Brand:

Mean Well EDR-120-24 DIN Rail Power Supply

Description

Economy 24 V DIN rail supply with a 40 mm footprint

The Mean Well EDR-120-24 is a 120 W single-output DIN rail power supply with a 24 V DC, 5 A output. The EDR-120 series is described by Mean Well as an economical slim series for TS-35/7.5 or TS-35/15 rails, with a metal housing that helps the unit shed heat and a body 40 mm wide.

Input is universal: 90 to 264 VAC, or 127 to 370 VDC through the AC terminals. The 24 V model reaches 87.5% typical efficiency and is cooled by free air convection. Protection covers short circuit, overload, overvoltage and overtemperature, and the constant-current overload characteristic suits inductive and capacitive loads.

Technical specifications

Parameter Specification
Manufacturer / series Mean Well, EDR-120
Model EDR-120-24
DC output 24 V DC / 5 A
Power rating 120 W
Trim range 24 to 28 V
Ripple (max.) 120 mVp-p
Setpoint tolerance +/-1.0%
Regulation (line / load) +/-0.5% / +/-1.0%
Mains input 90 to 264 VAC; 127 to 370 VDC
Typical efficiency 87.5%
Input current (typ.) 2.25 A at 115 VAC; 1.3 A at 230 VAC
Inrush (typ.) 20 A at 115 VAC; 35 A at 230 VAC
Hold-up (typ.) 16 ms at 230 VAC; 10 ms at 115 VAC
Overload behaviour 105 to 130%, constant current limiting, auto recovery
Overvoltage limit 29 to 33 V, shut down; re-power to recover
Ambient operating range -20 to +60 C, with derating curve
Dielectric strength Input-output 3 kVAC; input-FG 2 kVAC; output-FG 0.5 kVAC
Approvals named UL 508, TUV EN 62368-1, EAC TP TC 004, BSMI
Size (W x H x D) 40 x 125.2 x 113.5 mm
Mass 0.6 kg

Choosing between the 120 W DIN rail series

Mean Well offers several 120 W DIN rail families with the same 40 mm width, and the differences matter at purchase. The EDR-120 has an operating range up to +60 C at full load, which is 10 C lower than the NDR-120 data. It is a sensible choice for temperature-controlled cabinets where cost is the main driver. Where the panel runs hot, compare the derating curve in the datasheet or consider a family rated to +70 C.

Installation and operating checks

Fit the unit on the rail with the recommended clearances: 40 mm above, 20 mm below and 5 mm at each side when running at continuous full load. Check the input range against your supply: below 90 VAC the datasheet requires derating. The output potentiometer adjusts the voltage between 24 and 28 V, The datasheet for this series does not list a DC OK relay contact, so use an external monitoring relay if the control system needs a power-fail signal. Record the nameplate output and date code at commissioning so that a replacement can be matched quickly if the supply is ever swapped on a running line.

Documents and quotation

The official manufacturer datasheet is linked in the Datasheet & Documentation section at the end of this page. Please quote EDR-120-24 with the quantity, available mains, expected load and its peak, ambient temperature and approvals needed. More supplies can be found in Power Modules.

Reliability, EMC and environmental data for the Mean Well EDR-120-24

The values below are taken from the official Mean Well EDR-120 specification and complement the main table above.

Parameter Value (official datasheet)
Working humidity 20 – 95% RH non-condensing
Storage temperature -40 to +85°C, 10 – 95% RH
Vibration 10 – 500 Hz, 2G (component); mounting to IEC 60068-2-6
EMC emission EN 55032 (CISPR32) Class A, EN 61000-3-2/-3, CNS15936 Class A
Hold-up time (typ.) 16 ms at 230 VAC; 10 ms at 115 VAC
MTBF 2718.3K hours min. (Telcordia SR-332); 474.7K hours min. (MIL-HDBK-217F, 25°C)
Weight 0.6 kg

How the EDR-120-24 works

The EDR-120-24 uses the architecture shown in the Mean Well block diagram: an EMI filter and input rectifiers, a PWM-controlled power switching stage at about 70 kHz, and output rectifiers and filter that produce the isolated 24 V rail. The control circuit regulates the output and the protection functions cover short circuit, overload, over-voltage and over-temperature. The EDR family is the economical DIN rail range, and its emission rating is Class A rather than Class B.

Selection & Ordering Guide

The EDR-120 series is available in three output voltages:

  • EDR-120-12: 12 V DC, 10 A
  • EDR-120-24: 24 V DC, 5 A
  • EDR-120-48: 48 V DC, 2.5 A

Because the emission level is EN 55032 Class A, the EDR-120-24 is intended for industrial environments. For residential or light commercial buildings where Class B emission is required, compare it with a Class B series such as NDR-120.

