Schneider Electric ABLU3A24200 Modicon 24 V 20 A 3-Phase Power Supply

Description

Overview

The Schneider Electric ABLU3A24200 is a regulated switch mode power supply from the Modicon ABLU Universal range. It converts a three-phase 380 to 500 Vac line into a stabilised 24 Vdc output rated at 20 A, which equals 480 W, and it mounts directly on a 35 mm DIN rail. Schneider Electric designed the ABLU range to feed the control circuits of automation equipment such as logic controllers, PACs, I/O, sensors and actuators, and the range covers 120 W to 960 W in a single 124 mm height.

Many buyers still search for the older Phaseo ABL8WPS24200. Schneider Electric lists that reference as discontinued and states in its Modicon power supply catalog that it has been replaced by the Schneider Electric ABLU3A24200. Seven Star LLC supplies the new model to panel builders, system integrators, oil and gas operators, utilities and OEMs in the Sultanate of Oman and across the GCC, with engineering support from Muscat for anyone migrating from the ABL8WPS24200.

Operating Principle of the Schneider Electric ABLU3A24200

As a switch mode design, the Schneider Electric ABLU3A24200 rectifies the three-phase input, switches it at high frequency through an integrated isolation transformer and regulates the secondary to a DC voltage that the catalog states is precise to better than 3% whatever the load. The double insulation between the line side and the low-voltage output, together with internal circuitry that keeps the output below 60 V under single fault conditions, lets the unit supply PELV and SELV control circuits in line with IEC/EN 60364-4-41. The range also conforms to IEC/EN 61000-3-2 for harmonic current, so it can be connected to public low-voltage networks.

Two behaviours matter in daily operation. First, a power reserve (boost function) lets the supply deliver 1.5 times its nominal current for short periods; the instruction sheet gives a boost of 150% of nominal current for up to about 5 s, with recovery times that depend on the base load. This absorbs inrush from solenoid valves, contactor coils and capacitive loads without oversizing the supply. Second, the user chooses the reaction to overload or short circuit: in manual reset mode priority goes to voltage so PLC logic states are preserved, while automatic reset mode gives priority to current to keep the process running until maintenance arrives.

Engineering Design of the Schneider Electric ABLU3A24200

The front of the Schneider Electric ABLU3A24200 carries screw terminals for the three-phase input (L1, L2, L3 and earth), screw terminals for the DC output, cage clamp terminals for the volt-free diagnostic relay, a bicolour DC status LED, a protection mode selector and an output voltage adjustment potentiometer used to compensate voltage drop on long cable runs. A QR code printed on the front links to the latest technical documentation, and the printed circuit board carries a conformal coating to resist common dust and humidity. The catalog weight is 1.151 kg.

The diagnostic relay is rated 30 V AC/DC, 1 A resistive, and is usually wired to a PLC input so the control system knows when the DC output is healthy. The supply is approved for TN, TT and IT three-phase networks, and the Schneider Electric ABLU3A24200 can be combined with ABL8 functional modules such as the ABL8RED24400 redundancy module, ABL8BUF24400 buffer module and ABL8DCC DC/DC converters. For primary protection the catalog recommends TeSys Deca frame 2 breakers, GV2ME08 or GV2RT07 for this rating, and warns against smaller breakers that could trip on inrush.

Key Features of the Schneider Electric ABLU3A24200

The points below summarise what Schneider Electric documents for the Schneider Electric ABLU3A24200 in its catalog, instruction sheet and product page.

  • Three-phase input from 380 to 500 Vac (-15% to +15%, 50/60 Hz) with a 24 Vdc, 20 A, 480 W output.
  • Power reserve that delivers 1.5 times nominal current at regular intervals for loads with high inrush current.
  • Selectable manual or automatic reset after output overload or short circuit.
  • Integrated protection against overload, short circuit, overvoltage and undervoltage.
  • Local diagnostics through a front LED and remote diagnostics through a volt-free relay contact.
  • Conformal-coated circuit board and an operating range of -25 to +70 °C, with derating above 55 °C.
  • Compatibility with Modicon functional modules for redundancy, buffering and auxiliary DC/DC voltages.
  • Direct replacement path for the discontinued Phaseo ABL8WPS24200 named by Schneider Electric.

