Moore Industries SIY/PRG/4-20MA/10-42DC [DIN] Signal Isolator

Description

Moore Industries SIY/PRG/4-20MA/10-42DC [DIN]: a programmable isolator you configure once and reuse

Moore Industries SIY/PRG/4-20MA/10-42DC [DIN] is a two-wire signal isolator and converter in a DIN-rail housing. Instead of fixed ranges, the SIY handles several current inputs and several voltage inputs, and delivers an isolated 4-20 mA output. The same unit can therefore serve as a spare for dozens of different interface jobs.

The selection between current and voltage is made at the input terminals, while all other settings come from Windows software. That is why one SIY on a shelf can cover isolation of a 0-10 V transmitter, conversion of a 0-50 mA meter signal or repeating of a 4-20 mA loop.

Another practical point is the tracking behaviour. With a 4-20 mA input and a 4-20 mA output, the SIY output follows the input down to 3.8 mA if the input fails, so the receiving system sees a clear low-current alarm instead of a frozen reading. This simple rule, together with the 21.4 mA upper limit, gives a predictable failure pattern for loop diagnostics.

Capabilities

  • Opto-isolated path that breaks ground loops and stops erratic readings caused by differences in ground potential.
  • Signal conversion between common industrial ranges so that dissimilar instruments can talk to each other.
  • Signal diversion: a transmitter output can be sent to two receivers via two SIY units.
  • Output tracking that follows a 4-20 mA input down to 3.8 mA when the input fails.
  • Configuration features such as input trim, custom linearization and output damping.

The unit is loop-powered from the output side so no separate supply is needed.

SIY/PRG/4-20MA/10-42DC [DIN] specifications

Values are taken from the SIY datasheet.

Parameter Value for SIY/PRG/4-20MA/10-42DC [DIN]
Model code SIY/PRG/4-20MA/10-42DC [DIN]
Unit SIY PC-programmable signal isolator/converter, 2-wire loop powered
Input PRG: current 0-20 mA, 4-20 mA, 0-50 mA, 10-50 mA; voltage 0-1, 0-5, 1-5, 0-10 V; special ranges
Minimum span Current 1 mA; voltage 250 mV
Output 4-20 mA isolated
Supply 10-42 V DC
Accuracy Plus or minus 0.08% of span including input, output, linearity, hysteresis, repeatability
Isolation 500 Vrms input to output to case for the DIN housing (HPP is 1500 Vrms)
Input impedance Voltage 1 Mohm; current 20 ohms
Maximum overrange Current 100 mA; voltage 18 V
Output response 256 ms maximum, 128 ms typical, for 10-90% step
Measurement cycle Output updates 8 times per second
Load capability Supply voltage minus 10 V divided by 21.4 mA
Output limiting 3.8 mA low and 21.4 mA high
Weight DIN housing 184 g (6.5 oz)
Ambient -40 to +85 C; 0 to 95% RH; effect plus or minus 0.015% of span per C

Read the load figure as a simple formula: the supply voltage minus 10 V gives the voltage available for the loop resistance at the 21.4 mA upper limit. At 24 V the available drop is 14 V, which corresponds to about 650 ohms in the loop, comfortably above the 250 ohm sense resistor of most input cards.

How SIY/PRG/4-20MA/10-42DC [DIN] differs from the HPP version and from the SIX

The SIY also exists in a hockey-puck module (65 g, 1500 Vrms isolation) and an LH head version (283.5 g with a polyester cover and 468 g with a metal cover). The DIN style is 184 g with 500 Vrms isolation. Against the fixed-range SIX, the SIY is programmable by PC, and has an accuracy of 0.08% of span rather than 0.1%.

Another point is the 10 V lower supply limit: the SIY needs 10 V, whereas the SIX needs 12 V.

Applications

Use it to protect PLC analog inputs, to isolate a transmitter that shares a ground with a different system, to boost a signal for an overloaded loop, or to resolve bucking power supplies when a 4-wire transmitter and a DCS both try to power the same loop.

In water and power plants it is a frequent solution for motor current and level signals with ground-loop problems.

Selecting SIY/PRG/4-20MA/10-42DC [DIN]

Check that the input signal fits the available ranges and the 1 mA or 250 mV minimum span. For hazardous areas, check the certification page of the datasheet, since the listed approvals relate to the specific housing.

The unit comes with one copy of the configuration software; the interface cable is a separate item.

Installation

Clip the module onto the rail, connect the input to the current or voltage terminals as required, connect the 2-wire loop, and use the PC software and configuration cable to choose the range. Verify with a calibrator that 4 and 20 mA follow the chosen input.

Keep signal wiring apart from power cables to benefit fully from the isolation.

After installation save the configuration to a file named with the tag number. If the unit is later replaced with a new SIY, the file restores input range, damping and any linearization table. A loop test at 4, 12 and 20 mA confirms the result before the loop returns to automatic.

