Brand: Schneider Electric
Schneider Electric A9F44270 Acti9 iC60N 2P 0.5A C MCB
Description
A9F44270: Acti9 iC60N 2P 0.5 A C-curve breaker
The A9F44270 is an Acti9 iC60N miniature circuit breaker from Schneider Electric: 2P, rated 0.5 A, thermal-magnetic trip unit and C tripping curve. It has two protected poles, which suits a single-phase circuit that must break both phase and neutral, or a two-wire DC circuit. Seven Star LLC supplies the A9F44270 in Oman and the GCC as an independent supplier based in Muscat.
The reading of the part number is taken from the product title and datasheet fields rather than from a published ordering key: A9F44270 sits in the iC60N range with 2 poles, a 0.5 A rating and curve code C. The datasheet marks this reference as discontinued, with a stated discontinuation date of 13 Sep 2024. Availability therefore depends on remaining stock, and a current replacement reference may be needed. The datasheet was generated on 8 Nov 2026, and the figures below follow it.
Breaking capacity and DC use of the A9F44270
Breaking capacity is the largest fault current the device can interrupt. Icu is the ultimate capacity; Ics is the service capacity after which the breaker is still expected to remain usable, shown here as a percentage of Icu. This is the higher breaking-capacity version in the iC60N family: its datasheet shows 50 kA at both 230 V and 400 V class voltages, which is notable for such a small breaker. Always read the figure against the exact reference, because the larger ratings in the same family show lower values.
| Voltage | Icu | Ics |
|---|---|---|
| 12–133 V AC 50/60 Hz | 50 kA | 50 kA (100 %) |
| 220–240 V AC 50/60 Hz | 50 kA | 50 kA (100 %) |
| 380–415 V AC 50/60 Hz | 50 kA | 50 kA (100 %) |
| 440 V AC 50/60 Hz | 25 kA | 25 kA (100 %) |
| ≤ 125 V DC | 10 kA | 10 kA (100 %) |
Under EN/IEC 60898-1 the datasheet also lists 6000 A Icn at 415 V AC. The network type is AC/DC; for direct current the stated rated operational voltage is up to 125 V DC V DC with 10 kA Icu, and the breaker should not be applied beyond that.
Technical specifications of the A9F44270
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / A9F44270 |
| Range / product name | Acti9 / Disbo iC60 |
| Device short name | IC60N |
| Product type | Miniature circuit-breaker |
| Poles / protected poles | 2P / 2 |
| Rated current [In] | 0.5 A |
| Network type | AC/DC |
| Network frequency | 50/60 Hz |
| Trip unit | Thermal-magnetic |
| Curve code | C |
| Magnetic tripping limit | 8 x In ± 20 % |
| Breaking capacity (230 V AC) | 50 kA Icu, EN/IEC 60947-2 |
| Breaking capacity (380–415 V AC) | 50 kA Icu, EN/IEC 60947-2 |
| Rated insulation voltage [Ui] | 500 V AC |
| Rated impulse withstand [Uimp] | 6 kV |
| Limitation class | 3 (EN/IEC 60898-1) |
| Dimensions (height, width, depth) | 85 × 36 × 78.5 mm |
| 9 mm pitches | 4 |
| Net weight | 0.25 kg |
| Mounting | Clip-on, DIN rail |
| Terminals | Single terminal, top or bottom: 25 mm² rigid, 16 mm² flexible |
| Operating temperature | -35–70 °C |
| Protection degree | IP20 (IEC 60529) |
| Mechanical / electrical durability | 20000 / 10000 cycles |
| Warranty | 18 months |
Where the A9F44270 fits in Oman and the GCC
Breakers of this class are used in single-phase panels in offices, villas, site cabins and utility rooms. This unit is typically selected for very small loads such as signalling, control-transformer primaries and instrument supplies, where a standard 6 A device would not protect the cable or load closely. Gulf installations raise their own concerns: high board temperatures in direct sun, dust ingress through cable entries, and humidity in coastal areas. The datasheet allows operation to 70 °C and 95 % humidity at 55 °C, but a board that runs hot also reduces the margin before the thermal element trips, so ventilation and derating deserve attention.
Selection checklist for the A9F44270
- Circuit: 0.5 A suits very small loads such as signalling, control-transformer primaries and instrument supplies, where a standard 6 A device would not protect the cable or load closely; confirm the cable rating and the load starting current.
- Poles: 2P for single-phase or two-wire DC; make sure the system earthing matches.
- Fault level: available short-circuit current at the board must stay below 50 kA at 400 V class; the datasheet lists a higher 50 kA tier for this reference.
- Trip: C curve, magnetic trip around 4 A (± 20 %); compare with the expected fault current at the far end of the cable.
- Status: discontinued per datasheet, check stock or a replacement.
How the A9F44270 compares with its siblings
Other iC60N C-curve references with the same characteristics but different current or pole count are shown below, taken from their own datasheets. The width follows the number of poles at 9 mm per module pitch, the 2P family being 36 mm wide.
| Reference | Poles | Rated current | Width | Icu at 400 V class | Lifecycle note |
|---|---|---|---|---|---|
| A9F44206 | 2P | 6 A | 36 mm | 10 kA | No notice on datasheet |
| A9F44210 | 2P | 10 A | 36 mm | 10 kA | No notice on datasheet |
| A9F44216 | 2P | 16 A | 36 mm | 10 kA | No notice on datasheet |
| A9F44220 | 2P | 20 A | 36 mm | 10 kA | No notice on datasheet |
| A9F44370 | 3P | 0.5 A | 54 mm | 50 kA | Discontinued 13 Sep 2024 |
Trip characteristics of the A9F44270
A thermal-magnetic breaker uses two mechanisms. The thermal element follows sustained overload and responds slowly, so a motor start or a short inrush does not cause a nuisance trip. The magnetic element reacts to short-circuit current almost instantly. On this unit the datasheet gives the magnetic tripping limit as 8 × In ± 20 %, which for a 0.5 A rating works out to roughly 3.2 A to 4.8 A, centred on 4 A. Within that band the instantaneous element is expected to operate; below it, only the thermal element acts.
