- AC Drives
- Industrial Communications
- PLC & I/O Cards
- Vibration Monitoring
- Automation Accessories
- Controllers & Data Acquisition
- Safety Switches & Guard Locking
- CCTV & Security
- Encoders
- Industrial Computers
- HMI Displays
- Motor Soft Starters
- Isolator & Barrier
- Pneumatic Cylinders
- Servo Drives
- Automation Software
- Robotics
- Machine Vision
Brand: ABB
ABB FCAN-01 CANopen Adapter Module for ABB Drives
Description
CANopen control for ABB drives
The FCAN-01 is a CANopen adapter for ABB drives. It is used in mobile machinery, packaging lines and other systems where a CANopen master already coordinates drives, encoders and I/O blocks.
The module connects through a nine-pin D-SUB male connector, X1. The manual states that the 120 ohm bus termination is not built in, so the first and last nodes need external terminators, a detail that is often overlooked during commissioning.
Technical specifications
| Parameter | Specification |
|---|---|
| Type designation | FCAN-01 |
| Function | CANopen slave adapter |
| Connector | 9-pin D-SUB male, X1 |
| Bus termination | 120 ohm, not built in |
| Maximum data rate | 1 Mbit/s |
| Bus length by rate | 25 m at 1 Mbit/s, 100 m at 500, 250 m at 250, 500 m at 125, 1000 m at 50 kbit/s |
| Supply from drive | +3.3 V, max 300 mA |
| Mounting | Option slot of the drive |
Bus rates and wiring
The manual ties bus length to data rate: 25 m at 1 Mbit/s, 100 m at 500 kbit/s, 250 m at 250 kbit/s, 500 m at 125 kbit/s and 1000 m at 50 kbit/s. Planning the trunk with these limits avoids intermittent communication faults later.
Power comes from the drive, +3.3 V with a maximum of 300 mA. The adapter plugs into a drive option slot and is configured through the fieldbus parameter group of the drive’s control program.
Using the module in practice
Compared with Ethernet options, CANopen gives modest data volume but robust, low-cost wiring and mature tools. If the plant standard is CAN-based, the FCAN-01 keeps the drive on the same bus as the rest of the machine.
Typical steps are fitting the module, wiring CAN high, CAN low and shield to the connector, fitting terminators, setting node ID and bit rate and mapping the process data in the master.
Selection and planning notes
CAN networks are sensitive to topology. Keep stubs short, run the shield continuously and use a single protective earth point for the cable screen. The manual lists the connector pin assignment, so a ready-made cable can be checked with a meter before it is plugged into the module. Remember that every node on the bus must share the same bit rate, and that a changed node ID takes effect only after a restart of the module or a power cycle, as the manual describes.
More drive types are listed in AC drives; for a general-purpose platform see the ABB ACS580 page. Ask us when a CANopen project needs a matching option for a specific control program.
Documents and quotation
Seven Star LLC supplies the FCAN-01 on request from Muscat; send the drive type, control program version and the network details, and we reply with availability and lead time. The user manual (3AFE68615500, revision F) is linked on this page.
Confirm before ordering: supported drive types and firmware, the external termination plan, node ID and bit rate, and the cable length against your chosen data rate.
Datasheets & Documents
- fcan Manual Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.
ABB company profile
| Formed | 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50% |
|---|---|
| ASEA | Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators |
| Brown, Boveri & Cie | Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri |
| Headquarters | Zurich, Switzerland; ABB Ltd became the group holding company in 1999 |
| Ownership | Public company listed on SIX Swiss Exchange and Nasdaq Stockholm |
| Brands in the group | Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers |
| Product families | Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots |
Milestones
- 1883: ASEA is founded in Västerås, Sweden.
- 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
- 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
- 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
- 2011 and 2017: Baldor Electric and B&R join ABB.
- 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.
Choosing an ABB drive
ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.
Where ABB products are used
In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.
ABB products we list
| Family | Examples |
|---|---|
| AC drives | ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module |
| Breakers, motor control and protection | SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay |
| Flow measurement | ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500 |
| Pressure, temperature and level | 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge |
| Analysers | Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210 |
| Control systems and actuators | AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000 |
Ordering ABB products: what we need
Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.
Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.
Related products
Frequently Asked Questions
CANopen, with the drive acting as a slave node.
A nine-pin D-SUB male connector labelled X1.
No, the manual states the 120 ohm termination is not built in, so use external terminators.
1 Mbit/s, with a bus length of 25 m at that rate according to the manual.
From the drive at +3.3 V, maximum 300 mA.

Reviews