Brand: Jaquet
Jaquet FTFU 3024-E01 Overspeed Motherboard, FT 3000
Description
Jaquet FTFU 3024-E01 frequency relay motherboard overview
The Jaquet FTFU 3024-E01 is the measuring and monitoring motherboard of the FT 3000 overspeed protection system. One motherboard is used for each channel, that is for each speed sensor, and it performs the measurement and the watchdog functions of that channel. The suffix E01 identifies the input card that is plugged onto the motherboard, a version for electromagnetic and ferrostat sensors, HF sensors, proximity switches and sensors with line amplifiers. The board is a typical spare for turbine and compressor protection racks that are already in service. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.
Key features of the Jaquet FTFU 3024-E01
- Three hardware speed limit monitors for fast overspeed detection, plus a comparator for an acceleration limit.
- Three change-over relays that can be assigned to limits or status functions.
- Three test generators for on line testing of the channel.
- Maximum speed memory and direction sensing.
- Front panel LEDs for power supply, system fault, sensor monitor, direction and limit status.
- The system is designed for IEC 61508 SIL 3 and API 670 applications, according to the manufacturer.
FTFU 3024-E01 technical specifications
The values below come from the manufacturer documentation of the FT 3000 family. They apply to the module with the standard input card E01.
| Part number | FTFU 3024-E01 |
|---|---|
| Brand | Jaquet |
| System family | FT 3000 overspeed protection and speed monitoring |
| Module type | Motherboard, one per measurement channel (sensor), with input card E01 |
| Manufacturer article number | 377Z-03981 |
| Measuring range | 0 to 1 Hz (lowest) up to 0 to 35 kHz (highest) |
| Accuracy | 0.1 percent of the set point |
| Response time | over speed typically signalled by relay in 10 ms |
| Sensor input (card E01) | potential free, 500 V isolation, input voltage 50 mV to 80 V rms |
| Input impedance | 100 kilohm |
| Trigger level | adjustable 0 to plus 3.5 V |
| Sensor supply | about 12 V (11.5 to 12.5 V), maximum 25 mA, short circuit proof |
| Sensor monitoring | static supply current window plus programmable cross check |
| Relay outputs | 3 change-over relays, AC 250 V 5 A 1250 VA, DC 30 V 5 A 150 W |
| Limit values | up to 4 limits for speed or frequency functions |
| Binary inputs | 6, for test, trip reset, lamp test and similar functions |
| Frequency outputs | 2, square wave, 100 ohm output impedance |
| Supply | 18 to 33 VDC, typically 4.5 W, maximum 5.5 W |
| Power-on surge | 7 A |
| Operating temperature | minus 5 to plus 60 degC, plus 70 degC for up to 2 hours |
| Rack format | 3 HE plug-in card, 19 inch frame to DIN 41494 |
| Protection | plugged modules IP 20 |
Measurement and protection functions of the FTFU 3024-E01
The measuring range extends from 0 to 1 Hz up to 0 to 35 kHz, and the accuracy is 0.1 percent of the set point. Once the machine factor or the number of gear teeth is entered, set points and limits are given directly in rpm, or as a percentage of nominal speed. The range can be exceeded up to 55 kHz continuously without damage or loss of function. When a limit is assigned to one of the three speed monitors, the relay reaction time is at most one period of the input frequency plus 9 ms, and the manufacturer quotes a typical overspeed signalling time of 10 ms.
The sensor is monitored statically by a programmable current window and dynamically by cross checks between channels. A sensor fault can be assigned to a relay, and by default one relay of the module signals sensor monitoring while another signals a power supply fault.
Typical applications of the FTFU 3024-E01 in Oman and the GCC
Typical uses named by the manufacturer include single and dual shaft steam turbines, multi shaft aero derivative gas turbines, combined gas and steam turbine plants, compressor overspeed protection in chemical plants, pumps, hydro stations and marine drives. In the Gulf these are power and water plants, gas processing, petrochemical and oil and gas compression sites. A three channel rack with three motherboards of type FTFU 3024-E01 allows internal relay voting such as 2 out of 3, so that a failed channel does not stop the machine without need.
Selection and compatibility notes for the FTFU 3024-E01
Several versions of the motherboard exist, FTFU 3024-E01, -E02, -E03 and -E04, which differ by the input card. The E02 and E04 versions are special cards for specific applications. Choose the version that matches the sensor in your plant and compare it with the type label of the module being replaced. The motherboard works together with the optional FTV 3090 relay card, the FTW 3013 analogue card, the FTK 3072 communication module and the FTZ power supply modules in the same rack.
