Schneider Electric A9F54106 iC60H 1P 6A C Circuit Breaker

Description

A9F54106: single-pole 6 A C-curve miniature circuit breaker

The A9F54106 is a Schneider Electric Acti9 iC60H miniature circuit-breaker, listed in the datasheet as Acti9 iC60H 1P 6A C Miniature Circuit breaker. The reference describes a 1P device rated 6 A with a C trip curve, built for AC and DC networks with a thermal-magnetic trip unit. The datasheet gives a breaking capacity of 15 kA Icu at 220–240 V AC under EN/IEC 60947-2, which is the headline figure for a 230 V network. Seven Star LLC supplies the A9F54106 in Oman and the GCC as an independent supplier based in Muscat.

The datasheet for this reference carries the date 8 Nov 2026 and does not state a lifecycle status, so confirm availability before ordering. A 6 A rating is the classic lighting-circuit and control-circuit size, also used for small power supplies and socket-free auxiliary feeders. The datasheet also lists compatibility with add-on residual current devices: Vigi iC60 single terminal add-on residual current device 25/40/63 A; Quick Vigi iC60 single terminal add-on residual current device 25/40 A.

Technical specifications of the A9F54106

Parameter Specification
Manufacturer / part number Schneider Electric / A9F54106
Range / product name Acti9 / Disbo iC60
Product type Miniature circuit-breaker
Device short name iC60H
Poles 1P (1 protected pole)
Rated current [In] 6 A
Curve / trip unit Curve C, thermal-magnetic
Network type / frequency AC/DC, 50/60 Hz
Magnetic tripping limit 8 x In ± 20 %
Rated operational voltage [Ue] 12–60 V AC 50/60 Hz; 100–133 V AC 50/60 Hz; 220–240 V AC 50/60 Hz; 12–60 V DC; 60–72 V DC
Rated insulation voltage [Ui] 500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand [Uimp] 6 kV conforming to EN/IEC 60947-2
Mounting Clip-on on rail, 2 pitches of 9 mm
Height / width / depth 85 mm / 18 mm / 78.5 mm
Net weight 0.125 kg
Terminals Top or bottom, single terminal: 25 mm² rigid, 16 mm² flexible
Stripping length / torque 14 mm for top or bottom connection; 2 N.m top or bottom
Durability 20000 cycles mechanical; 10000 cycles electrical
Handle / indication Toggle, contact position indicator, trip indicator, padlockable
Protection / environment IP20 conforming to IEC 60529; pollution degree 3; overvoltage category IV; tropicalisation 2
Humidity / temperature 95 % at 55 °C; operation -35–70 °C; storage -40–85 °C

Using a 6 A rating: what the A9F54106 protects

Low-current ratings need attention to cable and load rather than to fault level. A very small breaker does not protect a cable against anything the cable could not already survive, so its job is mostly to isolate a faulty control feeder quickly and to give the maintenance team a visible, labelled switch point. The thermal element is slow by design, so short switching surges from transformers or power supplies are normally tolerated, while the magnetic element still acts at 8 times the rated current with a tolerance of 20 %.

The C curve of the A9F54106 trips magnetically at 8 x In ± 20 %. In general engineering practice a C curve is chosen for mixed loads with moderate starting currents, such as lighting, small motors and power supplies, rather than for loads with extreme inrush.

Breaking capacity of the A9F54106 by voltage band

Breaking capacity is the figure that decides whether a breaker can be installed at a given point of the network. Icu is the ultimate capacity; Ics is the service capacity, expressed as a share of Icu, after which the device is still expected to remain serviceable. For the A9F54106 the datasheet lists the following.

Voltage band Icu Ics
12–60 V AC 50/60 Hz 42 kA 21 kA (50 % of Icu)
100–133 V AC 50/60 Hz 30 kA 15 kA (50 % of Icu)
220–240 V AC 50/60 Hz 15 kA 7.5 kA (50 % of Icu)
12–60 V DC 20 kA 20 kA (100 % of Icu)
60–72 V DC 15 kA 15 kA (100 % of Icu)

The datasheet adds a rated short-circuit capacity Icn of 10000 A at 240 V AC 50/60 Hz under EN/IEC 60898-1, the household-standard rating. The limitation class is 3, which describes how strongly the device limits the let-through energy of a short circuit. Compare these values with the prospective fault current at the installation point; if the supply side can exceed them, the design needs a higher-rated device or upstream back-up protection.

