Schneider Electric A9Z66463 Acti9 iID 4P 63 A 500 mA B-SI

Description

A9Z66463: Acti9 iID 4P 63 A 500 mA type B-SI RCCB

The A9Z66463 is a Schneider Electric Acti9 iID residual current circuit breaker (RCCB) with four poles, a rated current of 63 A, a sensitivity of 500 mA and protection class type B-SI (Super Immunised). The datasheet lists photovoltaic, three-phase speed drive and lift as its device applications. It clips onto a 35 mm DIN rail, is 72 mm wide (8 modules of 9 mm) and is rated 400 V AC at 50 Hz. Seven Star LLC supplies the A9Z66463 in Oman and the GCC as an independent supplier based in Muscat.

Unlike the type AC and type A iID devices, this reference is aimed at circuits where the residual current may contain a smooth DC component. IEC/EN 62423, listed among its standards next to EN/IEC 61008-1, is the standard that covers type F and type B residual current devices, which is why it appears on a type B-SI unit.

Technical specifications of the A9Z66463

Parameter Specification
Manufacturer / part number Schneider Electric / A9Z66463
Range / product name Acti9 / Acti9 iID
Product type Residual current circuit breaker (RCCB)
Device short name iID
Device application Photovoltaic; 3P speed drive; lift
Poles 4P, neutral on the left
Rated current [In] 63 A
Earth-leakage sensitivity 500 mA, instantaneous
Protection class Type B-SI (Super Immunised)
Network / frequency AC / 50 Hz
Rated operational voltage [Ue] 400 V AC 50 Hz
Rated insulation voltage [Ui] 500 V
Rated impulse withstand [Uimp] 6 kV
Rated breaking and making capacity Idm 1500 A / Im 1500 A
Rated conditional short-circuit current 10 kA
Residual current tripping Voltage independent
Device location in system Outgoer; group incomer
Control / signalling Toggle; ON/OFF indication; green LED for presence of voltage; trip indicator; contact position indicator
Mounting Clip-on, 35 mm DIN rail
Width / height / depth 72 mm (8 × 9 mm pitches) / 88 mm / 73 mm
Net weight 415 g
Colour White (RAL 9003)
Mechanical / electrical durability 20000 / 15000 cycles
Locking Padlocking device
Terminals Double terminal front: 1–35 mm² rigid, 1–25 mm² flexible, 1–25 mm² flexible with ferrule; double terminal back: 1–25 mm² rigid, 1–16 mm² flexible, 1–16 mm² flexible with ferrule
Wire stripping / torque 14 mm / 3.5 N.m, top or bottom
Standards EN/IEC 61008-1; EN/IEC 61008-2-1; IEC/EN 62423
Quality labels / certification VDE; NF; IMQ; KEMA / CCC
Degree of protection IP20; IP40 in modular enclosure (IEC 60529); IK05
Pollution degree / overvoltage category 3 / IV
Surge immunity 8/20 µs impulse withstand, 3 kA (EN/IEC 61008-1)
Operating altitude 0–2000 m
Operating temperature -25 to 60 °C
Storage temperature -40 to 85 °C
Packing 1 piece, 428 g; 27 pieces in the second package level
Warranty 18 months

Why type B-SI matters for the A9Z66463

A basic RCCB responds to sinusoidal alternating residual current. Equipment that rectifies the supply, such as inverters, speed drives and lift controllers, can leak current with a smooth DC content that blinds a type AC or type A device or saturates its core. A type B device is built to detect that kind of fault current as well as the alternating and pulsating forms. The A9Z66463 is rated for exactly the three applications Schneider names: photovoltaic installations, three-phase variable speed drives and lifts.

The SI suffix stands for Super Immunised. The datasheet backs this with an 8/20 µs impulse withstand of 3 kA and an overvoltage category of IV. In practice a super-immunised device is less likely to trip when transients, switching surges or the high-frequency leakage of electronic equipment pass through, which cuts nuisance trips on installations where they are costly.

