Brand:

Pepperl+Fuchs KFA5-DU-Ex1.D Timer Relay 115 V AC

Description

Timer relay for 115 V AC panels: KFA5-DU-Ex1.D

North American style control panels, marine switchboards and some older export packages use a 115 V AC auxiliary supply, and the Pepperl+Fuchs KFA5-DU-Ex1.D is the timer-relay barrier made for them. It reads a NAMUR sensor or a dry contact from a hazardous area through an intrinsically safe input and processes the signal with on-delay, off-delay, one-shot or pulse-lengthening functions from 10 ms to 60 minutes.

The supply is 115 V AC plus or minus 10 percent on terminals 23 and 24, drawing 35 mA and 4 VA. There is no Power Rail, and the front keypad sets every parameter.

Quick specification list

  • Input I: NAMUR to EN 60947-5-6, open-circuit 8.2 V, short-circuit 10 mA, switching point 1.2 to 2.1 mA
  • Input II (reset): active above 3 mA, passive below 1.5 mA, 12 V open circuit, 3.5 mA short circuit, minimum pulse 10 ms
  • Relay output on terminals 10, 11, 12 and isolated electronic output on terminals 19+ and 20-
  • Pulse divider from 1:1 to 9999:1; input frequency up to 80 Hz
  • Line fault detection with red LED: breakage 0.15 mA or less, short circuit above 6.5 mA

KFA5-DU-Ex1.D data

Parameter Value
Supply 115 V AC plus or minus 10 percent, 35 mA, 4 VA
Maximum safe voltage Um 253 V AC
Timer range 10 ms to 60 min; resolution under 0.1 percent of setting, minimum 10 ms; accuracy 2 ms
Relay 253 V AC / 2 A / cos phi 0.7 or better; 40 V DC / 2 A; 5 x 10 to the power 7 cycles
Electronic output 40 V / 50 mA, 1-signal about supply minus 2.5 V; off-state current 10 microamps or less
Switching delay of output II 3 ms rising edge, 2 ms falling edge
Temperature influence 0.003 percent per K
Insulation reinforced, 300 Veff between supply, input, reset and outputs
Safe-side values Uo 10.1 V, Io 13.5 mA, Po 34 mW
Certificates TUV 99 ATEX 1408; TUV 02 ATEX 1885 X; IECEx TUN 03.0000; FM 16-538FM-12; UL E223772
Dimensions, mass 40 x 119 x 115 mm, housing C2, about 300 g
Ambient -20 to 60 degrees C

Who needs a 115 V version

Typical buyers are operators of imported skid packages, drilling-support equipment and ship systems whose control transformers deliver 115 V. Replacing a failed timer with a 24 V or 230 V unit would require a new supply, so the exact voltage variant matters more than the function. When an old module label is unreadable, measure the actual supply at terminals 23 and 24 before ordering.

KFA5-DU-Ex1.D compared with KFA6-DU-Ex1.D and KFD2-DU-Ex1.D

The only change between KFA5-DU-Ex1.D and the 230 V twin is the supply: 115 V AC at 35 mA instead of 230 V AC at 15 mA. Both use the 12 V, 3.5 mA reset circuit and reinforced insulation to the supply. The DC version, KFD2-DU-Ex1.D, uses an 18 V, 5 mA reset circuit, a Power Rail and 24 V DC.

Typical timer settings

A valve position contact that bounces during stroke may be given an on-delay of 200 ms. A slow PLC scan may need a 500 ms one-shot. A burner flame sensor might use a three-second off-delay to ride through flicker. Prepare a table of such settings so that replacements can be configured quickly.

Wiring cautions

Mains-rated conductors on terminals 23 and 24 must be separated from intrinsically safe wiring. Fuse the supply appropriately and mark the cabinet with the voltage. The reset input is non-intrinsically-safe and may be driven from a dry contact in the control room.

Maintenance

Check delay accuracy against a stopwatch, test both outputs and record the configuration. Replace the module if the keypad becomes unresponsive.

Verification of a replacement unit

After fitting the module, apply the 115 V supply and confirm that the display shows the programmed values. Simulate the field contact with a 1 kilohm resistor in place of the proximity sensor, for example, to drive the input between its switching limits of 1.2 and 2.1 mA, and observe the outputs. Time the on-delay and off-delay with a stopwatch or the PLC trace. If the process uses the divider function, count a known number of pulses and check the output count. Finally verify the reset input by closing a dry contact for 10 ms or longer while a time function is running, and confirm that the output returns to its idle state at once.

