PULS UB10.241 24V 10A DC-UPS Control Unit

Description

A DC-UPS that bridges power failures with a single 12 V battery

The PULS UB10.241 is a DC uninterruptible power supply control unit that is added behind a standard 24 V power supply to bridge mains failures or voltage fluctuations. PULS points out that expensive downtime, long restart cycles and data loss can be avoided this way. Its distinctive feature is that only one 12 V battery is needed to buffer a 24 V output, which removes the matching of battery strings and allows precise charging and testing. The unit includes a battery management system that charges and monitors the battery for long service life, plus diagnostic signals including a replace-battery warning.

The UB10.241 is the controller only. The datasheet lists matching battery modules (UZK12.072, 7 Ah, and UZK12.261, 26 Ah), and a related model, the UBC10.241, includes the same controller with an integrated 5 Ah battery.

Technical specification

Parameter Specification
Order number UB10.241 (DC-UPS control unit)
Input voltage 24 Vdc nominal, range 22.5 to 30 Vdc
Output current min. 15 A in normal mode; min. 10 A in buffer mode
Output voltage typ. 0.23 V below the input in normal mode; 22.25 V in buffer mode at 10 A
Ripple and noise max. 20 mVpp, 20 Hz to 20 MHz; short-circuit current min. 17.9 A
Battery One maintenance-free 12 V VRLA lead-acid battery; allowed capacities 3.9 Ah to 40 Ah; battery voltage range 9.0 to 15.0 V
Charging CC-CV; constant charging current 1.5 A independent of battery size; typ. 5 h for a 7 Ah battery
Battery discharge current typ. 21 A in buffer mode at 10 A output current and 11.5 V at the battery terminal
Deep-discharge protection typ. 10.5 V at 0 A output current; limit is battery-current dependent
Buffer time typ. 6 min 45 s at 10 A with 7 Ah module; typ. 55 min with 26 Ah module; min. 19 min 12 s and 99 min 30 s at 5 A with UZK12.072 and UZK12.261
Buffer-time limiter Selectable setting on the front
Efficiency typ. 97.8 % in normal mode, 10 A output, battery fully charged
Signals Status and diagnosis LEDs; signal contacts for buffering and battery status; inhibit signal input (max. 35 Vdc, 6 mA); contact rating max. 50 mA, 35 V
Protection Overvoltage protection typ. 32 Vdc; reverse battery polarity (max. -35 Vdc); battery deep-discharge; electronic overload and short-circuit protection; IP20
Terminals Spring-clamp 0.5-6 mm2 solid, 0.5-4 mm2 stranded (10 mm stripping); signals: pluggable screw terminal 0.2-1.5 mm2 (6 mm stripping)
Environment -25 C to +70 C operating; derating 0.43 A/C above +60 C in normal mode; 5 to 95 % r.H.; altitude 0 to 6000 m (approvals only up to 2000 m)
Dimensions / weight 49 x 124 x 117 mm (W x H x D); 530 g
Lifetime / MTBF Lifetime min. 137 400 h and MTBF (SN 29500) 886 000 h at 10 A output and 40 C
Approvals on cover page UL 508, UL 60950-1, Class I Div 2, Marine; IEC 60950-1 CB certificate listed in chapter 19

How the battery management works

In normal mode the controller passes the supply voltage to the load (about 0.23 V lower) while charging the battery at a constant 1.5 A until the CV stage takes over. A periodic battery test and the replace-battery signal warn before a weak battery fails during an outage. When the input voltage drops below the transfer threshold the unit switches to buffer mode and supplies a stable 24 V output from the 12 V battery through its converter. A deep-discharge protection switches the output off before the battery is damaged, and the selectable buffer-time limiter can end buffering early.

Installation and selection notes

  • Place the UB10.241 between the 24 V supply and the load; the battery connects to its own terminals, with reverse-polarity protection.
  • Choose battery capacity from the buffer-time curves in the datasheet. The 7 Ah module can be mounted on the DIN rail; the 26 Ah module is panel mounted.
  • Observe the battery maker limits; the datasheet allows 3.9 Ah to 40 Ah VRLA batteries and gives a charging time of about 5 hours for 7 Ah.
  • Heat shortens battery life, so mount the battery in a cooler position than the controller where possible.
  • Accessories in the order list: UZK12.072, UZO12.072, UZK12.261, UZO12.26, ZM1.WALL and ZM10.WALL.

GCC applications

DC-UPS units protect PLCs, SCADA gateways, telemetry and valve-controller circuits in remote pumping stations, wellhead and utility sites where a mains dip must not reset the process. Lead-acid battery life drops quickly in high ambient temperatures, so in desert kiosks plan battery replacement according to the replace-battery signal. When only short bridging of milliseconds to seconds is needed, the UF20.241 capacitor buffer module on this site is a maintenance-free alternative. See the UPS and batteries category.