Sensitivity of 500 mA on the A9Z66463

At 500 mA the A9Z66463 is far less sensitive than a 30 mA device and is not a personal-protection stage. A level like this is typically chosen for fire-risk protection, for group incomers feeding several outgoing circuits, or on equipment with higher normal leakage. The datasheet lists its location in the system as outgoer and group incomer, and the tripping time is instantaneous.

If the circuit also has sockets or other points where a person can touch live parts, add a 30 mA stage downstream. Because tripping is instantaneous, a fault on the downstream device may trip both unless the system is arranged so that the upstream device is selective, so check the discrimination design before commissioning.

Terminals, indicators and mounting of the A9Z66463

The A9Z66463 is 72 mm wide, 88 mm high and 73 mm deep, weighs 415 g and comes in white (RAL 9003). Double terminals are fitted at the front and the back. The front takes 1 to 35 mm² rigid, 1 to 25 mm² flexible or the same flexible size with a ferrule, and the back takes 1 to 25 mm² rigid and 1 to 16 mm² flexible, with or without ferrule. Strip 14 mm and tighten to 3.5 N.m, top or bottom. The neutral is on the left.

Front signalling includes a toggle with ON/OFF indication, a green LED for the presence of voltage and a trip indicator. A padlocking device is listed to hold the unit open during maintenance, and the contact position indicator shows whether the poles are open.

Ratings and environment of the A9Z66463

The this RCCB lists a rated insulation voltage of 500 V, an impulse withstand of 6 kV, a breaking and making capacity of Idm 1500 A and Im 1500 A, and a conditional short-circuit current of 10 kA. Durability is 20000 mechanical and 15000 electrical cycles. Protection is IP20, or IP40 in a modular enclosure, with IK05 and pollution degree 3.

Operation is listed from -25 to 60 °C up to 2000 m, and storage from -40 to 85 °C. The upper limit is a good fit for Gulf switchrooms, but the temperature inside a loaded inverter or drive cabinet should be checked, since heat from neighbouring power electronics reaches an this RCCB mounted beside them.

Selection checklist for the A9Z66463

  • Residual current waveform: confirm that the loads justify type B-SI, and confirm which type the drive or inverter manufacturer requires.
  • Supply: 400 V AC, 50 Hz, four poles with neutral on the left.
  • Current: load up to 63 A, with a short-circuit device upstream.
  • Sensitivity: 500 mA instantaneous against the protection goal.
  • Approvals: the datasheet lists VDE, NF, IMQ and KEMA quality labels and CCC certification; check which your project requires.
  • Space: 8 modules, 72 mm of DIN rail.

Installing and testing the A9Z66463

Isolate and prove dead, clip the this RCCB onto the rail and connect the conductors as the diagram on the housing shows, with neutral on the left. Use the 14 mm strip length and 3.5 N.m torque. Energise, confirm the green voltage LED, and use the test function to check that the device trips. Reset by hand afterwards.

Keep a record of the setting and rating, test the unit at regular intervals, and investigate before reclosing after a trip. On a drive or inverter circuit, check the cable shielding, filters and earthing first because they set the normal leakage that the A9Z66463 sees.

In the region a type B-SI device is typically considered for rooftop and carport solar installations, lift machine rooms, and pump or fan drives at water, HVAC and industrial sites. Heat, dust and humidity are the main ageing factors, so enclosure sealing and ventilation matter. Requirements for residual current protection on inverters and drives come from the equipment supplier and the project specification, and those take precedence over general guidance.

Information to send with an RFQ for the A9Z66463

  • Exact reference A9Z66463 and the quantity needed.
  • Equipment on the circuit, such as inverter, drive or lift controller, with its make and model.
  • Supply voltage, system type and earthing arrangement.
  • Upstream protective device and its rating.
  • Approvals required by the project.
  • Delivery location and timeline.

Documents and quotation

The Schneider Electric datasheet for the A9Z66463 is attached on this page and holds the full specification summarised above. It is dated 8 Nov 2026 as printed on the manufacturer’s document.

