- Automation & ControlView all 2,896 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- Safety Switches & Guard Locking
- Motor Soft Starters
- CCTV & Security
- Encoders
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Phoenix Contact
Phoenix Contact AXL F DI16/1 1H 16-Channel Digital Input Module
Description
AXL F DI16/1 1H: 16-channel 24 V digital input module
The AXL F DI16/1 1H is an Axioline F input module with 16 digital inputs for 24 V DC signals. Each channel is a single-conductor connection, which makes it possible to wire 16 sensors in a width of only 35 mm. It comes with its bus base module and the Axioline F connectors, and it runs on the 100 Mbps Axioline local bus behind a bus coupler such as the AXL F BK PN TPS. Seven Star LLC supplies the AXL F DI16/1 1H in Oman and the GCC as an independent supplier in Muscat.
The name reads: AXL F for Axioline F, DI for digital input, 16 for the number of channels, /1 for single-conductor connection and 1H for the housing and connector arrangement used for order number 2688310.
Technical specifications of the AXL F DI16/1 1H
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Phoenix Contact AXL F DI16/1 1H (order no. 2688310) |
| Function | Digital input module, 16 channels |
| Input voltage 0 signal | -3 to 5 V DC |
| Input voltage 1 signal | 11 to 30 V DC |
| Nominal input voltage / current | 24 V DC / 2.4 mA at nominal voltage |
| Protective circuit | Polarity reversal protection; electronic surge protection (35 V, 0.5 s) |
| Connection technology | 1-conductor |
| Local bus speed | 100 Mbps |
| Degree of protection | IP20 |
| Ambient temperature | -25 to 60 °C |
| Dimensions | 35 x 126.1 x 54 mm |
How the AXL F DI16/1 1H reads 24 V signals
Each input is a high-impedance circuit that sees a 0 signal between -3 V and 5 V and a 1 signal between 11 V and 30 V. The nominal input current of 2.4 mA at 24 V is low, so sensors with a small leakage current may still pull the input into the undefined range; check the leakage of two-wire proximity sensors before choosing this module.
The inputs are protected against polarity reversal and short voltage spikes. The status of all 16 channels is sent over the local bus to the coupler, and the coupler passes it to the controller on PROFINET or another supported network, according to the coupler type.
Where the AXL F DI16/1 1H fits in an Axioline station
The module goes to the right of the coupler in the row. It is commonly placed together with the AXL F DO16/1 1H, which provides 16 outputs, so a 35 mm-wide pair gives 32 channels with a clean split of signals. A sensor supply from a separate power module can feed the 24 V field circuit.
Compared with the output module, the input module has no load current and no short-circuit limit; the focus is on the voltage window and input filter. In the station, both module types appear as 16-bit process data words.
Selection and ordering checklist for the AXL F DI16/1 1H
- Signal type: 24 V DC, PNP-style sensors or dry contacts with a supply.
- Sensor leakage current versus the 2.4 mA input level.
- Number of channels (16) and spare channels for the future.
- Connection technology: single-conductor wiring on this variant.
- Coupler compatibility in the Axioline F family.
- Operating temperature up to 60 °C.
Installation, commissioning and maintenance of the AXL F DI16/1 1H
Mount the bus base module on the rail beside the coupler, plug the connector into the base, then insert the module. Wire sensors to the push-in or screw terminals with the correct marking and supply the sensor circuit from a protected 24 V line. Check the channel mapping with the engineering tool.
During commissioning, simulate each input and watch the process image. Keep a labelled drawing of terminal numbers, since a 16-channel module hides little room for marking. In maintenance, replace the module as a unit and keep the bus base module in place.
Typical applications in Oman and the GCC
In Oman and the GCC, 16-channel input modules collect limit switches, push buttons, pump status and valve position feedback at skids, water treatment units and conveyor lines. The temperature range up to 60 °C matches a ventilated cabinet in an air-conditioned plant room but should be checked for non-conditioned kiosks.
The compact 35 mm width is attractive in retrofit cabinets where space is tight.
When planning a station, count the process image: 16 inputs occupy two bytes of input data, and a fully built station with many modules can approach the subslot limits of the coupler. Reserve a few spare channels on each module for later additions, and group inputs by function so that a module replacement affects only one machine section. A defined labelling scheme, with the rack position and terminal number on each sensor cable, shortens fault finding considerably.
Comparison with related devices
| Device | Distinguishing data |
|---|---|
| AXL F DI16/1 1H (this part) | 16 inputs, 24 V DC, 1-conductor |
| AXL F DO16/1 1H | 16 outputs, 24 V DC, 500 mA |
| AXL F BK PN TPS | PROFINET bus coupler for the station |
| IB IL 24 DI 4 family | Inline 4-channel input terminals |
Information to send with an RFQ for the AXL F DI16/1 1H
- Part number AXL F DI16/1 1H and quantity.