Installation & Maintenance

  • Isolate and lock out the supply circuit before wiring; installation should be carried out by a qualified electrician.
  • Use the conductor sizes, terminal data and protective earth connection shown in the official datasheet.
  • Respect the mounting orientation and clearances given by Mean Well so that the cooling of the EDR-120-24 works as designed.
  • After commissioning, measure the output voltage at the load and trim it only within the documented adjustment range.
  • During planned maintenance, check terminals for tightness and discolouration, remove dust, and confirm that the cabinet temperature stays inside the derating curve.

Typical Applications in Oman & the GCC

The EDR-120-24 suits cost-sensitive industrial panels in Oman and the GCC: machine control cabinets, conveyor and packaging lines, pump control panels in industrial plants, and general 24 V automation where Class A emission is acceptable. Check the cabinet temperature against the derating curve, since full load is specified up to +60°C.

Why Source from Seven Star LLC

Seven Star LLC supplies Mean Well products, including the EDR-120-24, to panel builders, contractors and maintenance teams across Oman and the GCC. Send us the model code and quantity to request a quote, and our team can help confirm the correct ordering code, the right variant and any accessories for your project. When you are replacing an existing unit, share the nameplate data and we will compare it with the official EDR-120 documentation before you order.

Datasheets & Documents
  • PDF Datasheet Mean Well EDR-120 series datasheet (EN) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Mean Well is the Taiwanese manufacturer of standard switching power supplies: DIN rail, enclosed and open-frame supplies, LED drivers, DC-DC converters, battery chargers and high-power rack systems. It was founded in 1982 and is headquartered in New Taipei City, with production in Taiwan and China. Its catalogue of thousands of standard models is widely used in control panels, LED lighting and telecom equipment.

Seven Star LLC is an independent supplier in Muscat. We list Mean Well power supplies for control panels, automation equipment, lighting and electronics in Oman and the GCC.

Mean Well company profile

Founded 1982, Taiwan
Headquarters New Taipei City, Taiwan
Ownership Mean Well Enterprises Co., Ltd., privately held
Product families SE, MSP, HRPG and LRS enclosed supplies, HDR, NDR, SDR and XTR DIN rail supplies, LED drivers, DC-DC converters, battery chargers and redundancy modules

Mean Well product series

DIN rail supplies include the MDR, DRA, EDR, NDR and SDR families, the ultra-slim XDR, the wide-input WDR and the three-phase TDR and XTR families, plus DDR DIN rail DC-DC converters. Enclosed supplies include the LRS, SE, SPV, MSP and HRPG families and the RST three-phase 5 kW unit. For lighting, the LPV constant voltage supply and the ELG LED driver are IP-rated for outdoor use.

The model code shows the family, the power and the output voltage: NDR-120-24, for example, is the NDR family, 120 W, 24 V output.

Where Mean Well power supplies are used

24 V control circuits in machine and process control panels, PLC and instrument supplies, telecom and security systems, LED lighting, battery charging and industrial electronics.

Mean Well products we list

Family Examples
Power Modules DDR-15L-24 DIN Rail DC-DC Converter, DRA-40-12 DIN Rail Power Supply, EDR-120-24 DIN Rail Power Supply, ELG-200-24A 24 V 200 W IP65 LED Driver with, HRPG-450-15 Enclosed Power Supply, LPV-100-12 12 V 102 W IP67 Constant Voltage, LRS-150-48 Enclosed Switching Power Supply, MDR-40-12 DIN Rail Power Supply and 10 more

Ordering Mean Well power supplies: what we need

State the exact model code, the output voltage and current, the input range (single-phase, three-phase or DC), the mounting style, the cabinet or ambient temperature and any approvals required, so the correct variant can be quoted.

Facts checked against Mean Well's published corporate profile, October 2026.

FAQ

Questions about the Mean Well EDR-120-24 DIN Rail Power Supply

Answers from our engineering team on installation, compatibility and integration.

01What is the EDR-120-24 output rating?
24 V DC at 5 A, 120 W, adjustable from 24 to 28 V.
02What is the maximum ambient temperature?
The datasheet gives -20 to +60 C with a derating curve.
03What mains range is accepted?
90 to 264 VAC, or 127 to 370 VDC through the AC terminals.
04How wide is the housing?
40 mm; height 125.2 mm and depth 113.5 mm.
05What warranty does the series carry?
The datasheet lists 2 years.