Brand:

Danfoss 137H3007 VACON 100 Flow Drive 12 A 380-500 V STO

Description

VACON 100 FLOW 12 A: a pump and fan drive with STO and ATEX thermistor board

Danfoss 137H3007 is a VACON 100 FLOW drive of 12 A in Frame 04, IP21 / NEMA 1, for 380 to 500 V mains. The FLOW type is the version for pumps and fans. Motor power at low overload is 5.5 kW and the continuous current at that rating is 12 A.

The decisive option is in slot E: the store lists an “BJ” board with Safe Torque Off and an ATEX thermistor input. Together with the 3-relay board in slot B this gives the drive the hardware for a safety circuit and for thermistor monitoring of a suitably certified motor. Size is 128 x 328 x 190 mm and mass 6 kg.

Technical specifications

Parameter Specification
Danfoss code number 137H3007
Type code VACON0100-3L-0012-5-FLOW+SEBJ+EMC4+DPAP
Series VACON 100 FLOW
Rated current 12 Amp
Mains voltage 380-500 Vac
Installation DM Drive Module
Enclosure IP21/NEMA1
Frame Frame 04
Dimensions (W x H x D) 128 x 328 x 190 mm
Control panel Graphical Keypad MK01
EMC emission category EMC C4 System Component
Brake chopper No dynamic braking device
Fieldbus (internal) Std protocol,Modbus,N2,BacNet
B-slot board F3,3 Relay board
E-slot board BJ,STO, ATEX therm
Motor power, low overload 5.5 kW
Continuous current, high / low overload 12 A
Default motor frequency 50 Hz def motor freq settings
Language pack UK, DE, FI, SE, IT, FR lang
Net weight 6 kg
EAN = 5715253396347

STO and the ATEX thermistor board

Safe Torque Off removes the torque-producing power without a contactor and is used in safety functions for machines. An ATEX thermistor input lets the drive read the thermistors of an explosion-protected motor and trip when the temperature limit is reached. Both functions need correct wiring and a validated safety concept; the board is only one part of it.

For a motor in a classified area, check the motor certificate, the drive board certificate and the conditions of use together. The operating guide contains the safety information. If this is not clear for your plant, ask a competent engineer before ordering.

Pump-specific setup

The code has no preloaded application. The EMC category is C4 (system component), so check the final installation. The 50 Hz default motor frequency suits the Gulf grid. A brake chopper is not fitted, which is usual for pump loads.

The FLOW version covers multi-pump control and pump-specific functions described in the operating guide AQ298036140958; set them up in the commissioning phase and save the parameters.

If the motor is a certified explosion-protected type, keep the drive outside the hazardous area and wire only the thermistor circuit into it, following the certificate of the motor and the board. Keep the certificates in the plant file. For a non-hazardous pump, the same board still provides an STO function, so the order code can be kept uniform across a mixed fleet.

For repeat purchases of 137H3007, tell us the quantity you expect to use each year and the delivery point in Oman. That helps us to plan the enquiry with the manufacturer channel and to give you a realistic lead time, which we confirm only when we quote.

Ordering notes

Confirm the supply, motor current, safety needs and the required options before ordering. Seven Star LLC is an independent supplier in Muscat and can quote 137H3007. Related drives are listed under AC drives.

Datasheets & Documents
  • PDF Operating Guide Danfoss VACON 100 Wall-mounted Drives Operating Guide AQ298036140958 (manufacturer, unaltered) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Danfoss is the Danish engineering group that makes refrigeration and air-conditioning controls, heating components, variable speed drives and mobile hydraulics. Mads Clausen founded it on 1 September 1933 at his parents' farm in Nordborg on the island of Als, after making his first refrigeration expansion valve in 1932. Nordborg is still the group's headquarters, and Danfoss remains controlled by the Clausen family through the Bitten & Mads Clausen Foundation.

Danfoss company profile

Founded 1 September 1933, Nordborg, Denmark, by Mads Clausen (1905–1966)
First product Thermostatic expansion valve for refrigeration
Headquarters Nordborg, Denmark
Ownership Private; majority controlled by the Bitten & Mads Clausen Foundation and the Clausen family
Size About 42,000 employees (2023)
Business segments Danfoss Climate Solutions (refrigeration, air conditioning and heating), Danfoss Drives (VLT and VACON frequency converters, soft starters), Danfoss Power Solutions (mobile and industrial hydraulics)
Brands in the group VLT, VACON, Eaton Hydraulics (bought 2021), Ikusi radio remote controls

Milestones

  • 1932–1933: First expansion valve; the company is founded in Nordborg.
  • 1939: 26 employees. By the 10th anniversary in 1943 the company has 179.
  • 1950s: Rapid growth turns Nordborg into a Danfoss town with housing and schools for its workforce.
  • 1968: Danfoss launches its VLT frequency converter, one of the first mass-produced AC drives.
  • 2014: Acquisition of the Finnish drives maker Vacon, now the VACON brand.
  • 2021: Acquisition of Eaton's hydraulics business.

Choosing Danfoss products

For solenoid valves, check the operating principle. A direct-operated valve such as EV210B opens even at 0 bar differential pressure. A servo-operated valve such as EV220B needs a minimum differential (typically about 0.3 bar) to open, while an assisted-lift valve such as EV250B works from 0 bar. Coils are ordered separately, so the voltage on the coil (for example 230 V AC or 24 V DC) must match the control circuit. For drives, the VLT family is split by application: FC 51 Micro Drive for small machines, FC 102 HVAC Drive for fans and pumps in buildings, FC 202 AQUA Drive for water, and FC 302 AutomationDrive for demanding industrial duty.

Where Danfoss products are used

In Oman and the GCC, Danfoss drives run pumps, fans and compressors in district cooling plants, water and wastewater stations, desalination and building HVAC. Danfoss pressure switches, transmitters and solenoid valves are built into chillers, refrigeration plants, boilers and hydraulic systems, and AB-QM valves balance chilled-water circuits in large buildings.

Danfoss products we list

Family Examples
Variable speed drives and soft starters VLT Micro Drive FC 51, VLT HVAC Drive FC 102, VLT AQUA Drive FC 202, VLT AutomationDrive FC 302, FC 280, iC2-Micro, VACON NXP, MCD 600 soft starter
Solenoid valves and coils EV220B, EV210B, EV250B, EV225B steam, EVR 25, AM230C coil
Pressure switches and thermostats KP 37, KP 44, RT 200, CS, MBC 5000, KPS 77, RT 101
Pressure transmitters MBS 3000, MBS 5100, MBS 3250, MBS 4251 Ex, AKS 33, DST P92S SIL 2
HVAC and refrigeration valves AB-QM PICV, NovoCon S, AB-PM, AVTA, ICV, TE 5 element

Ordering Danfoss products: what we need

Send the Danfoss code number from the label (for example 032U7115 or 131B0149) or the full drive type code (FC-302P3K0T5...). For drives, add the motor power, supply voltage and any fieldbus option. For valves, add the size, connection, medium and coil voltage. For pressure switches and transmitters, add the range, output and pressure connection.

Facts checked against Danfoss's company history pages and published company data, October 2026.

Frequently Asked Questions

What is Danfoss 137H3007?
A VACON 100 FLOW 12 A drive: 380-500 V, IP21 / NEMA 1, Frame 04, STO and ATEX thermistor board in slot E.
What does the E-slot board provide?
The store lists Safe Torque Off and an ATEX thermistor input.
Is a brake chopper fitted?
No dynamic braking device is listed.
What default frequency is set?
50 Hz.
Which document is included?
The Danfoss VACON 100 wall-mounted drives operating guide AQ298036140958.