Industrial Applications

A 480 W, 24 V supply is the backbone of many control panels in Oman. The Schneider Electric ABLU3A24200 suits PLC and RTU cabinets on oil and gas wellsites and gathering stations, motor control centre auxiliary circuits, pump station panels in water networks, and control panels for reverse osmosis desalination plants where three-phase power is available but no neutral conductor is available. Schneider Electric lists the ABLU3A24 range for use with Modicon M221, M241, M251 and M262 controllers and Modicon M340 and M580 PACs, so it fits naturally beside a Modicon M221 compact PLC or a Modicon M241 logic controller.

For plants in Sohar, Duqm and Salalah that standardised on the ABL8WPS24200, the Schneider Electric ABLU3A24200 is the documented successor, which simplifies spare part planning and panel upgrades. Seven Star LLC supplies the Schneider Electric ABLU3A24200 on request with engineering support in Muscat, and can quote the recommended TeSys Deca GV2ME08 motor circuit breaker for upstream protection in the same order.

Technical Specifications

The values below for the Schneider Electric ABLU3A24200 come from the Schneider Electric Modicon power supply catalog (DIA3ED2170401EN), the ABLU instruction sheet (GEX54437) and the Schneider Electric product page.

Parameter Specification
Model Schneider Electric ABLU3A24200 (Modicon ABLU Universal, 3-phase)
Replaces ABL8WPS24200 (end of commercialisation)
Input voltage 380 to 500 Vac, -15% to +15%, 50/60 Hz, 3-phase (L1-L2-L3)
Network compatibility TN, TT, IT
Output 24 Vdc, 20 A nominal, 480 W
Output precision Better than 3%, whatever the load
Power reserve 1.5 In (150% boost, approx. 5 s)
Reset mode Manual or automatic, selectable
Diagnostic relay Volt-free contact, 30 V AC/DC, 1 A resistive
Recommended primary protection GV2ME08 or GV2RT07 (TeSys Deca frame 2)
Operating temperature -25 to +55 °C; up to +70 °C with derating
Altitude Up to 2000 m without derating
Humidity 5 to 95% RH at 25 °C, no condensation
Degree of protection IP20 (IEC 60529)
Standards IEC/EN 61010-1, IEC/EN 61010-2-201, UL/CSA 61010-1, UL/CSA 62368-1
Certifications (range) CE, CB Scheme, cULus Listed, UL Class I Div 2, cURus, RCM, EAC, UKCA, KC, BIS
Mounting 35 mm DIN rail
Weight 1.151 kg

How to Order

To order the Schneider Electric ABLU3A24200 or replace an existing ABL8WPS24200, send Seven Star LLC the quantity, your supply network details and any redundancy or buffer requirements. We will confirm the configuration, stock and lead time for Oman and the GCC, and the Schneider Electric catalog and instruction sheet are available to download on this page.

Datasheets & Documents
  • PDF Catalog Schneider Electric Modicon Power Supply Catalog (DIA3ED2170401EN) Download
  • PDF Manual Schneider Electric ABLU3A24 / ABLU3A48 Instruction Sheet (GEX54437) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric ABLU3A24200 Modicon 24 V 20 A

Answers from our engineering team on installation, compatibility and integration.

01Does the Schneider Electric ABLU3A24200 replace the ABL8WPS24200?
Yes. Schneider Electric states in its Modicon power supply catalog that the ABL8WPS24200 has reached end of commercialisation and has been replaced by the ABLU3A24200. Both are 380-500 Vac three-phase, 24 Vdc 20 A, 480 W units, but check panel space and terminal arrangement when retrofitting.
02What input voltage does the ABLU3A24200 accept?
It is a three-phase unit for 380 to 500 Vac, -15% to +15%, at 50/60 Hz, connected L1-L2-L3, and it is approved for TN, TT and IT networks.
03How does the ABLU3A24200 handle inrush and overloads?
It has a power reserve that can deliver 1.5 times nominal current for short periods, and the user can select manual or automatic reset after an overload or short circuit.
04What circuit breaker is recommended upstream of the ABLU3A24200?
The Schneider Electric catalog recommends a TeSys Deca frame 2 breaker, GV2ME08 or GV2RT07, and advises against smaller breakers that could trip on inrush current.
05Does Seven Star LLC supply the Schneider Electric ABLU3A24200 in Oman?
Yes. Seven Star LLC supplies the Schneider Electric ABLU3A24200 with engineering support in Muscat, including help with migrating panels from the ABL8WPS24200.