Brand:

Samson 3730-5 FOUNDATION Fieldbus Positioner

Description

The Samson 3730-5 is a bus-powered electropneumatic positioner that speaks FOUNDATION fieldbus. It sits on a pneumatic control valve, reads the valve stem travel or the rotation angle, and adjusts the air pressure fed to the actuator until the valve position matches the set point arriving over the fieldbus segment. Because the same two-wire cable carries both power and data, no separate 4 to 20 mA loop and no auxiliary supply are needed at the valve. This page describes Samson 3730-5 as published in the manufacturer’s data sheet T 8384-5 (edition April 2021) and explains what a buyer in Oman or the wider Gulf should check before ordering.

What the Samson 3730-5 does in the loop

Inside the housing, an electric travel sensor without gears, an analog i/p module with a downstream air booster and a microcontroller work together. When the set point and the measured position differ, the booster either fills or vents the actuator. The signal pressure can be capped in software or on site to 1.4, 2.4 or 3.7 bar with a tolerance of 0.2 bar, which protects small actuators from overpressure. A fixed flow regulator keeps a constant bleed of fewer than 110 normal litres per hour flowing through the case, flushing it with instrument air.

Function blocks built into Samson 3730-5

The distinguishing feature of the 3730-5 compared with simpler fieldbus positioners is its block set. Each device carries one PID control block, one analog output block, one multiple analog output block, one multiple analog input block, two discrete output blocks and two discrete input blocks. The PID block lets a flow, level or pressure loop run inside the valve, and the Link Master capability allows autonomous control loops in the field if the host stops communicating. Execution times given are 30 ms for the AO block, 20 ms for each DI block and 40 ms for PID.

  • Interoperability tested to ITK 6.2.0; communication profile class 31 PS and 32 L
  • Field device conforming to FM 3610 entity, FISCO and FNICO concepts
  • Physical layer class 113 for general use and class 111 for the explosion-protected version
  • Operating voltage 9 to 32 V DC, drawn from the bus, with a maximum operating current of 15 mA and 0 mA extra current in a fault

Technical specifications of 3730-5

Rated travel, direct on Type 3277 3.6 to 30 mm
Rated travel, NAMUR or VDI/VDE 3847 3.6 to 300 mm
Rotary actuators, VDI/VDE 3845 24 to 100 degrees opening angle
Supply air 1.4 to 7 bar (20 to 105 psi)
Air quality (ISO 8573-1) Particle class 4, oil class 3, moisture class 3, dew point 10 K below lowest ambient
Hysteresis / sensitivity up to 0.3 percent / up to 0.1 percent
Characteristic deviation up to 1 percent
Air output, supply (6 bar) 8.5 m3n/h, KVmax 0.09
Air output, exhaust (6 bar) 14.0 m3n/h, KVmax 0.15
Ambient temperature -20 to +80 C; -45 to +80 C with metal gland; -55 to +80 C special low-temperature version
Temperature effect up to 0.15 percent per 10 K
Vibration effect up to 0.25 percent to 2000 Hz and 4 g (IEC 770)
Cable entry One M20x1.5 gland (6 to 12 mm) plus a second M20x1.5 thread; screw terminals 0.2 to 2.5 mm2
Protection class IP 66 / NEMA 4X
Weight about 1.0 kg; stainless steel housing about 2.2 kg
Housing Die-cast aluminum EN AC-44300, chromate and powder coated; stainless steel 1.4408 optional

Safety-related and hazardous-area facts

The data sheet states that, observing IEC 61508, the systematic capability of the pilot valve used for emergency venting is given. With IEC 61511 requirements and the necessary hardware fault tolerance, the optional solenoid valve path suits safety instrumented systems up to SIL 2 as a single device and SIL 3 in a redundant arrangement. The solenoid input is 24 V DC; a signal below 12 V triggers venting and a signal above 19 V keeps the positioner running. Ex approvals include PTB 04 ATEX 2109 with II 2G Ex ia IIC T6 Gb, and further national approvals are listed in the data sheet. Always confirm the marking on the exact device ordered.

