- Vibration Monitoring
- Industrial Communications
- PLC & I/O Cards
- Automation Accessories
- Controllers & Data Acquisition
- AC Drives
- Industrial Computers
- Encoders
- Safety Switches & Guard Locking
- Isolator & Barrier
- Automation Software
- HMI Displays
- CCTV & Security
- Motor Soft Starters
- Servo Drives
- Robotics
- Pneumatic Cylinders
- Machine Vision
Brand: SAUTER
Sauter AKM115F120 8 Nm 230 V Rotary Actuator for Ball Valves
Description
The AKM115F120 is the 8 Nm, 230 V~ member of the Sauter AKM rotary actuator family. It turns the spindle of a 2- or 3-way ball valve through 90 degrees in 120 seconds on a switching (2-point or 3-point) signal, which makes it the simplest way to motorise Sauter VKR and BKR ball valves up to DN 50 on heating, chilled-water and fan-coil branches.
Motorising a ball valve without a toolbox
The AKM is designed for ball valves in building services rather than for process isolation. It clips onto the valve with a bayonet ring made of glass-fibre-reinforced plastic, so the datasheet states that it is fitted to ball valves up to DN 50 without tools, and the coupling between valve spindle and carrier stem forms automatically. The actuator is shipped in the middle position. The AKM115 is the stronger of the two sizes: 8 Nm against 4 Nm for the AKM105, for the larger valve sizes in the range.
Key features from the datasheet
- Actuates 2- and 3-way ball valves of types VKR and BKR
- For controllers with a switching output (2-/3-point control)
- Synchronous motor with electronic activation and cut-out, torque-dependent cut-off to save energy
- Maintenance-free gear unit that can be disengaged with a slide switch so the valve can be set by hand with the lever
- Bracket and bayonet ring in glass-fibre-reinforced plastic; fire-retardant plastic housing
- Fitting from vertically upright to horizontal, but never suspended
Technical specification
| Parameter | Specification |
|---|---|
| Type | AKM115F120 |
| Description | Rotary actuator for ball valve |
| Torque | 8 Nm |
| Power supply | 230 V~ ±15 %, 50 to 60 Hz |
| Power consumption | 2.0 W, 4.0 VA on the type overview; 2.0 W, 5.0 VA in the operating table |
| Running time for 90° | 120 s |
| Angle of rotation | 90° |
| Control | 2-point or 3-point |
| Response time | Min. 200 ms |
| Power cable | 1.2 m, 3 × 0.75 mm² |
| Ambient temperature | -10 to 55 °C |
| Ambient humidity | 5 to 95 % rh, no condensation |
| Temperature of medium | Max. 100 °C without an adapter |
| Weight | 0.7 kg |
| Housing | Fire-retardant plastic, lower section black, upper section yellow |
| Type of protection | IP 54 (EN 60529), horizontal |
| Protection class | II (IEC 60730) for the 230 V version |
| Over-voltage category / pollution degree | III / II |
| Standards listed | EN 60730-1, EN 60730-2-14, EN 61000-6-1, -6-2, -6-3, -6-4 |
Derived note: the type overview and the power-consumption table of the same datasheet give slightly different apparent power for this type (4.0 VA and 5.0 VA); size the transformer or fusing on the higher figure.
Selection and ordering guide
The five AKM types differ in torque, running time and voltage. Pick the 8 Nm size when the ball valve is a larger DN or has a stiff seat, and match the supply voltage to the controller output.
| Order code | Torque | Running time | Voltage | Power |
|---|---|---|---|---|
| AKM105F100 | 4 Nm | 30 s | 230 V~ | 2.4 W, 4.5 VA |
| AKM105F120 | 4 Nm | 120 s | 230 V~ | 2.0 W, 4.0 VA |
| AKM105F122 | 4 Nm | 120 s | 24 V~ | 1.6 W, 1.7 VA |
| AKM115F120 | 8 Nm | 120 s | 230 V~ | 2.0 W, 4.0 VA |
| AKM115F122 | 8 Nm | 120 s | 24 V~ | 1.6 W, 1.7 VA |
Only the F100 type has the short 30 second running time; it is the only one whose positioning signal is cut off after 60 seconds, the other types after 3 minutes.
Operation and installation notes
- For 3-point control the stem turns anti-clockwise with voltage on the brown cable (valve opens) and clockwise with voltage on the black cable (valve closes); reversing direction means swapping the connections.
