Schneider Electric A9R34463 Acti9 iID 4P 63 A 300 mA RCCB

Description

A9R34463: Acti9 iID 4P 63 A 300 mA type A-SI RCCB

The A9R34463 is a Schneider Electric Acti9 iID residual current circuit breaker (RCCB) with 4 poles, a rated current of 63 A, a sensitivity of 300 mA and an earth-leakage protection class of type A-SI. It clips onto a 35 mm DIN rail, is 72 mm wide (8 modules of 9 mm) and works from 400–415 V AC at 50/60 Hz. Seven Star LLC supplies the A9R34463 in Oman and the GCC as an independent supplier based in Muscat.

The datasheet does not publish an ordering-code table, so we do not decode the digits of the reference ourselves. Treat the parameters listed on this page, which are copied from the datasheet, as the definition of the part: 4 poles, 63 A, 300 mA, type A-SI. When a drawing or schedule quotes only a reference, check each of those parameters against it before ordering.

Durability, ratings and environment of the A9R34463

The datasheet lists 20000 mechanical and 15000 electrical operating cycles, an insulation voltage Ui of 500 V AC, a 6 kV impulse withstand and pollution degree 3. Protection is IP20 on the device and IP40 when it sits in a modular enclosure. It operates from -25 to 60 °C and may be stored from -40 to 85 °C.

The wider operating range, from -25 °C, is helpful in boards that see large swings in temperature, such as unconditioned outdoor kiosks. Inside a closed board in a hot Oman summer the internal temperature can pass the room temperature by a wide margin, so give this unit ventilation and spacing from heat sources such as large contactors and busbars.

Technical specifications of the A9R34463

Parameter Specification
Manufacturer / part number Schneider Electric / A9R34463
Range / product name Acti9 / Acti9 iID
Product type Residual current circuit breaker (RCCB)
Device short name iID
Poles 4P
Rated current [In] 63 A
Earth-leakage sensitivity 300 mA
Earth-leakage protection class Type A-SI
Time delay Instantaneous
Residual current tripping Voltage independent
Network type / frequency AC / 50/60 Hz
Rated operational voltage [Ue] 400–415 V AC
Rated insulation voltage [Ui] 500 V AC
Rated impulse withstand [Uimp] 6 kV
Rated breaking and making capacity Idm 1500 A / Im 1500 A
Rated conditional short-circuit current 10 kA
Neutral position Left
Device location in system Outgoer
Control / signalling Toggle; contact position indicator
Mounting Clip-on, 35 mm DIN rail
Width 72 mm (8 × 9 mm pitches)
Height / depth / embedding depth 85 mm / 69 mm / 44 mm
Net weight 370 g
Colour White (RAL 9003)
Terminals Single terminal top or bottom: 1–35 mm² rigid; 1–25 mm² flexible; 1–25 mm² flexible with ferrule
Wire stripping / torque 14 mm / 3.5 N.m, top or bottom
Locking Padlocking device
Mechanical / electrical durability 20000 / 15000 cycles
Standards EN/IEC 61008-1, EN/IEC 61008-2-1
Product certifications CCC
Degree of protection IP20; IP40 in modular enclosure (IEC 60529)
Pollution degree 3
Operating temperature -25 to 60 °C
Storage temperature -40 to 85 °C
Packing 1 piece, 354.000 g; carton of 27
Warranty 18 months

Typical uses of the A9R34463 in Oman and the GCC

In the region this unit is typically specified for retail units and warehouses, site offices and labour camps and villa and apartment blocks, always together with a miniature circuit breaker or fuse ahead of it. Heat, dust and coastal humidity are the main ageing factors, and they favour closed, well-sealed enclosures and regular test-button checks. For process plants and critical loads the choice of residual current protection and its sensitivity is normally set by the project specification, so follow that over any general advice.

Choosing 300 mA for the A9R34463

The A9R34463 has a 300 mA threshold, typically chosen for fire-risk protection and as a general incomer or sub-board device rather than for personal protection. The datasheet gives an instantaneous tripping time, so the device acts without an intentional delay. If it is installed upstream of other residual current devices, remember that it can trip together with them, and discrimination has to be arranged with a selective device or by splitting the circuits.