Curve code C is the general-purpose choice for loads with moderate inrush, such as lighting transformers and mixed socket circuits. The limitation class is 3 under EN/IEC 60898-1, which means the breaker limits the let-through energy of a fault well below the prospective level.
Connections, mounting and dimensions of the A9F44270
The A9F44270 clips onto a DIN rail and occupies 4 modules of 9 mm, a width of 36 mm, with a height of 85 mm and a depth of 78.5 mm. Net weight is 0.25 kg. The control is a toggle, a contact position indicator and a trip indicator show the state, and the lever can be padlocked in the open position, which helps with lock-out procedures.
Each pole has a single terminal at the top and at the bottom accepting up to 25 mm² rigid or 16 mm² flexible conductor. The datasheet specifies a wire stripping length of 14 mm and a tightening torque of 2 N.m, so use a calibrated screwdriver and a conductor cross-section suited to the 0.5 A rating and to the cable-installation method. The datasheet lists compatible Vigi iC60 and Quick Vigi iC60 add-on residual current devices for specific current ranges, and earth-leakage protection is a separate block, not built into this breaker.
The operating range is −35 to 70 °C, the storage range is −40 to 85 °C, and humidity is rated at 95 % at 55 °C. Tropicalisation class 2 applies, the protection degree is IP20, pollution degree 3 and overvoltage category IV.
Information to send with an RFQ for the A9F44270
- Exact reference A9F44270 and quantity.
- System voltage, number of phases and whether the circuit is AC or DC.
- Available fault level at the board and the cable size to be protected.
- Any matching add-on residual current block, auxiliary or accessory needed in the same order.
- Delivery location in Oman or the GCC and project timeline; because of the lifecycle notice, also whether a replacement reference is acceptable.
Documents and quotation
The manufacturer datasheet for the A9F44270 is attached on this page. It holds the specification summarised here; check the date and lifecycle notice against your project.
Send us the reference A9F44270, quantity and delivery location and Seven Star LLC will reply to your request. We supply as an independent supplier based in Muscat.
Other Models in the Se Acti9 Ic60n C Range
Seven Star LLC supplies models from the Se Acti9 Ic60n C range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric A9F44206 Acti9 iC60N 2P 6A C MCB | Circuit Breakers | View details |
| Schneider Electric A9F44210 Acti9 iC60N 2P 10A C MCB | Circuit Breakers | View details |
| Schneider Electric A9F44216 Acti9 iC60N 2P 16A C MCB | Circuit Breakers | View details |
| Schneider Electric A9F44220 Acti9 iC60N 2P 20A C MCB | Circuit Breakers | View details |
| Schneider Electric A9F44225 Acti9 iC60N 2P 25A C MCB | Circuit Breakers | View details |
| Schneider Electric A9F44232 Acti9 iC60N 2P 32A C MCB | Circuit Breakers | View details |
| Schneider Electric A9F44240 Acti9 iC60N 2P 40A C MCB | Circuit Breakers | View details |
| Schneider Electric A9F44250 Acti9 iC60N 2P 50A C MCB | Circuit Breakers | View details |
| Schneider Electric A9F44263 Acti9 iC60N 2P 63A C MCB | Circuit Breakers | View details |
| Schneider Electric A9F44270 Acti9 iC60N 2P 0.5A C MCB | Circuit Breakers | You are viewing this model |
| Schneider Electric A9F44301 Acti9 iC60N 3P 1A C MCB | Circuit Breakers | View details |
| Schneider Electric A9F44303 Acti9 iC60N 3P 3A C MCB | Circuit Breakers | View details |
Datasheets & Documents
- Datasheet Schneider Electric A9F44270 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric A9F44270 Acti9 iC60N 2P 0.5A C
Answers from our engineering team on installation, compatibility and integration.
01What is the rating of the A9F44270?
The datasheet lists a 2P Acti9 iC60N miniature circuit breaker with 0.5 A rated current, C curve and a thermal-magnetic trip unit for 50/60 Hz AC/DC networks.
02What is the breaking capacity of the A9F44270?
50 kA Icu at 220–240 V AC and 50 kA Icu at 380–415 V AC under EN/IEC 60947-2, and 10 kA at ≤ 125 V DC DC.
03At what current does the A9F44270 trip magnetically?
The magnetic tripping limit is 8 × In ± 20 %, which for 0.5 A is about 3.2 to 4.8 A. Overloads below this are handled by the thermal element.
04What terminals and mounting does the A9F44270 use?
Single terminals top and bottom accept 25 mm² rigid or 16 mm² flexible conductors; the breaker is 36 mm wide, occupies 4 modules and clips onto a DIN rail.
05Is the A9F44270 still available?
The datasheet marks it as discontinued on 13 Sep 2024, so check stock and ask about a replacement.