Schneider Electric 33487 NS800 NA 800 A Switch-Disconnector

Description

33487: Compact NS800 NA 800 A switch-disconnector, 3 poles

The 33487 is not a circuit breaker in the protective sense. Schneider Electric lists it as a molded case switch-disconnector, Compact NS800 NA, 800 A, 3 poles, from the ComPact NS family. Its job is to make, carry and break load current and to give a visible-status isolation point, while the protection comes from a separate breaker or fuse upstream. Seven Star LLC supplies the 33487 in Oman and the GCC as an independent supplier based in Muscat.

The performance level is given as NA, the device is of the fixed-mounting type with toggle control, and the datasheet identifies the offer type as C4. The datasheet also carries a discontinued notice dated 31 Mar 2024, so confirm availability or an alternative before using it on a new project.

Technical specifications of the 33487

Parameter Specification
Manufacturer / part number Schneider Electric / 33487
Device short name Compact NS800 NA
Product type Switch-disconnector, distribution application
Poles 3P
Network AC, 50/60 Hz
Rated operational current Ie AC-23A: 800 A at 220/240, 380/415, 440/480, 500/525 and 660/690 V AC
Rated operational voltage Ue 690 V AC 50/60 Hz (IEC 60947-3)
Rated insulation voltage Ui / Uimp 800 V AC / 8 kV
Conventional thermal current Ith 800 A at 60 °C
Short-time withstand Icw 25 kA for 0.5 s; 4 kA for 20 s
Short-circuit making capacity Icm 52 kA at 690 V AC
Suitability for isolation Yes, conforming to IEC 60947-3
Contact position indicator / visible break Yes / No
Mechanical durability 6000 cycles
Electrical durability 1000 cycles at 440 V AC
Control / mounting Toggle / fixed; front connections, 70 mm pitch
Dimensions W x H x D 210 x 327 x 147 mm
Net weight 14 kg
Pollution degree 3 (IEC 60947-3)
Ambient temperature, operation / storage -25 to 70 °C / -50 to 85 °C
Certifications listed ASTA, ASEFA

How a switch-disconnector differs from a breaker

A switch-disconnector is selected by its load-making and load-breaking duty and by its withstand ratings, not by trip curves. The datasheet therefore gives the AC-23A category rating of 800 A across the whole voltage range up to 690 V. AC-23A covers switching of motor loads and other highly inductive loads, which is a demanding duty, so the figure is useful when the device is used as a motor-circuit or main isolating switch.

There is no trip unit and no adjustable protection in the datasheet. If a fault occurs downstream, the device does not clear it by itself; it must be protected by a breaker or fuses ahead of it that coordinate with its Icw and Icm values. This is a common arrangement for a bus-section, a main isolator on a transformer output, or a disconnector for maintenance on a feeder.

Withstand and making capacity of the 33487

Two numbers decide whether the switch-disconnector survives the fault level at its location. The first is the short-time withstand: 25 kA for 0.5 s, or 4 kA for 20 s. The second is the short-circuit making capacity Icm, 52 kA at 690 V AC, which is the peak current the device can close onto.

To check an installation, compare the prospective fault current at the board with those figures and with the let-through of the upstream protective device. Where the upstream device limits the fault energy strongly, the real stress may be lower than the prospective value, but that coordination data comes from the manufacturer’s tables, not from this datasheet.

Rating Value
Icw 0.5 s 25 kA
Icw 20 s 4 kA
Icm at 690 V AC 52 kA
Ith at 60 °C 800 A

Where the 33487 fits

The Compact NS800 NA belongs to the same frame family as the NS800 and NS630b to NS1600 breakers, with identical outline dimensions of 210 x 327 x 147 mm and the same 70 mm front connection pitch. A switch-disconnector can therefore be mounted in the place of a breaker of that frame when only isolation or switching is needed and protection is provided elsewhere.

Related references that Seven Star LLC handles in the same family include the 800 A four-pole breaker 33555 with MicroLogic 5.0, the 1000 A breaker 33558 and the 630 A breaker 33546. These are breakers with trip units, and so serve a different purpose from the 33487, but share the frame size and the front connections.

Installation and operation of the 33487

Mount the 33487 on a backplate and connect the busbars or cables to the front terminals on the 70 mm pitch, checking tightening torque against the installation instruction of the manufacturer. The datasheet lists a contact position indicator but no visible break; if the site isolation procedure demands a visible gap or a lockable position, confirm how that will be provided before relying on the device as the sole point of isolation.

Mechanical durability is 6000 cycles and electrical durability 1000 cycles at 440 V AC, which is less than the 10000 mechanical cycles of the breakers in the same frame family; for a switch operated daily, count the operations. Inspect terminals and the housing at each shutdown, and keep the device inside an enclosure suited to pollution degree 3.

Using the 33487 in Oman and the GCC

In Oman and the GCC, a molded-case switch-disconnector of this size is typically seen as a main isolator on a transformer secondary, a bus-coupler or a feeder isolator for a motor control centre in oil and gas camps, desalination units, power stations and large buildings. The operating ambient is stated as -25 to 70 °C, which leaves some headroom for hot switchrooms, but dust and humidity make a sealed enclosure with ventilation or air conditioning worthwhile.

Selecting the right isolating device: checklist for the 33487

  • Confirm the duty: isolation and switching only, with protection upstream, versus protection and switching in one device.
  • Check the 800 A AC-23A rating against the load current and voltage, up to 690 V AC.
  • Compare prospective fault current with Icw (25 kA for 0.5 s) and Icm (52 kA).
  • Check how isolation will be proven or padlocked, since no visible break is listed.
  • Check availability, because the datasheet shows the device as discontinued.

Information to send with an RFQ for the 33487

Please include the part number 33487, the quantity, the system voltage and prospective fault level, the intended upstream protective device, and the delivery location in Oman or the GCC. If you are replacing an existing device, a photo of the nameplate helps us confirm the match.

Documents and quotation

The official English datasheet for the 33487 is attached on this page. It contains the AC-23A ratings, withstand values, dimensions and the discontinued notice referred to above.

To request a quotation, send the part number 33487, the quantity and the delivery location. Seven Star LLC is an independent supplier in Muscat and quotes according to current availability.

Datasheets & Documents
  • PDF Datasheet Schneider Electric 33487 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric 33487 NS800 NA 800 A

Answers from our engineering team on installation, compatibility and integration.

01What is the rated current of the 33487?
AC-23A: 800 A at 220/240 up to 660/690 V AC, with a conventional thermal current of 800 A at 60 °C.
02Does the 33487 protect against overload or short-circuit?
No trip unit is listed. It is a switch-disconnector and needs upstream protection.
03What fault level can the 33487 withstand?
The datasheet gives Icw of 25 kA for 0.5 s and 4 kA for 20 s, and a short-circuit making capacity of 52 kA at 690 V AC.
04Is the 33487 suitable for isolation?
Yes, the datasheet states suitability for isolation under IEC 60947-3; it lists a contact position indicator but no visible break.
05Is the 33487 still available?