Phoenix Contact AXL F BK PN TPS Axioline F PROFINET Coupler

Description

AXL F BK PN TPS: PROFINET bus coupler for Axioline F stations

The AXL F BK PN TPS is the head module of an Axioline F remote I/O station on PROFINET. It connects the station to the controller through RJ45 Ethernet, exchanges the process data of up to 63 I/O modules over the Axioline local bus at 100 Mbps and supplies the logic of the station. It is supplied with its bus base module and the Axioline F connector. Seven Star LLC supplies the AXL F BK PN TPS in Oman and the GCC as an independent supplier in Muscat.

The name breaks down as AXL F for Axioline F, BK for bus coupler, PN for PROFINET and TPS for the variant covered by order number 2403869. Do not confuse it with the extended-temperature XC version, which has a separate part number.

Technical specifications of the AXL F BK PN TPS

Parameter Specification
Manufacturer / part number Phoenix Contact AXL F BK PN TPS (order no. 2403869)
Function Bus coupler for PROFINET, Axioline F local bus
Network interfaces 2 x RJ45, 100 Mbps per PROFINET standard, Ethernet on twisted pair
Local bus speed 100 Mbps
Modules per station Up to 63 local bus devices
PROFINET devices / subslots Up to 63 devices and 128 subslots; 2 subslots per bus coupler without IO-Link, 1 with IO-Link
Conformance class Conformance Class C
Supply voltage 24 V DC, range 19.2 to 30 V DC including ripple
Current consumption typ. 97 mA without I/O modules at 24 V
Local bus supply 5 V DC through the bus base module
Power dissipation 4.4 W at nominal condition
Degree of protection IP20
Dimensions 45 x 126.1 x 74 mm (W x H x D)

How the AXL F BK PN TPS connects the field to PROFINET

The coupler has two RJ45 sockets, so the Ethernet connection can be passed on to the next device in a line topology without an external switch. Inside, it converts PROFINET telegrams to the Axioline F local bus protocol, collects input data from the modules and writes output data to them in each cycle. The local bus speed of 100 Mbps keeps the update time short even in stations with many channels.

Conformance Class C means the device supports the properties required for fast, deterministic communication, which suits applications with isochronous requirements. Subslots number up to 128 per station, so the station can be divided into logical blocks in the engineering tool.

Where the AXL F BK PN TPS fits in the system

It sits on the left of the Axioline F row, followed by input, output and function modules such as the AXL F DI16/1 1H and AXL F DO16/1 1H, which are covered on separate pages. Each module snaps onto the DIN rail, and the local bus and power are passed through the bus base modules, so no extra wiring links the modules.

The supply of 24 V DC feeds the coupler logic; the I/O modules take their own load voltage from power modules placed in the row. Plan the segment supply carefully because the number of modules you can add depends on the current drawn from the 5 V local bus supply.

Selection and ordering checklist for the AXL F BK PN TPS

  • Network type: PROFINET with RJ45; check the controller and device description file.
  • Number of I/O modules (maximum 63) and total subslots (maximum 128).
  • Supply: 24 V DC within 19.2 to 30 V DC.
  • Temperature class: standard version versus the XC version.
  • Cabinet space: 45 mm wide for the coupler plus module widths.
  • Whether IO-Link modules are used, since they change the subslot count.

Installation, commissioning and maintenance of the AXL F BK PN TPS

Snap the bus base module onto the rail, place the coupler and connect the 24 V supply. Assign the PROFINET device name using the engineering tool, import the device description, and then plug in the I/O modules. Check the segment and local bus diagnostics after power-up.

Because the modules are hot-swappable only according to the manufacturer rules, switch off power before inserting or removing parts unless the data sheet states otherwise. Keep the device description files and the station configuration as part of the maintenance records, so that a replacement coupler can be given the same name and configuration quickly.

Typical applications in Oman and the GCC

In Oman and the GCC, PROFINET remote I/O stations of the AXL F BK PN TPS type are used in water treatment, desalination skids, packaging and material handling and in oil and gas package units where the PLC is in a control room and signals are collected near the machine. A line topology with two ports saves cable and switches.

High cabinet temperature and dust are common; the IP20 module should be mounted in a closed, ventilated enclosure.