- Sensor types and leakage currents.
- Coupler model.
- Cabinet temperature.
Site conditions in Oman for the AXL F DI16/1 1H
Control cabinets in Gulf plants often run hot, because many sit in outdoor kiosks or in rooms where air conditioning is not always reliable. Before you finalise the AXL F DI16/1 1H, check the permitted ambient range and any derating stated by the manufacturer against the real temperature inside your panel, and leave the recommended spacing around the device so that heat can escape. Long cable runs between the field and the marshalling cabinet are common on large sites, so confirm the signal types, wiring limits and earthing arrangement early in the design.
It also helps to standardise on a small number of part numbers across a project. Keeping a few spare AXL F DI16/1 1H units on site in Oman shortens recovery time after a fault, and documenting configuration settings makes replacement faster for the maintenance team.
Documents and quotation
Send us the part number AXL F DI16/1 1H and the quantity you need, and we will confirm which official documents are available for this item. Seven Star LLC is an independent supplier in Muscat and quotes for projects across Oman and the GCC; we do not act on behalf of the manufacturer.
Please also tell us the delivery location and the project timeline so that availability can be checked before you commit to a schedule.
Other Models in the Phoenix Axioline F Range
Seven Star LLC supplies models from the Phoenix Axioline F range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Phoenix Contact AXL F BK PN TPS Axioline F PROFINET Coupler | PLC & I/O Cards | View details |
| Phoenix Contact AXL F DI16/1 1H 16-Channel Digital Input Module | PLC & I/O Cards | You are viewing this model |
| Phoenix Contact AXL F DO16/1 1H 16-Channel Digital Output Module | PLC & I/O Cards | View details |
Datasheets & Documents
- Datasheet Phoenix Contact AXL F DI16/1 1H Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Phoenix Contact is a German, family-owned manufacturer of electrical connection technology and industrial automation, founded in 1923 in Essen by Hugo Knümann. It began as a sales company, and in 1928 Knümann developed the modular terminal block mounted on a rail, the product the company is still best known for. Phoenix Contact is headquartered in Blomberg, North Rhine-Westphalia.
Seven Star LLC lists Phoenix Contact surge protection, power supplies and safety relays, and sources these components by order number for panel builders and maintenance teams in Oman.
Phoenix Contact company profile
| Founded | 1923, Essen, Germany, by Hugo Knümann, as Phönix Elektro- und Industrie-Bedarfsgesellschaft |
|---|---|
| Headquarters | Blomberg, Germany |
| Ownership | Family-owned (Eisert and Stührenberg families) |
| Key invention | The modular terminal block on a DIN rail, 1928 |
| Product families | CLIPLINE terminal blocks, PCB terminals and connectors, QUINT and TRIO power supplies, relay modules, surge protection, signal conditioners, Ethernet switches and PLCnext controllers |
Milestones
- 1923: Hugo Knümann founds the company in Essen.
- 1928: The first modular terminal block is developed.
- Later: Headquarters move to Blomberg, Ostwestfalen-Lippe.
Phoenix Contact parts listed on this page
The TTC-6-2X1-24DC-UT (order number 2906799) is a surge protection device with screw connection for two 24 V DC signal wires that share a common reference potential. The QUINT-PS/1AC/24DC/10 is a single-phase DIN rail power supply delivering 24 V DC at 10 A. The PSR-SCP-24DC/ESP4/2X1/1X2 (order number 2981020) is a single-channel PSR safety relay for emergency stop and safety door monitoring, with two enabling current paths and plug-in screw terminals.
Phoenix Contact products we list
Ordering Phoenix Contact components: what we need
Phoenix Contact items are ordered by a seven-digit order number together with the type designation, both printed on the side of the module. Send both, plus the quantity. If the number is unreadable, send the type text and a photo. For power supplies, state input voltage, output current and whether the unit runs in parallel or with a redundancy module. For buyers in the GCC replacing an older unit, we check the manufacturer's documentation for the listed successor type.
Facts checked against Phoenix Contact's own company history (phoenixcontact.com), October 2026.
Browse Phoenix Contact products by category: Isolator & Barrier, Power Modules, Automation Accessories.
FAQ
Questions about the Phoenix Contact AXL F DI16/1 1H 16-Channel Digital
Answers from our engineering team on installation, compatibility and integration.
01How many inputs does it have?
16 digital inputs.
02What voltage is a 1 signal?
11 to 30 V DC.
03What is the input current?
2.4 mA at nominal 24 V DC.
04What protection is built in?
Polarity reversal protection and electronic surge protection.
05What is the ambient temperature range?
-25 to 60 °C.


















Reviews