Installation and commissioning of the FTFU 3024-E01
The module is a plug-in card for a 19 inch card frame. Sensor, binary input, relay and supply connections are made at the rear of the frame by screw terminals or optional Termi-Point connectors. Parameters such as measuring range, limits, hysteresis and relay behaviour are stored in EEPROM and are set by a PC connected to the RS 232 port of the FTK 3072 module. Because the unit is part of an overspeed trip chain, perform the on line test and a full functional test of every limit and relay before the machine is released, and keep a record of the configuration.
Maintenance of the FTFU 3024-E01
The manufacturer gives a mean time between failures of about 230700 hours for each overspeed protection channel and a system life of 20 years. Follow the periodic test interval defined in your safety procedure, use the built in test generators, and keep a spare FTFU 3024-E01 available so that a failed channel can be replaced quickly. Keep the rack within its temperature and humidity limits and avoid condensation.
Related products and ordering notes for the FTFU 3024-E01
Related modules are the FTW 3013 analogue output card, the FTV 3090 relay card, the FTK 3072 communication module, the FTBU 3034 trip chain control card and the FTZ 306x supplies. When you ask for a quotation please state the exact part number FTFU 3024-E01, including the E01 suffix, and the quantity.
Documents and quotation
A manufacturer product sheet of the FT 3000 family that covers the module is available as a datasheet on this page. To receive availability and lead time, send the RFQ with part number FTFU 3024-E01, the quantity and the delivery location, and Seven Star LLC will reply by return.
Other Models in the FT3000 Range
Seven Star LLC supplies models from the FT3000 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Jaquet FTW 3013 Analogue Output Card, FT 3000 | Vibration Monitoring | View details |
| Jaquet FTFU 3024-E01 Overspeed Motherboard, FT 3000 | Vibration Monitoring | You are viewing this model |
Datasheets & Documents
- Datasheet Jaquet FTFU 3024-E01 Overspeed Motherboard, FT 3000 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Jaquet is a Swiss maker of speed sensors and speed measurement systems, based in Basel. Its sensors are used for speed and overspeed measurement on gas and steam turbines, engines, rail vehicles and automotive test benches. TE Connectivity acquired Jaquet in May 2016.
Seven Star LLC, an independent supplier in Muscat, lists Jaquet FT3000 system modules for maintenance teams in Oman and the GCC who need a like-for-like electronic module for a speed measurement rack already in service.
Jaquet company profile
| Location | Basel, Switzerland |
|---|---|
| Ownership | TE Connectivity, since 2016 |
| Markets | Power generation turbines, rail, automotive, industrial engines |
| Product families | Hall effect and inductive speed sensors, FT series speed switches and overspeed protection |
Jaquet FT3000 modules on our site
Two parts are listed at present, both belonging to the FT3000, a rack-mounted overspeed protection and speed measurement system built from plug-in cards. The FTW3013 analog module, type number 377Z-03984, is an analog output card. The FTFU3024-E01, type number 377Z-03981, is the frequency relay motherboard on which the system is based; other FTFU3024 variants carry different type numbers. A specialist distributor lists the FT3000 as discontinued, so the supply of each card has to be checked case by case.
Ordering Jaquet spare parts: what we need
Send the module designation and the full 377Z type number from the label, with any revision or serial number printed beside it. Add a photo of the label and of the rack position, and tell us which machine the system protects. For speed sensors we need the type number, thread, length, connector or cable form and the signal type.
Facts checked against TE Connectivity's acquisition announcement, October 2026.
Browse Jaquet products by category: Vibration.
FAQ
Questions about the Jaquet FTFU 3024-E01 Overspeed Motherboard, FT 3000
Answers from our engineering team on installation, compatibility and integration.
01What is the Jaquet FTFU 3024-E01?
It is the motherboard of one FT 3000 measurement channel, fitted with input card E01. It measures sensor frequency, monitors limits and drives three relays.
02What sensors suit the FTFU 3024-E01?
The E01 input card accepts electromagnetic, ferrostat and HF sensors, proximity switches and sensors with line amplifiers, from 50 mV to 80 V rms input.
03How fast is the overspeed reaction of the FTFU 3024-E01?
The manufacturer states that an overspeed is typically signalled through a relay output in 10 ms.
04What do the E01, E02, E03 and E04 suffixes mean?
They identify the input card plugged onto the FTFU 3024 motherboard. E02 and E04 are special versions for specific applications.
05How do I request a quotation for the FTFU 3024-E01?
Send an RFQ with the part number FTFU 3024-E01, the quantity and the delivery location. No price is shown on this page.