Comparison with related devices

Device Distinguishing data
AXL F BK PN TPS (this part) PROFINET coupler, 2 x RJ45, 63 modules
AXL F BK PN TPS XC Extended-temperature version (separate order number)
AXL F DI16/1 1H 16-channel digital input module
AXL F DO16/1 1H 16-channel digital output module

Information to send with an RFQ for the AXL F BK PN TPS

  • Part number AXL F BK PN TPS and quantity.
  • Controller type and PROFINET version.
  • List of I/O modules to be connected.
  • Cabinet temperature.
  • Segment supply concept.

Documents and quotation

Send us the part number AXL F BK PN TPS and the quantity you need, and we will confirm which official documents are available for this item. Seven Star LLC is an independent supplier in Muscat and quotes for projects across Oman and the GCC; we do not act on behalf of the manufacturer.

Please also tell us the delivery location and the project timeline so that availability can be checked before you commit to a schedule.

Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Phoenix Contact is a German, family-owned manufacturer of electrical connection technology and industrial automation, founded in 1923 in Essen by Hugo Knümann. It began as a sales company, and in 1928 Knümann developed the modular terminal block mounted on a rail, the product the company is still best known for. Phoenix Contact is headquartered in Blomberg, North Rhine-Westphalia.

Seven Star LLC lists Phoenix Contact surge protection, power supplies and safety relays, and sources these components by order number for panel builders and maintenance teams in Oman.

Phoenix Contact company profile

Founded 1923, Essen, Germany, by Hugo Knümann, as Phönix Elektro- und Industrie-Bedarfsgesellschaft
Headquarters Blomberg, Germany
Ownership Family-owned (Eisert and Stührenberg families)
Key invention The modular terminal block on a DIN rail, 1928
Product families CLIPLINE terminal blocks, PCB terminals and connectors, QUINT and TRIO power supplies, relay modules, surge protection, signal conditioners, Ethernet switches and PLCnext controllers

Milestones

  • 1923: Hugo Knümann founds the company in Essen.
  • 1928: The first modular terminal block is developed.
  • Later: Headquarters move to Blomberg, Ostwestfalen-Lippe.

Phoenix Contact parts listed on this page

The TTC-6-2X1-24DC-UT (order number 2906799) is a surge protection device with screw connection for two 24 V DC signal wires that share a common reference potential. The QUINT-PS/1AC/24DC/10 is a single-phase DIN rail power supply delivering 24 V DC at 10 A. The PSR-SCP-24DC/ESP4/2X1/1X2 (order number 2981020) is a single-channel PSR safety relay for emergency stop and safety door monitoring, with two enabling current paths and plug-in screw terminals.

Phoenix Contact products we list

Family Examples
Isolator & Barrier 2906799 TTC-6-2X1-24DC-UT Surge Protector, MACX MCR-EX-SL-RPSSI-I Signal Isolator, MINI MCR-2-UI-UI 3-Way Signal Conditione…, PLT-SEC-T3-230-FM Type 3 Surge Protectio…
Power Modules QUINT-PS/1AC/24DC/10 QUINT Power Supply, QUINT4-PS/1AC/24DC/10 Power Supply, TRIO-PS-2G/1AC/24DC/10 Power Supply, UNO-PS/1AC/24DC/100W Power Supply
Automation Accessories PLC-RSC-24DC/21 Relay Module, PSR-SCP-24DC/ESP4/2X1/1X2 Safety Relay (…

Ordering Phoenix Contact components: what we need

Phoenix Contact items are ordered by a seven-digit order number together with the type designation, both printed on the side of the module. Send both, plus the quantity. If the number is unreadable, send the type text and a photo. For power supplies, state input voltage, output current and whether the unit runs in parallel or with a redundancy module. For buyers in the GCC replacing an older unit, we check the manufacturer's documentation for the listed successor type.

Facts checked against Phoenix Contact's own company history (phoenixcontact.com), October 2026.

FAQ

Questions about the Phoenix Contact AXL F BK PN TPS Axioline F PROFINET

Answers from our engineering team on installation, compatibility and integration.

01How many modules can the AXL F BK PN TPS control?
Up to 63 local bus devices per station.
02Which network does it use?
PROFINET over two RJ45 Ethernet ports at 100 Mbps.
03What supply voltage is needed?
24 V DC, range 19.2 to 30 V DC.
04What conformance class is listed?
Conformance Class C.
05What is the local bus speed?
100 Mbps.