Options that change the 3730-5 order code

  • Inductive limit switch with Pepperl+Fuchs SJ2-SN proximity switches, switching at 3 mA or more undetected and 1 mA or less detected
  • Integrated solenoid valve with a KV coefficient of 0.15 and a service life above 5 million switching cycles
  • Binary input BI2 for a floating contact, 100 ohm maximum, 100 mA contact load
  • Leakage sensor for hazardous areas, usable from -40 to +130 C with a 20 plus or minus 5 Nm tightening torque
  • External position sensor on a 10 m cable, IP67, rated -60 to +105 C, for valves where the electronics must stay away from heat or vibration

Typical applications in Oman and the GCC

A fieldbus positioner earns its price where a plant already runs FOUNDATION fieldbus: gas processing trains, refinery utilities, desalination blocks and power stations with a fieldbus DCS. In such sites, the 3730-5 lets one segment carry many valves instead of many separate loops. Because the case is sealed to IP 66 and the stainless steel variant exists, coastal installations with salt-laden air are practical. Its PID block is useful for self-contained pressure or temperature loops on package skids, such as fuel gas conditioning or chemical dosing manifolds.

Selection and compatibility notes

Choose the attachment first. For small linear actuators, direct attachment to a Type 3277 actuator gives short internal piping. For other linear valves use the NAMUR rib or the rod-type yoke arrangement of IEC 60534-6-1, and for quarter-turn valves the VDI/VDE 3845 bracket. The data sheet gives travel ranges that determine the lever size: sizes S, M, L and XL cover 17 to 33 mm, 25 to 66 mm, 70 to 116 mm and 100 to 216 mm respectively. Your RFQ should name the valve travel in millimetres and, where relevant, the stem diameter, because the ordering text asks for both.

How 3730-5 differs from other Series 3730 variants

All Series 3730 positioners share the same pneumatic section. The -5 suffix means FOUNDATION fieldbus, whereas the 3730-4 uses PROFIBUS PA and the 3730-2 and 3730-3 work with HART or 4 to 20 mA. Only the 3730-5 provides the PID, MAO and MAI block set listed above and requires the TROVIS-VIEW database module 3730-5 for local configuration through the SSP interface. Its rated travel reaches 300 mm, while the explosion-proof Type 3731-5 stops at 200 mm and carries an Ex d housing of about 2.5 kg.

Installation and commissioning

Mount the positioner in any orientation except hanging upside down. Supply clean, dry air and check the dew point before connecting. Set the DIP switch for air to open or air to close, mount the feedback lever, then press INIT. The automatic start-up measures travel, friction and transit times and moves straight into closed-loop operation. Fieldbus wiring follows the FISCO or FNICO rules for the segment, and the display can be rotated through 180 degrees so it reads upright in every position.

Maintenance. Parameters live in non-volatile memory, so a power interruption does not lose the tuning. Routine work is limited to checking filters, the air supply quality, the mounting hardware and the diagnostic messages, which follow NAMUR NE 107 classes. The integrated EXPERTplus diagnostics, described in data sheet T 8389, help predict seat or packing trouble before a shutdown. Keep the unit’s full type code and serial number to match replacement electronics.

Documents and quotation

The Samson 3730-5 data sheet is attached to this page. To receive a quotation, send an RFQ with the part number, the quantity, the valve travel or angle, the actuator type and the required hazardous-area marking. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Other Models in the Samson 3730 Range

Seven Star LLC supplies models from the Samson 3730 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Samson 3731-5 Ex d FOUNDATION Fieldbus PositionerValve PositionersView details
Samson 3730-0 Analog Electropneumatic PositionerValve PositionersView details
Samson TROVIS 3730-3 HART Smart PositionerValve PositionersView details
Samson 3730-5 FOUNDATION Fieldbus PositionerValve PositionersYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Samson 3730-5 FOUNDATION Fieldbus Positioner Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

SAMSON is a German manufacturer of control valves, actuators, positioners and self-operated regulators. Hermann Sandvoss founded the company in Düsseldorf on 1 April 1907, and its first important product was a thermostatic valve that controlled temperature without external power. After moves to Mannheim, SAMSON settled in Frankfurt am Main in 1916, where SAMSON AG is still headquartered.

Seven Star LLC supplies Samson control valves, pneumatic actuators and positioners to process plants in Oman, including the types listed on this page and their replacement units.

