Brand:

Autonics MT4Y-DV-43 72×36 DC Voltage Meter Relay 4-20 mA

Description

Overview

When panel height is scarce, a meter only 36 mm tall is a help, and the Autonics MT4Y-DV-43 fits that slot. It is a 72 x 36 mm four-digit DC voltage panel meter with a red LED display, and it does more than indicate: a relay output switches when the reading falls below a limit, and a 4 to 20 mA transmission output repeats the displayed value to a PLC or recorder. It runs on 100 to 240 V AC. Seven Star LLC is an independent supplier serving Oman and the GCC.

What Autonics MT4Y-DV-43 says about the unit

MT4 is the four-digit panel meter family and Y is the 72 x 36 mm size. DV means DC voltage input. After the dash, 4 is the supply of 100 to 240 V AC. The final digit 3 is the output combination listed in the ordering table for the Y size: a relay with low-limit operation, written LOW OUT, as the preset output, plus a 4 to 20 mA DC transmission as the sub output. By contrast, a 0 gives a plain relay, 1 an NPN open collector, 2 a PNP open collector, 4 a LOW OUT relay with RS485, 5 BCD dynamic and 6 low speed serial.

Autonics MT4Y-DV-43 specification table

Item Data
Front size 72 x 36 mm
Input DC voltage: 250 mV or 50 mV, 5 V or 1 V, 50 V or 10 V, 500 V or 100 V
Display Red 7-segment LED, 14.2 mm, minus 1999 to 9999
Accuracy 0.1 percent F.S. plus or minus 2 digit at 23 degrees C plus or minus 5
Sampling cycle 50 ms (DC)
Preset output Relay LOW OUT, 1a, 250 V AC 3 A, 30 V DC 3 A, OFF or L.ST operation only
Sub output Transmission 4 to 20 mA DC, resolution 1/12,000, load up to 600 ohm, response 550 ms or less, accuracy 0.3 percent F.S.
Supply 100 to 240 V AC 50/60 Hz, 5 VA
Dielectric strength 3,000 V AC for 1 minute
Ambient minus 10 to plus 50 degrees C
Protection IP56 front
Weight about 134 g, about 213.5 g packaged

How the Autonics MT4Y-DV-43 differs from other MT4Y variants

The MT4Y range is narrower than the MT4W: it offers only the mains supply and seven output codes. A code N gives an indicator, 0 a relay, 1 and 2 open collectors, 4 a LOW OUT relay with RS485, 5 BCD dynamic and 6 low speed serial. In the Autonics MT4Y-DV-43, the relay is a LOW OUT type, which the manual limits to the output modes OFF or L.ST, meaning that it can only act as a low-limit alarm, unlike the relay of code 0, which supports the full list of OFF, L.ST, H.ST, LH.ST, HH.ST, LL.ST and LD.ST. The 4 to 20 mA output is another difference: its load resistance can be up to 600 ohm and its scale is set from the front keys.

Low-limit relay and transmission output

The relay can watch a battery voltage or a process signal and open or close when the value drops below the preset, with a hysteresis that can be set within 10 percent of the maximum display range. The transmission output converts the displayed value into 4 to 20 mA: the display value for 4 mA is the low-limit transmission value, and for 20 mA the high-limit value. The span between them must be at least 10 percent of full scale and, if you set a narrower span, the meter widens it automatically. Below the low value the output stays at 4 mA and above the high value at 20 mA.

Choosing the range and scale for the Autonics MT4Y-DV-43

The signal range has to match the terminal. A 12 V or 24 V battery system is best read on the 50 V terminal, which gives a resolution of 0.01 V at the 10 V sub-range and 0.1 V at 50 V, while a 48 V telecom battery fits the same terminal in the 50 V setting only if the maximum voltage stays below 110 percent of the range, so a 100 V range is the safer choice there. The manual tabulates input resistances for each range, for example about 4.33 megohm on the 100 V range and about 43 kilohm on the 1 V and 5 V ranges, which matters when a high-impedance sensor is connected, since a low input resistance loads the source and causes a reading error.

Scaling is performed with a high-limit and low-limit display value and an optional gradient correction. To display 0 to 100.0 percent from a 1 to 5 V signal, for example, set the low-limit display to 0 at 1 V and the high-limit display to 100.0 at 5 V, with one decimal place. The transmission output scale is set independently from the display, so a 4 to 20 mA copy can cover a narrower or wider band than the one shown locally. Keep a record of the chosen values, because they are not visible from the front once the meter is back in run mode.

