- AC Drives
- Industrial Communications
- PLC & I/O Cards
- Vibration Monitoring
- Automation Accessories
- Controllers & Data Acquisition
- Safety Switches & Guard Locking
- CCTV & Security
- Encoders
- Industrial Computers
- HMI Displays
- Motor Soft Starters
- Isolator & Barrier
- Pneumatic Cylinders
- Servo Drives
- Automation Software
- Robotics
- Machine Vision
Brand: Lovato Electric
Lovato VLB107A240XX 0.75 kW VLB1 Drive Power Unit
Description
0.75 kW VLB1 power unit without keypad for single-phase supply
Variable speed from a single-phase supply is what the VLB107A240XX (VLB1 series, 0.75 kW, 4.2 A) provides; input 200-240VAC 50/60Hz, output 0-599 Hz. It lets a squirrel-cage motor accelerate and run at controlled speed.
Overload capacity is 150% for 60s; 200% for 3s, with a switching frequency of 2-16kHz.
This code is the power-unit version: it has no integrated keypad, so a keypad or configuration tool is selected separately to commission it. Confirm the control interface you need before ordering.
Technical specifications
| Parameter | Specification |
|---|---|
| Order code | VLB107A240XX |
| Product designation | Variable speed drives |
| Product type designation | VLB1 |
| Rated power supply voltage | 200-240VAC 50/60Hz |
| Rated output current | 4.2 A |
| Rated output power | 0.75 kW |
| EMC filter | Built-in EMC suppressor cat. C1/C2 |
| Input type | Single-phase |
| Rated mains voltage | 200-240 VAC |
| Operating mains voltage range | 170-264 VAC |
| Rated mains frequency | 50/60 Hz |
| Operating mains frequency range | 45-65 Hz |
| Rated mains current without mains choke | 10 |
| Rated mains current with mains choke | 8.8 |
| Output type | Three-phase |
| Output voltage range | 0-240 VAC |
| Output frequency range | 0-599 Hz |
| Current overload | 150% for 60s; 200% for 3s %/s |
| Apparent output power | 1.6 |
| Power loss | 4kHz: 29W |
| Brake chopper | Yes |
| Switching frequency | 2-16kHz |
| Motor control modes | V/f linear, V/f quadratic, V/f multipoint, sensorless vector control, ECO mode, servo control with encoder feedback, torque setpoint, sensorless control for synchronous motors |
| Functions and protections provided | 3-wire control, S-shape curves, Slip compensation, Flying restart, DC braking, DC injection at start, PID control, Sequencer (programmable frequency/time cycles), Preset speeds, Motorpotentiometer, Different parameter configuration sets, Parameters changeover function, Favorite parameters menu, Autotuning, PTC probe input |
| Safe torque Off (STO) safety function | Optional |
| Protections | Overcurrent Output short circuit and earth/ground leakage Overvoltage Undervoltage Phase loss Motor heat overload (i2t) Overspeed Speed reverse |
| Special funct. | Multi-pump PID control (1 main pump frequency regulated + 2 auxiliary pumps activated in direct mode in case of necessity) |
| Number of digital input | 5 |
| Digital input type | Selectable PNP or NPN logic |
| Number of digital output | 1 |
| Digital output arrangement | 1 relay output with changeover contact (C/O-SPDT) + 1 digital output |
| Output contacts ratings | Relay output: 3A 250VAC Digital output: 100mA max 30VDC |
| Number of analog input | 2 |
| Analog input type | Configurable 0/2-10VDC, -10-+10VDC, 0-5VDC, 0/4-20mA |
| Number of analog output | 1 |
| Analog output type | configurable as 0-10VDC, 0-5VDC, 2-10VDC, 0/4-20mA |
| Operating temperature (min) | -10 °C |
| Operating temperature (max) | +60 (with derating over +45°C) |
| Current derating | Switching frequency 2 or 4kHz: 2.5%/°C over 45°C switching frequency 8 or 16kHz: 2.5%/°C over 40°C |
| Storage temperature (min) | -25 °C |
| Storage temperature (max) | +60 °C |
| Max altitude | 4000m (over 1000m derate the rated current by 5%/1000m) |
| Maximum Pollution degree | 2 |
| Overvoltage category | III up to 2000m altitude (II above 2000m) |
| Installation position | Vertical |
| IP degree of protection | IP20 |
| Dimensions (W x H x D) | 60 x 214 x 130 mm |
| Weight | 1 Kg |
Sizing and selection
With 4.2 A available at the output, motors up to about 0.75 kW fit, but always confirm by nameplate current and duty (the overload figure is 150% for 60s; 200% for 3s). A mains choke reduces the input current figure of 10 A and is a common choice on weak supplies.
Control modes listed: V/f linear, V/f quadratic, V/f multipoint, sensorless vector control, ECO mode, servo control with encoder feedback, torque setpoint, sensorless control for synchronous motors.
A brake chopper is built in and the safe-torque-off function is optional.
Applications and installation
Use cases range from single booster pumps to packaging-line conveyors and fan walls. Check the motor control modes listed below and the maximum motor cable length table, because both depend on the type of motor and cable installed.
Installation data: 60 x 214 x 130 mm, 1 Kg, IP20. Vertical mounting is required; allow airflow above and below the unit and observe the altitude derating stated in the table.
Commissioning the VLB1 power unit on a single-phase supply
Since the VLB107A240XX arrives without an integrated keypad, plan the commissioning method before the drive reaches site, so that the technician has the configuration tool or keypad ready on the day. Start by checking that the incoming single-phase supply sits within the stated operating range and that the earth connection is sound. Enter the motor nameplate data, run the autotuning routine where the chosen control mode benefits from it, and set acceleration and deceleration ramps that suit the driven machine rather than leaving factory values in place.