Maintenance

Little is needed beyond checking terminals and comparing outputs periodically. The ambient temperature effect is small, plus or minus 0.015% of span per degree C, and the unit has non-volatile storage of settings.

Keep the configuration file for fast replacement.

Supply of SIY/PRG/4-20MA/10-42DC [DIN]

Please quote SIY/PRG/4-20MA/10-42DC [DIN] in full and describe the input and output signals to be handled.

Seven Star LLC is an independent supplier serving Oman and the wider GCC and is not affiliated with the manufacturer; all names and part numbers are used only to identify the product being requested.

Documents and quotation

The datasheet for Moore Industries SIY/PRG/4-20MA/10-42DC [DIN] can be sent with our quotation. Submit an RFQ with part number, quantity and delivery location.

Datasheets & Documents
  • PDF Datasheet Moore Industries SIY/PRG/4-20MA/10-42DC [DIN] Signal Isolator Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Moore Industries is an American manufacturer of signal interface instruments, founded in 1968 by engineer Leonard W. Moore in North Hills, California. Its first product was the SCT signal converter, built in a friend's workshop. The company has been at its North Hills headquarters since 1974 and still designs and builds its products there, known for rugged aluminium housings.

Seven Star LLC, an independent supplier in Oman, lists Moore Industries temperature transmitters, limit alarm trips, isolators and a PID backup controller, and sources units and replacements by full model number.

Moore Industries company profile

Founded 1968, North Hills, California, USA, by Leonard W. Moore
Headquarters North Hills, California, since 1974
Ownership Privately owned (Moore Industries-International, Inc.)
First product SCT signal converter
Product families Signal isolators and converters (ECT, SCT), temperature transmitters (TRY, THZ), alarm trip units (SPA), miniMOORE multichannel signal conditioners, HART interfaces, SIL-rated safety logic solvers (STA)

Milestones

  • 1968: Leonard W. Moore founds the company and builds the first SCT signal converter.
  • 1974: The company moves into its North Hills headquarters.
  • 2009: miniMOORE wins a Control Engineering Engineers' Choice Award.

Moore Industries product families on this page

The manufacturer's catalog is arranged by function, and many of the items listed here map onto it directly:

  • Temperature transmitters: the TRX, and the STZ functional safety dual input smart HART transmitter
  • Alarm trips: the SPA2 programmable limit alarm trip, including an SPA2 with HLPRG input and four relay outputs
  • Signal isolators, repeaters and converters: the SIX
  • PID controllers and backup stations: the 535 in 1/4 DIN format

Other catalog groups include temperature assemblies and sensors, I/P and P/I converters, remote I/O, HART gateways and interfaces, indicators, and fieldbus device couplers.

Where Moore Industries instruments are used

These are control room and marshalling cabinet devices, plus field-mounted transmitters. Typical jobs are isolating a 4-20 mA loop between two systems, converting a thermocouple or RTD signal for a DCS input, adding an independent high or low trip next to the control system, and keeping a control loop running on a backup station when the main controller is out of service. Process plants in oil and gas, chemicals and power across the GCC use them for exactly these tasks.

Moore Industries products we list

Family Examples
Controllers & Data Acquisition Moore 535-21120BD000 | Industrial PID Ba…, SPA2 Programmable Limit Alarm Trip, Moore-SPA2HL Associated IS Programmable…
Isolator & Barrier HIM Smart HART Loop Interface and Monitor, SIX Signal Isolator, SLA SIL 2/3 Safety Logic Solver and Alarm
Temperature Instrumentation STZ Functional Safety Dual Input Smart H…, TRX Temperature Transmitter
Industrial Communications HES HART to Ethernet Gateway
Valve Positioners IPT2 Current-to-Pressure I/P Transmitter

Ordering Moore Industries instruments: what we need

Moore Industries model numbers are built from fields separated by slashes: unit, input, output, power and options, followed by the housing code in brackets. Every field matters. Send the complete string from the label, the serial number, and for programmable units the input type and range you want set. State any hazardous area or functional safety requirement, because approved versions are ordered with their own option codes.

Facts checked against trade press obituaries of Leonard W. Moore (Control Engineering, Control Global), October 2026.

FAQ

Questions about the Moore Industries SIY/PRG/4-20MA/10-42DC [DIN]

Answers from our engineering team on installation, compatibility and integration.

01Is the SIY programmable?
Yes. It is set up with Windows configuration software after choosing current or voltage at the input terminals.
02What input ranges does it accept?
Current 0-20, 4-20, 0-50 and 10-50 mA and voltages 0-1, 0-5, 1-5 and 0-10 V, plus special ranges.
03What isolation does the DIN version have?
500 Vrms input to output to case; the HPP version is rated at 1500 Vrms.
04How accurate is the SIY?
Plus or minus 0.08% of span including all input and output effects.
05How is it powered?
It is loop powered from the 4-20 mA output side with a 10-42 V DC supply.