Brand:

Legrand 412524 CX3 2-Pole 25 A Contactor 2NC 230 V

Description

412524: Legrand CX3 2-pole 25 A contactor, 2 NC, no handle

The Legrand 412524 is a CX3 modular power contactor with two normally closed poles, 25 A at 250 V AC, a 230 V AC coil and no front handle. It occupies one module (17.8 mm). Because both contacts are closed when the coil is de-energised, the load is on by default and is switched off while the coil is powered. The product page lists AC7a/AC1 at 25 A and AC7b/AC3 at 10 A and conformity with IEC/EN 61095. Seven Star LLC supplies 412524 in Oman and the GCC as an independent supplier in Muscat.

This reference is the compact choice for controlling a single-phase load that should normally stay on, such as emergency-support or security lighting, and that is switched off on command from a timer, a photocell or a building system.

Reading the 412524 reference

Element Value Meaning
2 pole 2NC Contacts Two normally closed contacts; open when the coil is powered
25 A 250 V Rating Single-phase power circuit, AC7a/AC1 25 A
230 V coil Control Excitation range 195 to 253 V AC
No handle Operation Remote control only; no manual override
1 module Width 17.8 mm on the DIN rail
Ref. 412524 Catalogue number Reference to quote

Technical specifications for 412524

Parameter Specification
Manufacturer / part number Legrand / 412524 (CX3 contactor 2P 25 A 2NC 230 V coil)
Contacts 2 NC (0 NO)
Rated operating voltage / current 250 V AC / 25 A; AC7b/AC3 at 10 A
Coil excitation voltage 230 V AC (195–253 V)
Coil consumption at 230 V About 20 mA holding and 90 mA inrush; 1.2 W holding
Lamp loads 3000 W incandescent; 2100 VA fluorescent; 2200 VA duo; 1000 VA parallel compensated
Width / height / depth 17.8 mm / 94.9 mm / 67.3 mm
Protection IP2X terminals
Insulation / impulse (data sheet) Ui 440 V; Uimp 4 kV
Terminals (data sheet) Cage, rigid 0.75–4 mm² (6 mm² accepted), flexible 0.75–6 mm²; torque 0.8 Nm recommended
Annual consumption (data sheet) About 1.0 kWh for 2NC at 230 V in standard use
Accessories Auxiliary contact reference 412429; prong busbar entry on the top side
Mounting 35 mm DIN rail with two clips

How 412524 behaves compared with a 2NO contactor

The spring holds both contacts closed. When 230 V is applied to A1 and A2, the electromagnet overcomes the spring and opens them. This inverts the usual logic, so a loss of control power returns the load to the on state. That is an advantage for loads that must not drop out when the control supply fails, and a point to check carefully in any design where an unwanted start would be dangerous.

Coil dissipation depends on the contact type. The data sheet lists about 1.2 W holding power for 2NC at 230 V against 0.8 W for 2NO, and annual consumption figures of 1.0 kWh for 2NC and 3.1 kWh for 2NO under its standard usage assumptions. Real consumption depends on how many hours per day the coil is energised, so estimate it from your own switching pattern when many devices are used.

Where 412524 fits and related parts

Compare 412524 with the 2NO version with handle, 412544, and the four-pole 412536 (4NC). The family also includes NO+NC mixed and 2NO+2NC four-pole versions according to the data sheet range. Upstream protection should be an MCB or gG fuse up to 25 A, and for an earth-leakage requirement an RCBO such as 411053 or 411097 can feed the contactor. Do not use this contactor as a motor starter: the AC3 rating is only 10 A and there is no overload relay.

Selection checklist for 412524

  • Default state: load on when the coil is off; confirm that this is safe for the application.
  • Rating: 25 A resistive, 10 A motor (AC3), 3000 W incandescent lighting.
  • Coil: 230 V AC; the control circuit does not operate on DC.
  • No handle: a separate isolating device is needed for local override.
  • Duty: low switching frequency; endurance is 100,000 cycles at AC7a.
  • Power: the coil is energised while the load is off, so estimate coil consumption from your switching pattern.

