Schneider Electric SR2B202BD Zelio 20 I/O 24 V DC Relay

Description

SR2B202BD: Zelio Logic smart relay with 20 I/O on 24 V DC

The SR2B202BD is a Schneider Electric Zelio Logic compact smart relay. It packs 12 discrete inputs and 8 transistor outputs into a single housing and replaces a small amount of hard-wired relay logic with a programme held in memory. SR2B202BD is the display and clock-equipped variant powered from 24 V DC, so the first thing to settle before ordering is that your control supply really matches that figure. Seven Star LLC supplies the SR2B202BD in Oman and the GCC as an independent supplier based in Muscat.

Reading the reference against the datasheet values: the letter after SR2 (B) lines up with display and real-time clock; the three digits give the I/O size (20 I/O here); and the suffix (BD) corresponds to the supply of 24 V DC. This reading is our interpretation of the datasheet data rather than a published ordering table, so confirm the exact reference on your drawing before you send an order.

Supply, programme capacity and environmental limits

Rated supply is 24 V DC with limits of 19.2–30 V. The datasheet gives a maximum supply current of 100 mA and a power figure of 3 W, both without extension, which is useful when several units share a small control transformer or a 24 V supply. Reverse polarity protection is fitted.

Operating temperature is −20 to 55 °C, with the lower band of −20 to 40 °C applying in a non-ventilated enclosure; storage is −40 to 70 °C and relative humidity up to 95 % without condensation. Protection is IP20 at the terminal block and IP40 at the front panel, pollution degree 2, overvoltage category III, at altitudes up to 2000 m. In Gulf installations that mostly means the relay belongs inside a closed, ventilated cabinet and not in an open junction box exposed to dust and heat.

The datasheet quotes a programme size of 0–240 with ladder programming; 0–500 with FBD programming, a cycle time of 6–90 ms, and a programme backup of 10 years at 25 °C. The memory is checked on each power-up. Because the unit carries a real-time clock, weekly schedules and timed events can be written directly into the programme; the datasheet gives a clock drift of 12 min/year at 0–55 °C or 6 s/month at 25 °C. The local display allows states and parameters to be read on site.

How the SR2B202BD compares with related Zelio Logic references

The table lists the nearest relatives of the SR2B202BD in the same family, taken from their own datasheets. They share the housing style and the screw-terminal wiring but differ in supply, I/O count, display and clock.

Reference I/O Supply Display Clock Analogue inputs
SR2A201BD 20 24 V DC Yes No 2
SR2E201BD 20 24 V DC No Yes 6
SR2D201BD 20 24 V DC No No 2
SR2B201FU 20 100-240 V AC Yes Yes –
SR2E121BD 12 24 V DC No Yes 4

Technical specifications of the SR2B202BD

Parameter Specification
Manufacturer / part number Schneider Electric / SR2B202BD
Range of product Zelio Logic
Product type Compact smart relay
I/O configuration 20 I/O: 12 discrete inputs, 8 transistor outputs
Local display Yes
Real-time clock Yes
Programme size 0–240 with ladder programming; 0–500 with FBD programming
Cycle time 6–90 ms
Backup time 10 years at 25 °C
Clock drift 12 min/year at 0–55 °C; 6 s/month at 25 °C
Rated supply voltage 24 V DC
Supply voltage limits 19.2–30 V
Maximum supply current 100 mA (without extension)
Power 3 W without extension
Reverse polarity / terminal inversion protection With
Discrete input voltage / current 24 V DC / 4 mA
Analogue inputs 6 (0–10 V; 0–24 V, 8 bits)
Outputs 8 transistor
Output voltage limits 19.2–30 V DC (transistor output)
Output current 0.5–0.625 A transistor output
Net weight 0.28 kg
Protection degree IP20 (terminal block) conforming to IEC 60529; IP40 (front panel) conforming to IEC 60529
Operating temperature -20 to 55 °C (-20 to 40 °C in a non-ventilated enclosure)
Storage temperature -40 to 70 °C
Relative humidity 95 % without condensation or dripping water
Operating altitude 2000 m

Installation, wiring and maintenance of the SR2B202BD

The datasheet specifies screw terminals for 0.2 to 2.5 mm² solid or semi-solid conductors and 0.25 to 2.5 mm² flexible conductors with cable end, with a tightening torque of 0.5 N.m. Wire the supply and input groups in line with the terminal markings, and keep input cabling separate from output cabling that carries inductive loads. For inductive loads on relay outputs, suppression at the load is a standard practice that protects the contacts.

After wiring, power up with the loads disconnected, check each input state, then exercise each output before connecting field equipment. Keep a backup copy of the programme with the project documents so that a replacement unit can be programmed quickly. Site inspections should look at terminal tightness, cabinet temperature and dust build-up on ventilation openings.

Typical uses of the SR2B202BD in Oman and the GCC

With 20 I/O on 24 V DC, SR2B202BD fits small automation tasks where a full PLC would be excessive: gate, door and shutter control, simple conveyor and packing interlocks, and lighting and signage sequences. In the Gulf these panels face high ambient temperatures and fine dust, so cabinet ventilation and the derating note in the datasheet deserve attention. Utilities, facilities contractors and OEM panel builders use units of this size mainly for standalone sequences, local backup logic and retrofits of ageing relay panels.