Leakage current accumulates across all the equipment downstream, and filters in drives, computers and cleaners all leak a little to earth. If many such loads share one RCCB, the sum may approach the tripping threshold and cause nuisance trips, which is why a board is often split into several residual current stages instead of one large one. Check the earthing system and the installation rules that apply on your site before settling on a sensitivity.

How the A9R34463 protects: residual current without overcurrent

An RCCB compares the current going out on the live conductors with the current coming back. If the difference reaches its sensitivity, which for this unit is 300 mA, a trip mechanism opens all 4 poles. The datasheet lists voltage-independent tripping, meaning the device does not need the line voltage to operate, so it still trips on a residual current if the supply dips or a neutral is lost upstream.

Type A-SI is a type A device, which detects sinusoidal and pulsating DC residual current, with an added super-immunised design. The datasheet describes it as Super Immunised and lists an 8/20 µs impulse withstand of 3000 A, which points to better resistance to nuisance tripping from surges and from the high-frequency leakage of electronic loads. Verify the immunity claims you rely on against the datasheet and the project specification.

The iID has no thermal or magnetic element. It will not open on an overload or a short circuit, and the listed 10 kA conditional short-circuit rating assumes a short-circuit protective device ahead of it. Pair this unit with a miniature circuit breaker or fuse of no more than its own 63 A rating, and check the backup protection against the upstream arrangement.

Installation, testing and upkeep of the A9R34463

Isolate and prove dead, clip the A9R34463 onto the DIN rail, connect conductors as shown on its diagram and torque to 3.5 N.m. After energising, press the test button on the front: the device should trip at once, and the toggle then needs resetting by hand. A failing test means the device must be replaced, not reset.

Plan for a periodic operation of the test button, usually monthly in service. Record the installed rating and sensitivity on the board schedule, and when an RCCB trips for real, find the leakage before closing it again: a repeated trip points to a damaged cable, wet equipment or an earth fault rather than a faulty device.

Selection checklist for the A9R34463

  • Supply: 400–415 V AC and 4 poles, to match a three-phase four-wire circuit.
  • Current: the load through the device must not exceed 63 A, and the upstream protection must not exceed the same value.
  • Sensitivity: 300 mA against the protection goal, people, equipment or fire.
  • Waveform: type A-SI against the loads on the circuit.
  • Backup: a short-circuit device upstream, since the iID does not trip on overcurrent.
  • Space: 8 modules, 72 mm of rail.

Information to send with an RFQ for the A9R34463

  • Exact reference A9R34463 and the quantity needed.
  • Supply voltage, system type and earthing arrangement.
  • Load description, including drives or electronic equipment on the circuit.
  • Upstream protective device and its rating.
  • Other poles, ratings or sensitivities needed in the same order.
  • Delivery location and timeline.

Documents and quotation

The Schneider Electric datasheet for the A9R34463 is attached on this page and holds the full specification summarised above. It is dated 8 Nov 2026 as printed on the manufacturer’s document.

Send us the reference A9R34463, quantity and delivery location and Seven Star LLC will reply to your request. We supply as an independent supplier based in Muscat and do not act for the manufacturer.

Datasheets & Documents
  • PDF Datasheet Schneider Electric A9R34463 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric A9R34463 Acti9 iID 4P 63 A 300

Answers from our engineering team on installation, compatibility and integration.

01What does the A9R34463 protect against?
It is an RCCB with 300 mA sensitivity and type A-SI protection. It trips on earth-leakage current but gives no overload or short-circuit protection, so a breaker or fuse of no more than 63 A must be fitted upstream.
02What supply is the A9R34463 rated for?
The datasheet lists 400-415 V AC AC at 50/60 Hz, 4 poles and a rated current of 63 A, with an insulation voltage of 500 V AC.
03What size and mounting does the A9R34463 have?
It is 72 mm wide, 85 mm high and 69 mm deep (8 modules of 9 mm), weighs 370 g and clips onto a 35 mm DIN rail.
04What conductors fit the A9R34463 terminals?
Top and bottom single terminals take 1 to 35 mm2 rigid, 1 to 25 mm2 flexible and 1 to 25 mm2 flexible with ferrule. Strip 14 mm and tighten to 3.5 N.m.
05What durability is listed for the A9R34463?
The datasheet lists 20000 mechanical and 15000 electrical cycles, IP20 protection and operation from -25 to 60 degrees C.