The Phoenix Contact PLC-RSC-24DC/21-21AU (order no. 2967125) is a PLC-INTERFACE module with two changeover contacts coated with hard gold, driven by a 24 V DC coil. AU in the code refers to gold. The module is 14 mm wide, 80 mm high and 94 mm deep. The coil range is 20.2 to 33.6 V DC at 20 degrees C.

Seven Star LLC supplies the PLC-RSC-24DC/21-21AU as an independent supplier in Muscat for projects in Oman and the GCC, quoted against the exact part number shown here.

Technical specifications of the PLC-RSC-24DC/21-21AU

Parameter Specification
Manufacturer / part number Phoenix Contact PLC-RSC-24DC/21-21AU (order no. 2967125)
Nominal input (coil) voltage 24 V DC
Input voltage range 20.2 V DC – 33.6 V DC (20 °C)
Typical response time 8 ms
Typical release time 10 ms
Typical input current 18 mA
Contact configuration 2 changeover contacts
Contact material AgNi, hard gold-plated
Maximum switching voltage 30 V AC; 36 V DC
Limiting continuous current 50 mA
Maximum inrush current 50 mA
Minimum switching current 1 mA (24 V)
Interrupting rating, ohmic load 1.2 W (at 24 V DC)
Switching capacity 2 A (at 24 V, DC13); 0.2 A (at 110 V, DC13); 0.2 A (at 250 V, DC13); 2 A (at 24 V, AC15); 2 A (at 120 V, AC15); 2 A (at 250 V, AC15)
Mechanical service life 3x 107 cycles
Test voltage winding/contact 4 kV AC (50 Hz, 1 min., winding/contact)
Ambient temperature (operation) -40 °C – 60 °C
Degree of protection RT III (Relay)
Connection method Screw connection
Tightening torque 0.6 Nm – 0.8 Nm
Dimensions (W x H x D) 14 x 80 x 94 mm

How the PLC-RSC-24DC/21-21AU works

The PLC-RSC-24DC/21-21AU is a PLC-INTERFACE module: a narrow basic terminal block with screw terminals on which a miniature plug-in relay is fitted. The block carries the coil input with its protective circuit and a yellow LED that shows when the coil is energised, and routes the contact(s) to separate screw terminals. Because the relay is plugged in, it can be replaced without rewiring. The coil side and the contact side are electrically isolated, with the test voltage in the table, which lets a low-voltage controller output switch a load on a different voltage level.

Gold contacts are meant for low signal levels. The datasheet lists a limiting continuous current of only 50 mA and a maximum switching voltage of 30 V AC or 36 V DC, so this module is intended for signal-level circuits, not power loads. The material is AgNi with hard-gold plating.

Where the PLC-RSC-24DC/21-21AU fits in a system

Modules like this are placed between a PLC output card (or a field sensor) and a load that the controller cannot drive directly: solenoids, contactors, signal lamps, small motors. They also give isolation and a replaceable wear element, so a failed contact does not mean rewiring a whole output card. In the PLC-RSC range, the choice of coil voltage, number of changeover contacts and contact material is what separates the variants.

Use the PLC-RSC-24DC/21-21AU to switch analogue-like or low-current signals, such as inputs to a PLC card, feedback circuits or measurement lines. Do not use it for coils or lamps, for which the standard 2967060 is correct.

Selection and ordering checklist

  • Confirm the coil voltage of the PLC-RSC-24DC/21-21AU against the controller output: DC or AC, and the tolerance range in the table.
  • Check that the PLC output can supply the typical input current.
  • Confirm the load voltage and current are within the switching data, including inrush.
  • Check the contact material (standard or gold-plated) against the load level, because small signals need gold.
  • Check the number of changeover contacts needed.
  • Consider the divider plate and bridging accessories for neighbouring modules at higher voltages.
  • Check that your load is a signal-level circuit under 50 mA and 30 V.

Installation, commissioning and maintenance of the PLC-RSC-24DC/21-21AU

Clip the PLC-RSC-24DC/21-21AU on a 35 mm DIN rail, wire the coil and contact terminals with screwdriver torque of 0.6 to 0.8 Nm and insert the relay. Check polarity on DC coils. At commissioning, switch each channel and confirm with the LED that the coil is energised, then measure the contact state.

Because the gold layer is thin, never switch inductive or lamp loads through these contacts, even once, since that can damage the plating and ruin the low-level capability. Keep the load within 50 mA and 30 V AC or 36 V DC.

Typical applications in Oman and the GCC

In Oman and the GCC, relay interface modules are used in pump, valve and compressor control panels, in lighting control and in building management systems. The temperature range in the table covers most indoor cabinets, but outdoor panels with strong solar load should be checked against the upper limit.

Signal switching in instrument cabinets and I/O marshalling panels across the Gulf benefit from gold contacts, which resist the oxidation that raises contact resistance at small currents.