Samson company profile

Founded 1 April 1907, Düsseldorf, by Hermann Sandvoss, as VULCAN Technische Apparate Baugesellschaft; products sold under the SAMSON name
Headquarters Frankfurt am Main, Germany, since 1916
Legal form SAMSON AG
First product A self-operated thermostatic valve
Group brands SAMSON together with PFEIFFER, LEUSCH, VETEC and AIR TORQUE
Product families Globe valves such as Type 3241, rotary and butterfly valves, 3271 and 3277 pneumatic actuators, 3730 and 3731 positioners, self-operated pressure and temperature regulators

Milestones

  • 1907: Hermann Sandvoss founds the company in Düsseldorf.
  • 1909: It is re-established as SAMSON Apparatebau GmbH.
  • 1916: After a period in Mannheim, the company moves to Frankfurt am Main.
  • 1975: The name becomes SAMSON Mess- und Regeltechnik.

Samson valve, actuator and positioner types

Samson builds a control valve from modules. The Type 3241 globe valve is the general-service body of Series 240, and the Type 3251 is the Series 250 body for higher pressure ratings. Either one is combined with a Type 3271 pneumatic diaphragm actuator or a Type 3277, whose yoke allows the positioner to be attached directly with a concealed travel linkage.

Among the positioners listed are the Type 3725 and the Type 3730 family: the 3730-1 as the basic electropneumatic version, sold in its current generation as TROVIS 3730-1, and the 3730-3 with HART communication and valve diagnostics. Samson also makes PROFIBUS PA and FOUNDATION fieldbus variants in the same family, plus self-operated pressure and temperature regulators.

Where Samson valves are used

Samson control valves throttle steam, gas and liquids in chemical and petrochemical units, refineries, gas processing, power stations, water and desalination plants, and food production. Many reach site as part of a skid or package, so the plant instrument team often meets them first when a positioner or actuator needs replacing. We supply these items to end users and contractors throughout the GCC.

Samson products we list

Family Examples
Valve Positioners 3730-3 Electropneumatic Smart Positioner, TROVIS 3730-1 Electropneumatic Positioner, Type 3725 Electropneumatic Positioner, Type 3767 Electropneumatic Positioner, Type 4763 Electropneumatic Positioner
Control Valves Type 3241 Globe Control Valve, Type 3244 Three-Way Control Valve, Type 3251 Globe Control Valve, Type 3310 Segmented Ball Control Valve
Valve Actuators Type 3271 Pneumatic Diaphragm Actuator, Type 3277 Pneumatic Actuator for Integra…, Type 3374 Electric Linear Actuator
Solenoid Valves Type 3963 Solenoid Valve for Pneumatic A…

Ordering Samson parts: what we need

Every Samson device has a nameplate with the type, a configuration ID (Var-ID) and a serial number. A photo of that plate is the surest route to an exact match. Without it, please send:

  • Valve: type, DN or NPS, pressure rating, body and trim material, Kvs or Cv, plug and seat style, packing and bonnet type
  • Actuator: type, effective area in cm², bench range, fail action and travel
  • Positioner: full type code including Ex protection, communication and options such as limit switches or position transmitter

We check the code against Samson documentation and provide the manufacturer's data sheet on request.

Facts checked against SAMSON's corporate chronicle and press material, October 2026.

FAQ

Questions about the Samson 3730-5 FOUNDATION Fieldbus Positioner

Answers from our engineering team on installation, compatibility and integration.

01What bus does Samson 3730-5 use?
It uses FOUNDATION fieldbus per IEC 61158-2, bus powered at 9 to 32 V DC with a 15 mA maximum operating current.
02Which function blocks are inside 3730-5?
One PID, one AO, one MAO, one MAI, two DO and two DI blocks are integrated, plus Link Master capability.
03What travel can the 3730-5 handle?
Direct on Type 3277 it covers 3.6 to 30 mm, with NAMUR or VDI/VDE 3847 it covers 3.6 to 300 mm, and rotary valves 24 to 100 degrees.
04Is Samson 3730-5 suitable for SIL applications?
The pilot valve for emergency venting has systematic capability per IEC 61508 and may be used up to SIL 2 single or SIL 3 redundant under IEC 61511.
05What do I send for a 3730-5 RFQ?
Send the full part number, quantity, valve travel in mm, actuator type, supply air range, and any needed options such as limit switches.