is around 3.2 A on one feed module, which can be split by placing several feed modules on separate rail sections with an insulation spacer.

Rail design with the KFD2-EB2

A rail section such as the UPR-03 carries up to 4 A. Segments can be separated with UPR-I insulation spacers if different supplies or different fault zones are wanted. All K-System modules that list Power Rail supply, for example the KFD2-STC5-1, KFD2-USC-1.D and KCD2-SR-2 on this site, can be fed through the same module.

The datasheet indicates that the combination of K-System modules and the rail can be mounted in Zone 2, which is why this module carries an Ex ec nC marking.

Selection and ordering checklist for the KFD2-EB2

  • Add up the supply currents of all modules on the rail and stay below 4 A (80 % fuse utilization)
  • Decide on fault relay logic: NO or NC
  • Check the supply voltage range and the maximum voltage rating of the rail modules
  • Check approvals and marking required for the area
  • Plan rail separation with insulation spacers if needed
  • Provide spare fuses

Installing the KFD2-EB2

Mount the module at the end of the rail section or in the middle, connect the supply to terminals 8 to 12 and the fault relay to the PLC input. Set switch S1 for the relay logic. Verify the voltage on the rail with a meter and trigger a fault in one of the isolators, for instance by breaking a field loop, to check that the fault relay operates.

Keep spare fuses of the stated type. A blown fuse indicates an overload or short circuit on the rail, which should be traced before replacing it.

Typical applications in Oman and the GCC

Power feed modules form part of nearly every K-System marshalling cabinet in oil and gas, power and desalination plants. Using a rail instead of daisy-chained wiring reduces both wiring time and the risk of a loose supply wire in a cabinet that is subject to vibration or thermal cycling. The -40 to 70 °C range supports cabinets exposed to extreme Gulf summer temperatures.

Power Rail components

From the datasheets.

Part number Description
KFD2-EB2 Power feed module, 4 A, fault relay
UPR-03 Universal Power Rail, 3 conductors, 2 m
UPR-E End cap
UPR-I Insulation spacer

Information to send with an RFQ for the KFD2-EB2

Please include the following.

  • Number of modules on the rail and total current
  • Supply voltage and fault logic
  • Area marking requirement
  • Quantity and delivery date

Documents and quotation

The manufacturer datasheet for the KFD2-EB2 is attached on this page, so the electrical data, terminal assignment and ambient limits quoted above can be checked against the original document before an order is placed.

Seven Star LLC supplies Pepperl+Fuchs products in Oman and the GCC as an independent supplier in Muscat. Send the quantity, the signal types and the project delivery date, and we will confirm availability and lead time in a written quotation.

Other Models in the Pf Kfd2 Misc Range

Seven Star LLC supplies models from the Pf Kfd2 Misc range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Pepperl+Fuchs KFD2-ER-1.W.LB Conductive Level Switch AmplifierIsolator & BarrierView details
Pepperl+Fuchs KFD2-EB2 Power Feed Module for Power RailIsolator & BarrierYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Pepperl+Fuchs KFD2-EB2 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.

Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.

Pepperl+Fuchs company profile

Founded 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs
Headquarters Mannheim, Germany
Ownership Privately owned (Pepperl+Fuchs SE)
Origins Radio repair workshop that began making replacement transformers
Product families Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures

Milestones

  • 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
  • 1958: The first proximity switch is developed (some company sources say 1959).

Pepperl+Fuchs product families on this page

On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.

Where Pepperl+Fuchs equipment is used

Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.

Pepperl+Fuchs products we list

Family Examples
Isolator & Barrier HiD2030 SMART Transmitter Power Supply w…, KFD2-SR2-Ex2.W K-System Isolated Switch…, KFD2-UT2-Ex2 Universal Temperature Conve…
Industrial Computers Tab-Ex 05 DZ1 WWAN Hazardous Area Tablet, Smart-Ex® 03 DZ2 smartphone for Zone 2/2…
Inductive Proximity Sensors NJ2-12GK-SN NAMUR Inductive Sensor
Power Modules PS1000-A6-24.20 Power Supply 24 VDC 20 A
Photoelectric Sensors R101 Retro-Reflective Photoelectric Sensor
Laser Distance, LiDAR & Radar Sensors R2000 2-D LiDAR Laser Scanner

Ordering Pepperl+Fuchs parts: what we need

Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.

Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.

FAQ

Questions about the Pepperl+Fuchs KFD2-EB2 Power Feed Module for Power

Answers from our engineering team on installation, compatibility and integration.

01How much current can the KFD2-EB2 supply?
Up to 4 A to the Power Rail, protected by a replaceable 5 AT fuse.
02What does the fault relay do?
It signals a collective fault from any isolator on the rail. It can be set as normally open or normally closed with switch S1.
03Does the module affect SIL calculations?
The datasheet states the device provides no dangerous failures, so it does not influence the safety calculation of the supplied isolators.
04Is there an Ex marking?
The datasheet lists II 3G Ex ec nC IIC T4 Gc with certificate UL 22 ATEX 2853 X and IECEx UL 16.0051X.
05What ambient range is permitted?
-40 to 70 degrees C.