Send us the reference A9Z66463, quantity and delivery location and Seven Star LLC will reply to your request. We supply as an independent supplier based in Muscat and do not act for the manufacturer.

Other Models in the Se Acti9 Iid Rccb Range

Seven Star LLC supplies models from the Se Acti9 Iid Rccb range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric A9R10225 Acti9 iID 2P 25 A 10 mA RCCBCircuit BreakersView details
Schneider Electric A9R11280 Acti9 iID 2P 80 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R11291 Acti9 iID 2P 100 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R11491 Acti9 iID 4P 100 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R12240 Acti9 iID 2P 40 A 100 mA RCCBCircuit BreakersView details
Schneider Electric A9R12263 Acti9 iID 2P 63 A 100 mA RCCBCircuit BreakersView details
Schneider Electric A9R12291 Acti9 iID 2P 100 A 100 mA RCCBCircuit BreakersView details
Schneider Electric A9R12440 Acti9 iID 4P 40 A 100 mA RCCBCircuit BreakersView details
Schneider Electric A9R12463 Acti9 iID 4P 63 A 100 mA RCCBCircuit BreakersView details
Schneider Electric A9R21225 Acti9 iID 2P 25 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R21240 Acti9 iID 2P 40 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R21263 Acti9 iID 2P 63 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R21425 Acti9 iID 4P 25 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R21440 Acti9 iID 4P 40 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R21463 Acti9 iID 4P 63 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R21491 Acti9 iID 4P 100 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R22463 Acti9 iID 4P 63 A 100 mA RCCBCircuit BreakersView details
Schneider Electric A9R24240 Acti9 iID 2P 40 A 300 mA RCCBCircuit BreakersView details
Schneider Electric A9R31491 Acti9 iID 4P 100 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R34463 Acti9 iID 4P 63 A 300 mA RCCBCircuit BreakersView details
Schneider Electric A9R41463 Acti9 iID 4P 63 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R61240 Acti9 iID 2P 40 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R61425 Acti9 iID 4P 25 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R61440 Acti9 iID 4P 40 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R61463 Acti9 iID 4P 63 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R71225 Acti9 iID 2P 25 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R71240 Acti9 iID 2P 40 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R71263 Acti9 iID 2P 63 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R71425 Acti9 iID 4P 25 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R71440 Acti9 iID 4P 40 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R71463 Acti9 iID 4P 63 A 30 mA RCCBCircuit BreakersView details
Schneider Electric A9R74225 Acti9 iID 2P 25 A 300 mA RCCBCircuit BreakersView details
Schneider Electric A9R74240 Acti9 iID 2P 40 A 300 mA RCCBCircuit BreakersView details
Schneider Electric A9R74263 Acti9 iID 2P 63 A 300 mA RCCBCircuit BreakersView details
Schneider Electric A9Z66463 Acti9 iID 4P 63 A 500 mA B-SICircuit BreakersYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Schneider Electric A9Z66463 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric A9Z66463 Acti9 iID 4P 63 A 500

Answers from our engineering team on installation, compatibility and integration.

01What does the A9Z66463 protect against?
It is a four-pole type B-SI RCCB with 500 mA sensitivity and instantaneous tripping. It responds to earth-leakage current, including forms with a DC component, but gives no overload or short-circuit protection, so a breaker or fuse must be fitted upstream.
02What applications does the datasheet list for the A9Z66463?
The datasheet lists photovoltaic, three-phase speed drive and lift as the device applications, and gives the location in the system as outgoer and group incomer.
03What supply is the A9Z66463 rated for?
The datasheet lists 400 V AC at 50 Hz, four poles, 63 A rated current and 500 V insulation voltage, with a 10 kA conditional short-circuit rating.
04What size does the A9Z66463 have?
It is 72 mm wide (8 modules of 9 mm), 88 mm high and 73 mm deep, weighs 415 g and clips onto a 35 mm DIN rail.
05What temperature range is listed for the A9Z66463?
Operation is listed from -25 to 60 degrees C up to 2000 m and storage from -40 to 85 degrees C, with IP20 protection and IP40 in a modular enclosure.