Comparison with related PLC-INTERFACE relay modules

Device Distinguishing data
PLC-RSC-24DC/21 (2966171) 1 changeover contact, 24 V DC, on our site
PLC-RSC-24DC/21-21 (2967060) 2 changeover contacts, 24 V DC, on our site
PLC-RSC-24UC/21 (2966184) 1 changeover contact, 24 V AC/DC coil
PLC-RSC-12DC/21 (2966906) 1 changeover contact, 12 V DC coil
PLC-RSC-230UC/21-21 (2967099) 2 changeover contacts, 230 V AC/220 V DC coil
PLC-RSC-24DC/21-21AU (2967125) 2 changeover contacts, 24 V DC, gold contact for small signals
PLC-RSC-230UC/21 (2966207) 1 changeover contact, 230 V coil, on our site

Information to send with an RFQ

  • Full part number PLC-RSC-24DC/21-21AU and quantity.
  • Coil voltage and type (DC or AC).
  • Load voltage, current and type (resistive, inductive or lamp).
  • Number of changeover contacts needed.
  • Cabinet ambient temperature.
  • Delivery location and date.

Documents and quotation

Send us the part number PLC-RSC-24DC/21-21AU and the quantity you need, and we will confirm which official documents are available for this device. Seven Star LLC is an independent supplier in Muscat and quotes for projects across Oman and the GCC; we do not act on behalf of the manufacturer.

Please also tell us the delivery location and required timeline so that availability can be checked before you commit to a project schedule.

Other Models in the Phoenix Plc Rsc Range

Seven Star LLC supplies models from the Phoenix Plc Rsc range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Phoenix Contact PLC-RSC-24UC/21 Relay Module 24 V AC/DCPLC & I/O CardsView details
Phoenix Contact PLC-RSC-12DC/21 Relay Module 12 V DCPLC & I/O CardsView details
Phoenix Contact PLC-RSC-230UC/21-21 Relay Module 230 VPLC & I/O CardsView details
Phoenix Contact PLC-RSC-24DC/21-21AU Relay Module GoldPLC & I/O CardsYou are viewing this model
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Phoenix Contact is a German, family-owned manufacturer of electrical connection technology and industrial automation, founded in 1923 in Essen by Hugo Knümann. It began as a sales company, and in 1928 Knümann developed the modular terminal block mounted on a rail, the product the company is still best known for. Phoenix Contact is headquartered in Blomberg, North Rhine-Westphalia.

Seven Star LLC lists Phoenix Contact surge protection, power supplies and safety relays, and sources these components by order number for panel builders and maintenance teams in Oman.

Phoenix Contact company profile

Founded 1923, Essen, Germany, by Hugo Knümann, as Phönix Elektro- und Industrie-Bedarfsgesellschaft
Headquarters Blomberg, Germany
Ownership Family-owned (Eisert and Stührenberg families)
Key invention The modular terminal block on a DIN rail, 1928
Product families CLIPLINE terminal blocks, PCB terminals and connectors, QUINT and TRIO power supplies, relay modules, surge protection, signal conditioners, Ethernet switches and PLCnext controllers

Milestones

  • 1923: Hugo Knümann founds the company in Essen.
  • 1928: The first modular terminal block is developed.
  • Later: Headquarters move to Blomberg, Ostwestfalen-Lippe.

Phoenix Contact parts listed on this page

The TTC-6-2X1-24DC-UT (order number 2906799) is a surge protection device with screw connection for two 24 V DC signal wires that share a common reference potential. The QUINT-PS/1AC/24DC/10 is a single-phase DIN rail power supply delivering 24 V DC at 10 A. The PSR-SCP-24DC/ESP4/2X1/1X2 (order number 2981020) is a single-channel PSR safety relay for emergency stop and safety door monitoring, with two enabling current paths and plug-in screw terminals.

Phoenix Contact products we list

Family Examples
Isolator & Barrier 2906799 TTC-6-2X1-24DC-UT Surge Protector, MACX MCR-EX-SL-RPSSI-I Signal Isolator, MINI MCR-2-UI-UI 3-Way Signal Conditione…, PLT-SEC-T3-230-FM Type 3 Surge Protectio…
Power Modules QUINT-PS/1AC/24DC/10 QUINT Power Supply, QUINT4-PS/1AC/24DC/10 Power Supply, TRIO-PS-2G/1AC/24DC/10 Power Supply, UNO-PS/1AC/24DC/100W Power Supply
Automation Accessories PLC-RSC-24DC/21 Relay Module, PSR-SCP-24DC/ESP4/2X1/1X2 Safety Relay (…

Ordering Phoenix Contact components: what we need

Phoenix Contact items are ordered by a seven-digit order number together with the type designation, both printed on the side of the module. Send both, plus the quantity. If the number is unreadable, send the type text and a photo. For power supplies, state input voltage, output current and whether the unit runs in parallel or with a redundancy module. For buyers in the GCC replacing an older unit, we check the manufacturer's documentation for the listed successor type.

Facts checked against Phoenix Contact's own company history (phoenixcontact.com), October 2026.

FAQ

Questions about the Phoenix Contact PLC-RSC-24DC/21-21AU Relay Module

Answers from our engineering team on installation, compatibility and integration.

01What does AU mean?
AU indicates gold-plated contacts for small signals.
02What is the maximum current?
The limiting continuous current is 50 mA.
03What is the maximum switching voltage?
30 V AC or 36 V DC.
04How many contacts?
Two changeover contacts.
05What coil voltage?
24 V DC, 20.2 to 33.6 V DC at 20 degrees C.