Information to send with an RFQ for the A9F54106

  • Full reference (A9F54106) and quantity
  • Supply voltage, frequency and AC or DC use at the installation point
  • Prospective short-circuit current and the load or cable the breaker protects
  • Existing board, rail and neighbouring devices, including any add-on residual current device
  • Delivery location, timing, and whether the order is a spare or a new installation

Installation and maintenance of the A9F54106

The A9F54106 clips onto a rail; the datasheet lists the mounting mode as clip-on. Strip conductors to 14 mm and tighten terminals to 2 N.m, using a calibrated screwdriver. Terminals accept 25 mm² rigid and 16 mm² flexible conductors at either the top or the bottom. The handle can be padlocked in the off position for isolation during maintenance.

Check periodically that the trip indicator is clear, that the handle moves freely and that terminals have not discoloured. Mechanical durability is 20000 cycles and electrical durability is 10000 cycles. A device that has cleared a heavy fault should be inspected and replaced rather than assumed intact.

1P construction of the A9F54106

As a single-pole device, it interrupts one live conductor and occupies two 9 mm pitches (18 mm) of rail. It is chosen for phase conductors of single-phase circuits and for individual poles in installations where each phase is protected separately. Where the neutral also has to be switched, or where two phases supply the load, a two-pole version is the correct step.

Net weight is 0.125 kg and the body is 18 mm wide, 85 mm high and 78.5 mm deep, so a panel layout should reserve 18 mm of rail per device plus a small gap for heat when several breakers sit side by side.

Where the A9F54106 is used in Oman and the GCC

In Oman and the GCC the iC60H family appears in commercial buildings, industrial distribution boards, utility auxiliary panels and process cabinets. The this unit fits circuits where a 6 A single-pole breaker with a high fault capacity is needed in a compact 9 mm module. Gulf plant rooms combine heat, dust and humidity; the datasheet gives operation from -35–70 °C, relative humidity of 95 % at 55 °C and tropicalisation class 2, so site conditions should be compared against these limits and against the derating practice of the board builder.

The A9F54106 within the iC60H 1P C-curve range

The closest same-width neighbours are A9F54104 (4 A) and A9F54102 (2 A), which share the housing and differ in the thermal setting and in the figures shown below. The same 6 A rating in another pole count is available as A9F54206 (2P, 36 mm wide) and A9F54306 (3P, 54 mm wide). The table lists every reference of this pole count that appears in our catalogue range.

Reference Rated current Icu at 220–240 V AC Rigid terminal
A9F54101 1 A 70 kA 25 mm²
A9F54102 2 A 70 kA 25 mm²
A9F54104 4 A 70 kA 25 mm²
A9F54106 (this page) 6 A 15 kA 25 mm²
A9F54110 10 A 15 kA 25 mm²
A9F54116 16 A 15 kA 25 mm²
A9F54120 20 A 15 kA 25 mm²
A9F54125 25 A 15 kA 25 mm²
A9F54132 32 A 15 kA 35 mm²
A9F54140 40 A 15 kA 35 mm²
A9F54150 50 A 15 kA 35 mm²
A9F54163 63 A 15 kA 35 mm²

Documents and quotation

A datasheet for the this unit is attached on this page. It lists the electrical, mechanical and environmental data summarised above and should be read together with the manufacturer’s installation instructions.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.

Other Models in the Se Ic60h 1p C Range

Seven Star LLC supplies models from the Se Ic60h 1p C range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric A9F54101 iC60H 1P 1A C Circuit BreakerCircuit BreakersView details
Schneider Electric A9F54102 iC60H 1P 2A C Circuit BreakerCircuit BreakersView details
Schneider Electric A9F54104 iC60H 1P 4A C Circuit BreakerCircuit BreakersView details
Schneider Electric A9F54106 iC60H 1P 6A C Circuit BreakerCircuit BreakersYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Schneider Electric A9F54106 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric A9F54106 iC60H 1P 6A C Circuit

Answers from our engineering team on installation, compatibility and integration.

01What is the rated current of the A9F54106?
The datasheet gives 6 A, with a C curve and a thermal-magnetic trip unit. The magnetic tripping limit is 8 x In plus or minus 20 %.
02What breaking capacity does the A9F54106 have at 230 V AC?
The datasheet lists 15 kA Icu for the 220 to 240 V AC band, with a service capacity Ics of 7.5 kA. Compare it with the prospective fault current at the installation point.
03How wide is the A9F54106 and how many poles does it have?
It is a 1P device, 18 mm wide, 85 mm high and 78.5 mm deep, occupying 2 pitches of 9 mm on the rail.
04What conductors fit the A9F54106 terminals?
The datasheet lists single terminals at top or bottom for 25 mm2 rigid and 16 mm2 flexible conductors, with a tightening torque of 2 N.m.
05Can the A9F54106 be used on DC circuits?
The datasheet lists network type AC/DC with DC ratings in the breaking-capacity table: 20 kA Icu at 12 to 60 V DC; 15 kA Icu at 60 to 72 V DC. Check the polarity and voltage of the real circuit against these bands.