Questions buyers ask about KFA5-DU-Ex1.D

What mains supply does KFA5-DU-Ex1.D need? It needs 115 V AC plus or minus 10 percent on terminals 23 and 24, with a rated current of 35 mA and 4 VA consumption.

What timer functions does KFA5-DU-Ex1.D offer? On-delay, off-delay, one-shot and pulse lengthening, adjustable from 10 ms to 60 minutes, plus a pulse divider of 1:1 to 9999:1.

What does the reset input of KFA5-DU-Ex1.D need? Input II is active above 3 mA and passive below 1.5 mA, with a pulse of at least 10 ms.

How does KFA5-DU-Ex1.D differ from KFA6-DU-Ex1.D? The function is the same, but KFA5-DU-Ex1.D runs on 115 V AC at 35 mA while KFA6-DU-Ex1.D runs on 230 V AC at 15 mA.

Which outputs are on KFA5-DU-Ex1.D? A relay on terminals 10, 11 and 12 and an isolated electronic output on terminals 19+ and 20- rated 40 V and 50 mA.

Documents and quotation

The manufacturer datasheet for KFA5-DU-Ex1.D accompanies this listing as a PDF so your engineers can verify terminals, ratings and approvals before purchase. Include the measured supply voltage at your panel. To request a quotation, send the RFQ with the exact part number KFA5-DU-Ex1.D, the quantity, the delivery location in Oman or the GCC and any project reference. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Installation and Commissioning Planning

Planning ahead shortens downtime when a Pepperl+Fuchs KFA5-DU-Ex1.D goes into service. Confirm the available mounting space, cable entry or process connection, and the tools and spare seals needed on the day. Keep the existing configuration or calibration data so the new unit can be set up to match, and check that loop drawings and the asset register are updated after the swap. If the installation has to fit a short shutdown window, tell us the date when you request a quotation so that delivery of the Pepperl+Fuchs equipment can be planned around it.

Datasheets & Documents
  • PDF Datasheet Pepperl+Fuchs KFA5-DU-Ex1.D Timer Relay 115 V AC Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.

Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.

Pepperl+Fuchs company profile

Founded 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs
Headquarters Mannheim, Germany
Ownership Privately owned (Pepperl+Fuchs SE)
Origins Radio repair workshop that began making replacement transformers
Product families Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures

Milestones

  • 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
  • 1958: The first proximity switch is developed (some company sources say 1959).

Pepperl+Fuchs product families on this page

On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.

Where Pepperl+Fuchs equipment is used

Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.

Pepperl+Fuchs products we list

Family Examples
Isolator & Barrier HiD2030 SMART Transmitter Power Supply w…, KFD2-SR2-Ex2.W K-System Isolated Switch…, KFD2-UT2-Ex2 Universal Temperature Conve…
Industrial Computers Tab-Ex 05 DZ1 WWAN Hazardous Area Tablet, Smart-Ex® 03 DZ2 smartphone for Zone 2/2…
Inductive Proximity Sensors NJ2-12GK-SN NAMUR Inductive Sensor
Power Modules PS1000-A6-24.20 Power Supply 24 VDC 20 A
Photoelectric Sensors R101 Retro-Reflective Photoelectric Sensor
Laser Distance, LiDAR & Radar Sensors R2000 2-D LiDAR Laser Scanner

Ordering Pepperl+Fuchs parts: what we need

Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.

Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.

FAQ

Questions about the Pepperl+Fuchs KFA5-DU-Ex1.D Timer Relay 115 V AC

Answers from our engineering team on installation, compatibility and integration.

01What mains supply does KFA5-DU-Ex1.D need?
It needs 115 V AC plus or minus 10 percent on terminals 23 and 24, with a rated current of 35 mA and 4 VA consumption.
02What timer functions does KFA5-DU-Ex1.D offer?
On-delay, off-delay, one-shot and pulse lengthening, adjustable from 10 ms to 60 minutes, plus a pulse divider of 1:1 to 9999:1.
03What does the reset input of KFA5-DU-Ex1.D need?
Input II is active above 3 mA and passive below 1.5 mA, with a pulse of at least 10 ms.
04How does KFA5-DU-Ex1.D differ from KFA6-DU-Ex1.D?
The function is the same, but KFA5-DU-Ex1.D runs on 115 V AC at 35 mA while KFA6-DU-Ex1.D runs on 230 V AC at 15 mA.
05Which outputs are on KFA5-DU-Ex1.D?
A relay on terminals 10, 11 and 12 and an isolated electronic output on terminals 19+ and 20- rated 40 V and 50 mA.