Applications in Oman and the GCC

A DC voltage meter with a low alarm is useful for battery chargers, DC distribution boards, solar charge controllers, telecom shelters and standby systems. The 4 to 20 mA copy can be sent to a PLC or SCADA to log the same voltage, and the compact 36 mm height lets several meters be stacked on a small panel. It is also a handy local indicator for 0 to 10 V or 1 to 5 V transmitters, with scaling to engineering units.

Wiring and set-up

Connect the supply to the source terminals, the measured voltage between the common terminal and the terminal for the range, and the relay and transmission terminals as shown in the diagram. Keep the 4 to 20 mA loop total resistance within 600 ohm. After power-up, use the parameter groups to select the range, decimal point and scale, set the relay setpoint and hysteresis, and adjust the transmission scale. A zero adjustment is available through the keys or the HOLD/ZERO input.

Cautions

Do not exceed 110 percent of the selected range, avoid measuring below 30 percent of the terminal range, where accuracy degrades, and keep input wires apart from power cables. The relay is rated 3 A resistive at 250 V AC, so drive contactors or large loads through interposing relays. The relay life is 100,000 electrical operations at that load.

Related items you may also need: Autonics E40S6-2500-6-L-5 Rotary Encoder Incremental | Keyence FS-N13N Digital Fiber Amplifier, 2-Output, NPN | SICK GRTE18S-P2442 GR18 Diffuse Photoelectric Sensor | All Autonics products.

Documents and quotation

The MT4Y series product manual covering the Autonics MT4Y-DV-43 is attached with ordering information, ranges, parameters and dimensions. Send an RFQ with the part number Autonics MT4Y-DV-43, quantity and delivery location in Oman or the GCC.

Datasheets & Documents
  • PDF Datasheet Autonics MT4Y-DV-43 72x36 DC Voltage Meter Relay 4-20 mA Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Autonics is a South Korean maker of sensors and controllers, founded in 1977 as a small engineering business making controllers for looms. It took the Autonics name in 1988 and opened a new corporate headquarters in Busan in 2014. Autonics makes proximity and photoelectric sensors, rotary encoders, temperature controllers, counters, timers and stepper motor systems, with factories in Busan and Yangsan.

Seven Star LLC lists the Autonics E40S6-2500-6-L-5 incremental rotary encoder and supplies Autonics sensors and control devices in Oman and the GCC.

Autonics company profile

Founded 1977, South Korea
Current name Autonics, since 1988
Headquarters Busan, South Korea
Factories Busan and Yangsan
Product families E40 and E50 rotary encoders, PR proximity sensors, BJ photoelectric sensors, TK temperature controllers

Milestones

  • 1977: The company is founded.
  • 1988: Renamed Autonics Corporation.
  • 2014: Opens its Busan headquarters.

Reading the Autonics E40S encoder code

E40S is the 40 mm diameter shaft-type incremental encoder, and the 6 that follows is the 6 mm shaft. 2500 is the resolution in pulses per revolution. The next 6 means six output signals: A, B and Z with their inverted signals. L is a line driver output and the final 5 is a 5 V DC supply. The same 40 mm body is made in hollow shaft form as the E40H and E40HB series.

Where Autonics encoders are used

Servo and spindle feedback, conveyor length measurement, packaging and printing machines.

Ordering Autonics encoders: what we need

Send the complete model string from the label. If it is worn off, give the body and shaft diameter, pulses per revolution, output type, supply voltage and cable or connector style.

Facts checked against Autonics corporate profiles, October 2026.

FAQ

Questions about the Autonics MT4Y-DV-43 72×36 DC Voltage Meter Relay

Answers from our engineering team on installation, compatibility and integration.

01What does the 3 mean in Autonics MT4Y-DV-43?
The 3 is the output code for a LOW OUT relay as the preset output plus a 4 to 20 mA DC transmission as the sub output.
02What size is the Autonics MT4Y-DV-43?
It is a 72 x 36 mm panel meter with a four-digit red LED display, weighing about 134 g.
03What does the Autonics MT4Y-DV-43 measure?
DC voltage on selectable ranges from 50 mV and 250 mV up to 100 V and 500 V, displayed from minus 1999 to 9999.
04What is the transmission output of the Autonics MT4Y-DV-43?
A 4 to 20 mA DC output with 1/12,000 resolution, accuracy of 0.3 percent F.S. and a load resistance of up to 600 ohm.
05Which relay modes does the Autonics MT4Y-DV-43 support?
Because it is a LOW OUT relay model, the manual allows only OFF or L.ST operation, a low-limit alarm.