Phoenix Contact AXL F DO16/1 1H 16-Channel Digital Output Module

Description

AXL F DO16/1 1H: 16-channel 24 V digital output module, 500 mA

The AXL F DO16/1 1H provides 16 digital outputs at 24 V DC, each rated 500 mA, in a module 35 mm wide. It belongs to the Axioline F family and is supplied with its bus base module and connector. It switches solenoid valves, relays, indicator lamps and small contactor coils from the PLC through the station coupler. Seven Star LLC supplies the AXL F DO16/1 1H in Oman and the GCC as an independent supplier in Muscat.

The part name is built from AXL F for the family, DO for digital output, 16 channels, /1 for single-wire connection and 1H for the housing configuration. The order number is 2688349.

Technical specifications of the AXL F DO16/1 1H

Parameter Specification
Manufacturer / part number Phoenix Contact AXL F DO16/1 1H (order no. 2688349)
Function Digital output module, 16 channels
Nominal output voltage 24 V DC
Output current 500 mA per channel
Maximum output current per module 8 A; external protection must be provided
Output when switched off Max. 1 V; leakage max. 300 µA
Switching frequency Max. 10,000 per second with at least 50 mA load
Behaviour at overload Shutdown with automatic restart
Inductive overload Output can be destroyed; use freewheeling protection where needed
Induced voltage limit -25.8 to -15 V on circuit interruption
Protective circuit Short-circuit and overload protection, electronic; surge protection (35 V, 0.5 s)
Current consumption At least 14 mA without actuators
Ambient temperature -25 to 60 °C
Dimensions 35 x 126.1 x 54 mm

How the AXL F DO16/1 1H drives loads

Each channel is a semiconductor switch that connects the load to the 24 V rail. The switch limits current if the load shorts and turns off with automatic restart when overloaded, so a short on one channel does not trip the whole station. The datasheet cautions that inductive loads beyond the limits can destroy the output, so a freewheeling diode or a suitable relay should be used for large coils.

Off-state values are small: maximum 1 V and 300 µA, so connected indicator lamps or high-impedance inputs do not glow or chatter. The high switching rate of up to 10,000 per second needs at least 50 mA of load.

Where the AXL F DO16/1 1H fits in the station

The output module sits behind the coupler, such as the AXL F BK PN TPS, and is usually paired with the 16-channel input module AXL F DI16/1 1H. Total current of all channels cannot exceed 8 A per module, so a module fully loaded at 500 mA on every channel would exceed this; check the sum of actual loads.

Load voltage comes from the power module in the row, which is protected externally. Keep the load circuit separate from the logic supply of the coupler to prevent disturbances.

Selection and ordering checklist for the AXL F DO16/1 1H

  • Load type: resistive, lamp, solenoid, relay coil; use protection for inductive loads.
  • Current per channel (500 mA max.) and total (8 A max.).
  • Short-circuit and overload behaviour acceptable to the process.
  • Leakage when off against the load sensitivity.
  • Wiring method: single wire per channel.
  • Fail-safe state needed on bus failure, to be set in the engineering tool.

Installation, commissioning and maintenance of the AXL F DO16/1 1H

Mount the module on its base, connect load wires to the terminals and place a fuse or breaker for the load supply, as the data sheet says external protection must be provided. Commission outputs one at a time, with actuators in a safe state.

Use the diagnostics of the station to detect overload on a channel. In maintenance, check terminals and any plug-in relays for wear, and keep spare modules for critical outputs.

Typical applications in Oman and the GCC

In Oman and the GCC the DO16 module drives solenoid valves on skids, pilot lamps in control panels, relay interfaces to motor starters and horn or beacon circuits. The module is a compact way to expand a PLC with 16 outputs close to the actuators.

In hot enclosures, check the power loss of the whole station and keep it under the temperature limit of 60 °C.

Typical wiring practice is to group outputs by function, for example all valves of one skid on one module, so that a module replacement affects a single process section. Use the engineering tool to define the substitute value for each output on bus failure: valves usually go to their safe position, while lamps may hold their last state. Document these choices in the I/O list so that commissioning and maintenance staff know what each channel does when communication is lost.

Comparison with related devices

Device Distinguishing data
AXL F DO16/1 1H (this part) 16 outputs, 24 V, 500 mA, 8 A per module
AXL F DI16/1 1H 16 inputs, 24 V
AXL F BK PN TPS PROFINET coupler
IB IL 24 DO 4 family Inline 4-channel output terminals

Information to send with an RFQ for the AXL F DO16/1 1H

  • Part number AXL F DO16/1 1H and quantity.
  • Load types and currents.
  • Coupler model.
  • Cabinet temperature.