- For 2-point control the black cable always carries voltage; the valve opens when the brown cable is energised and closes when it is de-energised.
- At the end stops or on overload a magnetic coupling takes over and an electronic cut-out switches the signal off, so no limit switches are needed.
- Manual positioning: release the gear unit with the slide switch beside the cable, turn with the lever, then put the switch back to engage the gear unit.
- Keep condensate and dripping water from running down the carrier stem into the actuator; the housing must not be opened.
- Several AKM actuators can be wired in parallel only with accessory 0372459100 (230 V version), which suits an AKM115F120 group.
Where it is used in Gulf projects
Fan-coil units and small air-handling coils are the volume application for 230 V switching ball-valve actuators in Oman and the wider GCC, where chilled water runs for most of the year. The AKM115F120 suits zone valves that are switched fully open or closed by a thermostat, and its IP 54 rating covers plant rooms and ceiling voids rather than exposed roofs. For dusty or coastal sites the datasheet advice to shelter outdoor units applies; confirm valve type and DN before ordering.
Accessories and related items
| Accessory | Description |
|---|---|
| 0372459100 | External switching, 230 V version, for parallel operation with A*M 1*4 or drives with limit switch, incl. junction box |
| 0372459102 | External switching, 24 V version, same use |
| 0510420001 | Adaptor required when the medium is above 100 °C |
| 0510240011 | Adaptor required when the medium is below 5 °C |
| 0510480001 | Auxiliary change-over contacts, single (5(2) A, 24 to 230 V) |
| 0510480002 | Auxiliary change-over contacts, double |
Only one auxiliary change-over contact or one potentiometer can be fitted per actuator.
Frequently asked questions
Which valves does the AKM115F120 drive?
The datasheet names 2- and 3-way ball valves of types VKR and BKR, fitted up to DN 50 with the bayonet ring and no tools.
Is it a modulating or a switching actuator?
It is for controllers with a switching output, either 2-point or 3-point. A continuous 0 to 10 V signal needs a different actuator type.
What is the maximum medium temperature?
Up to 100 degrees C without an accessory; above 100 degrees C adaptor 0510420001 is required and below 5 degrees C adaptor 0510240011.
Can the valve be operated by hand?
Yes. Release the gear unit with the slide switch beside the cable, turn the valve with the lever, then re-engage the gear unit.
Who supplies the AKM115F120 in Oman?
Seven Star LLC is an independent supplier in Muscat and quotes against the exact order code. Confirm the valve type, voltage and accessories before ordering.
Documents and quotation
The official Fr. Sauter AG product data sheet 51.363 for the AKM 105 and 115 (edition 2015) is linked on this page. Send the order code, quantity and valve type to request a quotation. See more in Valve Actuators.
Datasheets & Documents
- Datasheet Sauter AKM 105, 115 product data sheet 51.363 (PDF) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
SAUTER is a Swiss building-automation specialist based in Basel and active since 1910. The group designs and manufactures control valves, actuators, sensors, thermostats and room controllers that regulate heating, ventilation and air conditioning in commercial, industrial and public buildings.
Valves, actuators and field devices
The range covers globe, flanged and ball valves for chilled and hot water, rotary and spring-return actuators for valves and dampers, pressure switches, duct and room sensors, and universal thermostats and temperature limiters.
Controls for rooms and plant
Modbus fan coil thermostats, CO2 and differential-pressure transducers and room controllers feed building management systems in hotels, hospitals, offices, schools and laboratories, where comfort and energy use are managed room by room.
Sourcing SAUTER in Oman
Seven Star LLC supplies SAUTER products to Oman and the GCC as an independent supplier in Muscat, quoting against exact order codes and the official SAUTER data sheets.
Related products
Frequently Asked Questions
The datasheet names 2- and 3-way ball valves of types VKR and BKR, fitted up to DN 50 with the bayonet ring and no tools.
It is for controllers with a switching output, either 2-point or 3-point. A continuous 0 to 10 V signal needs a different actuator type.
Up to 100 degrees C without an accessory; above 100 degrees C adaptor 0510420001 is required and below 5 degrees C adaptor 0510240011.
Yes. Release the gear unit with the slide switch beside the cable, turn the valve with the lever, then re-engage the gear unit.
Seven Star LLC is an independent supplier in Muscat and quotes against the exact order code. Confirm the valve type, voltage and accessories before ordering.

Reviews
There are no reviews yet.