Test the digital inputs, the relay output and any analog signals against the control system before handing over. If the multi-pump PID function is used on a booster set, confirm the staging logic with the actual pumps and pressure transmitter, and save the final parameter set so it can be restored if the unit is ever replaced.
Panel layout and wiring practice
Keep the motor cable as short as the layout allows and run it apart from signal and control cables. Use a screened motor cable where the EMC category matters, and terminate the screen correctly at both ends according to the manufacturer’s guidance. If a braking resistor is connected to the built-in brake chopper, mount it where its heat cannot affect the drive or other panel components.
Heat, dust and humidity in Omani installations
The current derating above 45 °C becomes relevant quickly in GCC summers, particularly in small enclosures on rooftops or pump stations without air conditioning. Estimate the internal panel temperature, consider a lower switching frequency where motor noise is acceptable, and provide filtered ventilation or cooling as needed. An IP20 drive must be protected by its enclosure against fine sand and dust, which can block airflow paths, and against condensation in humid coastal areas.
Maintenance routine
With the supply isolated and after the waiting time stated in the documentation, inspect for dust build-up, clean or replace enclosure filters, check terminal tightness and review the fault history for recurring trips. Recurrent overcurrent or overvoltage events usually point to ramp settings, the load or the supply rather than the drive itself.
Documents and quotation
The Lovato Electric datasheet for VLB107A240XX (English, exported from the manufacturer’s online catalogue) is attached and is the source of the figures above. Please confirm the motor nameplate current, the supply type and voltage, the EMC category needed for your cable lengths and whether a keypad or safe-torque-off option is required before you order, and note that the manufacturer may revise datasheet values. Related items are listed under ac drives. To request VLB107A240XX, send the quantity and delivery location with the quotation form; Seven Star LLC is an independent supplier based in Muscat.
Datasheets & Documents
- Datasheet Lovato Electric VLB107A240XX datasheet (EN, catalogue export) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Lovato Electric is the Italian manufacturer of low-voltage electrical components for industrial automation and power distribution: contactors, motor protection circuit breakers, soft starters, variable speed drives, power factor controllers, transfer switch and generator controllers, and energy meters. It was founded in Bergamo in 1922 and has been run by the same family for four generations. Its headquarters is in Gorle, near Bergamo, and it celebrated its centenary in 2022.
Seven Star LLC is an independent supplier in Muscat. We list Lovato motor control, drives and power management products, and supply them to panel builders, contractors and maintenance teams in Oman and the GCC by order code.
Lovato Electric at a glance
| Established | 1922, Bergamo, Italy |
|---|---|
| Headquarters | Gorle (Bergamo), Italy |
| Ownership | Private, family-run for four generations |
| Product families | Contactors and relays, motor protection circuit breakers, motor starters, soft starters, variable speed drives, power factor controllers, ATS and gen-set controllers, multimeters and energy meters, micro PLCs |
Lovato products we list
| Family | Models | Typical use |
|---|---|---|
| Contactors | BF0910A230, BF1810A230, BF2510A230, BF2600A230, BF09T4A230 4-pole, BFS0923A024, 11BG0910A230 mini, 11BGR0901A048 reversing | Switching motors, heaters, lighting and capacitor banks |
| Motor protection and starters | SM1P0650, SM1P1000, SM1P3200, M1P enclosed DOL starter, ME024FD024, ME070RSD024, 31L48 time relay | Short-circuit and overload protection and direct starting of motors |
| Soft starters | ADXL0030600, ADXL0085600, ADXL0135600, ADXT0034, ADXT0084, ADXT0139 | Reducing starting current and mechanical shock on pumps, fans and compressors |
| Variable speed drives | VLA1, VLB1, VLB3 0.75 kW, VLB3 2.2 kW, VLB3 5.5 kW, VLB3 22 kW, VT1 | Speed control of pumps, fans and conveyors to save energy |
| Power management and control | DCRG8, DCRL8 PF controllers, ATL600 ATS controller, RGK600 gen-set controller, DMG200 multimeter, DMED300T2 energy meter, LRD20 micro PLC | Power factor correction, mains/generator changeover and energy monitoring |
Lovato order codes describe the product. On a contactor such as BF0910A230, "BF09" is the frame and rated current (9 A in AC-3), "10" is the built-in auxiliary contact (one normally open), "A" means an AC coil and "230" is the coil voltage. The coil voltage must match the control circuit exactly, so it is the most common detail to check when replacing one. For motors, a soft starter limits the inrush current at start and stop, while a variable speed drive controls the speed continuously and saves energy on pumps and fans that do not need full flow all the time.
Where Lovato products are used
In Oman and the GCC, Lovato components are built into motor control centres, pump and HVAC panels, capacitor banks for power factor correction, generator and ATS panels, and machine control panels for industry, water and buildings.
Ordering Lovato products: what we need
Send the full Lovato order code. For contactors and starters, confirm the coil or control voltage. For drives and soft starters, send the motor power, current and supply voltage. For power factor controllers, send the number of steps and the CT ratio.
Facts checked against Lovato Electric company profile brochures, October 2026.
Browse Lovato Electric products by category: Motor Soft Starters, Automation Accessories, Controllers & Data Acquisition, PLC & I/O Cards, Circuit Breakers, Diesel Generator Spare Parts.
Related products
Frequently Asked Questions
0.75 kW at 4.2 A output current, from a supply of 200-240VAC 50/60Hz.
The datasheet lists the input type as single-phase with rated mains voltage 200-240VAC 50/60Hz.
It is listed with Built-in EMC suppressor cat. C1/C2.
150% for 60s; 200% for 3s.
1 Kg.

Reviews
There are no reviews yet.