Site conditions in Oman for the AXL F DO16/1 1H

Control cabinets in Gulf plants often run hot, because many sit in outdoor kiosks or in rooms where air conditioning is not always reliable. Before you finalise the AXL F DO16/1 1H, check the permitted ambient range and any derating stated by the manufacturer against the real temperature inside your panel, and leave the recommended spacing around the device so that heat can escape. Long cable runs between the field and the marshalling cabinet are common on large sites, so confirm the signal types, wiring limits and earthing arrangement early in the design.

It also helps to standardise on a small number of part numbers across a project. Keeping a few spare AXL F DO16/1 1H units on site in Oman shortens recovery time after a fault, and documenting configuration settings makes replacement faster for the maintenance team.

Documents and quotation

Send us the part number AXL F DO16/1 1H and the quantity you need, and we will confirm which official documents are available for this item. Seven Star LLC is an independent supplier in Muscat and quotes for projects across Oman and the GCC; we do not act on behalf of the manufacturer.

Please also tell us the delivery location and the project timeline so that availability can be checked before you commit to a schedule.

Other Models in the Phoenix Axioline F Range

Seven Star LLC supplies models from the Phoenix Axioline F range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Phoenix Contact AXL F BK PN TPS Axioline F PROFINET CouplerPLC & I/O CardsView details
Phoenix Contact AXL F DI16/1 1H 16-Channel Digital Input ModulePLC & I/O CardsView details
Phoenix Contact AXL F DO16/1 1H 16-Channel Digital Output ModulePLC & I/O CardsYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Phoenix Contact AXL F DO16/1 1H Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Phoenix Contact is a German, family-owned manufacturer of electrical connection technology and industrial automation, founded in 1923 in Essen by Hugo Knümann. It began as a sales company, and in 1928 Knümann developed the modular terminal block mounted on a rail, the product the company is still best known for. Phoenix Contact is headquartered in Blomberg, North Rhine-Westphalia.

Seven Star LLC lists Phoenix Contact surge protection, power supplies and safety relays, and sources these components by order number for panel builders and maintenance teams in Oman.

Phoenix Contact company profile

Founded 1923, Essen, Germany, by Hugo Knümann, as Phönix Elektro- und Industrie-Bedarfsgesellschaft
Headquarters Blomberg, Germany
Ownership Family-owned (Eisert and Stührenberg families)
Key invention The modular terminal block on a DIN rail, 1928
Product families CLIPLINE terminal blocks, PCB terminals and connectors, QUINT and TRIO power supplies, relay modules, surge protection, signal conditioners, Ethernet switches and PLCnext controllers

Milestones

  • 1923: Hugo Knümann founds the company in Essen.
  • 1928: The first modular terminal block is developed.
  • Later: Headquarters move to Blomberg, Ostwestfalen-Lippe.

Phoenix Contact parts listed on this page

The TTC-6-2X1-24DC-UT (order number 2906799) is a surge protection device with screw connection for two 24 V DC signal wires that share a common reference potential. The QUINT-PS/1AC/24DC/10 is a single-phase DIN rail power supply delivering 24 V DC at 10 A. The PSR-SCP-24DC/ESP4/2X1/1X2 (order number 2981020) is a single-channel PSR safety relay for emergency stop and safety door monitoring, with two enabling current paths and plug-in screw terminals.

Phoenix Contact products we list

Family Examples
Isolator & Barrier 2906799 TTC-6-2X1-24DC-UT Surge Protector, MACX MCR-EX-SL-RPSSI-I Signal Isolator, MINI MCR-2-UI-UI 3-Way Signal Conditione…, PLT-SEC-T3-230-FM Type 3 Surge Protectio…
Power Modules QUINT-PS/1AC/24DC/10 QUINT Power Supply, QUINT4-PS/1AC/24DC/10 Power Supply, TRIO-PS-2G/1AC/24DC/10 Power Supply, UNO-PS/1AC/24DC/100W Power Supply
Automation Accessories PLC-RSC-24DC/21 Relay Module, PSR-SCP-24DC/ESP4/2X1/1X2 Safety Relay (…

Ordering Phoenix Contact components: what we need

Phoenix Contact items are ordered by a seven-digit order number together with the type designation, both printed on the side of the module. Send both, plus the quantity. If the number is unreadable, send the type text and a photo. For power supplies, state input voltage, output current and whether the unit runs in parallel or with a redundancy module. For buyers in the GCC replacing an older unit, we check the manufacturer's documentation for the listed successor type.

Facts checked against Phoenix Contact's own company history (phoenixcontact.com), October 2026.

FAQ

Questions about the Phoenix Contact AXL F DO16/1 1H 16-Channel Digital

Answers from our engineering team on installation, compatibility and integration.

01How many outputs does it have?
16 digital outputs at 24 V DC.
02What current per output?
500 mA per channel, 8 A maximum per module.
03What happens at overload?
The channel shuts down and restarts automatically.
04Are inductive loads allowed?
Large inductive loads can destroy the output, so use protection.
05What is the maximum switching rate?
10,000 per second with at least 50 mA load.