Selection and installation notes

A DC-UPS control unit works with a regulated 24 V supply and a battery module, so check that the supply has enough power to carry the load and charge the battery at the same time. Use the battery type and size the maker names, mount the battery where the temperature stays moderate, set the buffer time from the load and the battery capacity, test the changeover by switching the mains off and replace the battery at the intervals the manual states.

Information needed for a quotation

Send the full model code, the quantity, the delivery location in Oman or the GCC, the intended use and any accessories needed, so that the complete package can be quoted together.

Documents and supply information

The manufacturer data sheet is attached to this page and should be read together with the project specification and the site risk assessment before a purchase is confirmed. Ratings, standards and dimensions are quoted as printed on that sheet. Lead time, stock position and certificates available with the shipment are confirmed in the quotation, and we supply to Oman and the wider GCC region for industrial, utility and building services projects.

Datasheets & Documents
  • PDF Datasheet PULS UB10.241 datasheet (Nov. 2023, Rev. 1.6) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

PULS is a German manufacturer of DIN-rail power supplies for industrial automation, founded in Munich in 1980 by power supply engineer Bernhard Erdl, who leads it as CEO and chief developer. The company has focused only on industrial applications and helped make DIN-rail mounting, power reserves and wide operating temperature ranges standard features. PULS produces in the Czech Republic, China and Germany.

Seven Star LLC is an independent supplier in Muscat. We list PULS power supplies and supplementary modules for PLC cabinets, pumping stations, compressor packages and utility panels in Oman and the GCC.

PULS company profile

Founded 1980, Munich, by Bernhard Erdl
Headquarters Munich, Germany
Production Chomutov (Czech Republic), Suzhou (China), Drebach (Germany)
Focus Industrial power supplies only
Product families DIMENSION CP, QS, QT and XT DIN-rail power supplies, CS series, PIANO and MiniLine supplies, redundancy modules, buffer and DC-UPS modules

Milestones

  • 1980: Bernhard Erdl founds PULS in Munich.
  • 1997: PULS commits to the DIN-rail concept.

PULS product series

DIMENSION power supplies on this site include the CP10.241 (24 V, 10 A), the CS10.241 with auto-select input, the QS20.241 (24 V, 20 A) and the three-phase CT5.241, QT40.241 and semi-regulated XT40.241 for 40 A. Higher-featured models offer PowerBoost or BonusPower reserves and a DC-OK signal.

Supplementary units include the MLY10.241 dual diode redundancy module, the YR40.242 MOSFET redundancy module for 40 A, the UF20.241 capacitor buffer module that bridges supply interruptions of about 200 ms, and the UB10.241 DC-UPS control unit used with batteries.

Where PULS power supplies are used

24 V supply for PLCs, I/O, sensors and actuators in machine and process control panels, redundant supplies for critical systems, and buffered supplies for controllers that must ride through short mains dips.

PULS products we list

Family Examples
Power Modules CP10.241 24V 10A 240W Single-Phase DIN R…, CS10.241 24V 10A 240W Auto-Select DIN Ra…, MLY10.241 12-48V 10A Dual Diode Redundan…, QS20.241 24V 20A 480W Single-Phase DIN R…, QT40.241 24V 40A 960W Three-Phase DIN Ra…, XT40.241 24V 40A 960W Semi-Regulated 3-P…

Ordering PULS products: what we need

Send the full order code, such as QS20.241, together with the input voltage and phases, output current, ambient temperature and any approvals required, such as UL, marine, ATEX, IECEx or Class I Div 2, which apply only to selected models.

Facts checked against PULS company profiles and an interview with Bernhard Erdl, October 2026.

FAQ

Questions about the PULS UB10.241 24V 10A DC-UPS Control Unit

Answers from our engineering team on installation, compatibility and integration.

01How many batteries does the UB10.241 need?
Only one 12 V VRLA lead-acid battery, 3.9 Ah to 40 Ah, even though the output is 24 V.
02How long can it buffer a 10 A load?
Typically 6 min 45 s with the 7 Ah battery module and about 55 min with the 26 Ah module, per the datasheet.
03Is the battery included?
No. The UB10.241 is the control unit; battery modules UZK12.072 and UZK12.261 are listed as accessories.
04Does it include a replace-battery warning?
Yes, the datasheet lists a replace-battery signal and diagnosis LEDs as part of the battery management.
05Who supplies PULS DC-UPS units in Oman?
Seven Star LLC is an independent supplier in Muscat, not the manufacturer; send us your load and buffer time requirement.