Inputs and outputs of the SR2B202BD

The inputs on this unit are 24 V class DC inputs of the resistive type rated 24 V DC at 4 mA, conforming to IEC 61131-2 type 1, with a counting frequency of 1 kHz. The datasheet states that three-wire PNP proximity sensors can be connected directly, which makes the unit a natural fit for sensor-driven sequences. State 1 is guaranteed from ≥ 15 V and state 0 up to ≤ 5 V. 6 of the inputs can also be used as analogue inputs with a range of 0–10 V or 0–24 V, 8 bits resolution and a stated conversion error of ± 5 % at 25 °C. The datasheet lists temperature probe types NTC 10k at 25 °C, NTC 1000k at 25 °C, KTY81 210/220/221/222/250, Pt 500, which allows simple thermostat functions without a separate transmitter.

The 8 outputs are transistor outputs at 24 V transistor output with a voltage window of 19.2–30 V DC and a load current of 0.5–0.625 A each. The datasheet lists overload, short-circuit and overvoltage protection on these outputs and a response time of about 1 ms, so they are suited to fast switching of small DC loads, pilot relays or solid-state interfaces rather than direct mains switching.

Selection checklist for the SR2B202BD

  • Confirm the control supply: 24 V DC (polarity matters).
  • Count field inputs and outputs: this unit offers 12 inputs and 8 transistor outputs; spare capacity should be considered before choosing 20 I/O.
  • Check whether the load needs fast DC transistor switching.
  • Decide on display (present) and clock (present) against the programme you intend to write.
  • Check the panel space: the datasheet weight is 0.28 kg and the width and depth should be checked on the datasheet drawing.

Information to send with an RFQ for the SR2B202BD

  • Exact reference SR2B202BD and the quantity required.
  • Control supply voltage and frequency available on site.
  • Type of loads on the outputs and whether surge suppression is fitted.
  • Whether a programming cable or other accessory is needed in the same order.
  • Delivery location and any project deadline.

Documents and quotation

The manufacturer datasheet for the SR2B202BD is attached on this page and lists the full specification summarised above. Check the datasheet revision date against your project requirements.

Send us the reference SR2B202BD, quantity and delivery location and Seven Star LLC will reply with a quotation request confirmation. We supply as an independent supplier based in Muscat.

Other Models in the Se Zelio Sr2 Range

Seven Star LLC supplies models from the Se Zelio Sr2 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric SR2A101FU Zelio 10 I/O 100-240 V AC RelayLogic ControllersView details
Schneider Electric SR2A201BD Zelio 20 I/O 24 V DC RelayLogic ControllersView details
Schneider Electric SR2A201E Zelio 20 I/O 48 V AC RelayLogic ControllersView details
Schneider Electric SR2A201FU Zelio 20 I/O 100-240 V AC RelayLogic ControllersView details
Schneider Electric SR2B121FU Zelio 12 I/O 100-240 V AC RelayLogic ControllersView details
Schneider Electric SR2B121JD Zelio 12 I/O 12 V DC RelayLogic ControllersView details
Schneider Electric SR2B201FU Zelio 20 I/O 100-240 V AC RelayLogic ControllersView details
Schneider Electric SR2B202BD Zelio 20 I/O 24 V DC RelayLogic ControllersYou are viewing this model
Schneider Electric SR2D101BD Zelio 10 I/O 24 V DC RelayLogic ControllersView details
Schneider Electric SR2D201BD Zelio 20 I/O 24 V DC RelayLogic ControllersView details
Schneider Electric SR2E121B Zelio 12 I/O 24 V AC RelayLogic ControllersView details
Schneider Electric SR2E121BD Zelio 12 I/O 24 V DC RelayLogic ControllersView details
Schneider Electric SR2E121FU Zelio 12 I/O 100-240 V AC RelayLogic ControllersView details
Schneider Electric SR2E201B Zelio 20 I/O 24 V AC RelayLogic ControllersView details
Schneider Electric SR2E201BD Zelio 20 I/O 24 V DC RelayLogic ControllersView details
Schneider Electric SR2E201FU Zelio 20 I/O 100-240 V AC RelayLogic ControllersView details
Datasheets & Documents
  • PDF Datasheet Schneider Electric SR2B202BD Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric SR2B202BD Zelio 20 I/O 24 V DC

Answers from our engineering team on installation, compatibility and integration.

01What supply voltage does the SR2B202BD need?
The datasheet lists a rated supply of 24 V DC with limits of 19.2…30 V. Match it to the actual control supply before ordering.
02How many inputs and outputs does the SR2B202BD have?
It is a 20 I/O unit with 12 discrete inputs and 8 transistor outputs. 6 inputs can work as analogue inputs.
03Does the SR2B202BD have a display and a clock?
Display: yes. Real-time clock: yes. These two points are what separate it from other references in the Zelio Logic range.
04What are the output ratings of the SR2B202BD?
Transistor outputs at 24 V with a load current of 0.5…0.625 A transistor output.
05What temperature range does the SR2B202BD allow?
Operation from -20 to 55 degC (-20 to 40 degC in a non-ventilated enclosure) and storage from -40 to 70 degC, with front protection IP40 and terminal block IP20.