Installation and maintenance of 412524

Fit the contactor to the rail and connect the power terminals 1 to 4 and coil terminals A1 and A2. Tighten the cage terminals to 0.8 Nm. With 230 V coils, the control line can be up to 400 m on 2-module devices and 250 m on 1-module devices according to the data sheet. Mark the load and the reference 412524 on the label. When maintaining the circuit, remember that removing control power closes the contacts and energises the load, so isolate upstream before working. Check periodically for heating and terminal discolouration.

Typical applications in Oman and the GCC

Typical uses include security and perimeter lighting that runs unless a photocell or timer switches it off, ventilation fans that should run unless interrupted, and similar default-on duties in commercial buildings, camps and utility rooms across Oman and the GCC. In hot rooms keep clearance around the coil, which runs warm when it stays energised for long periods.

Information to send with an RFQ for 412524

  • Reference 412524 and the quantity, including spares for panel maintenance.
  • Contact configuration (2NC), rated current and coil voltage.
  • Load type, daily switching pattern and the safety consequence of power loss.
  • Accessories such as auxiliary contact 412429.
  • Delivery location (Muscat, Sohar, Salalah or elsewhere in the GCC) and the date you need the goods.
  • Any documents you need with the quotation, such as a technical data sheet or a compliance statement.

Documents and quotation

The Legrand technical data sheet that covers 412524 is attached on this page. It gives the range table, dimensions, curves and accessories, so check its notes against your design before you order.

To request a quotation, send reference 412524, the quantity and your delivery location. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer; we will confirm availability and lead time for your order.

Other Models in the Legrand Cx3 Contactor Range

Seven Star LLC supplies models from the Legrand Cx3 Contactor range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Legrand 412536 CX3 4-Pole 25 A Contactor 4NC 230 VContactors & Overload RelaysView details
Legrand 412544 CX3 2-Pole 25 A Contactor with HandleContactors & Overload RelaysView details
Legrand 412524 CX3 2-Pole 25 A Contactor 2NC 230 VContactors & Overload RelaysYou are viewing this model
Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Legrand is a French maker of electrical and digital building infrastructure, headquartered in Limoges. Its roots lie in a nineteenth-century porcelain workshop in Limoges, and it grew into one of the largest makers of wiring devices, circuit protection, cable management and data centre products. Legrand is listed on Euronext Paris and sells under brands including Legrand, Bticino and Cablofil.

Seven Star LLC, an independent supplier in Muscat, lists Legrand circuit breakers for electrical contractors and panel builders in Oman and the GCC, at present a DX3 4-pole miniature circuit breaker rated C32.

Legrand company profile

Headquarters Limoges, France
Listing Euronext Paris
Brands Legrand, Bticino, Cablofil, Zucchini
Product families DX3 miniature circuit breakers and RCDs, wiring devices, cable trays, busbar trunking, UPS

Legrand DX3 circuit breakers

DX3 is the Legrand family of modular protection devices for DIN rail mounting. The item on our site is a 4-pole MCB with a C tripping curve and a 32 A rated current. Three things besides the pole count define a breaker of this kind: the curve, the rated current and the breaking capacity printed on the front. Legrand catalogs DX3 breakers in 6000 A and 10000 A versions under separate references.

Ordering Legrand breakers: what we need

Send the Legrand catalog number printed on the device, a six-digit reference, where it is legible. Otherwise give the number of poles, the curve, the rated current, the breaking capacity and the voltage. Mention any auxiliary contact or residual current add-on module fitted beside the breaker, and the board type.

Facts checked against Legrand's published corporate information, October 2026.

FAQ

Questions about the Legrand 412524 CX3 2-Pole 25 A Contactor 2NC 230 V

Answers from our engineering team on installation, compatibility and integration.

01What is 412524?
It is a Legrand CX3 modular contactor with two normally closed contacts, 25 A at 250 V AC, a 230 V AC coil, no handle and a one-module body.
02What happens to the load when control power fails on 412524?
The contacts close when the coil is not powered, so the load switches on. Check that this default state is safe in your application.
03How much coil power does 412524 use?
The data sheet lists about 1.2 W holding power and 20 mA holding current at 230 V for 2NC versions, so continuous energisation adds up over time.
04Can 412524 start a motor?
Only small motors. The AC3 rating is 10 A, and the contactor has no overload protection, so a separate thermal relay or motor protection breaker is needed.
05How does 412524 differ from 412544?
412524 has two normally closed contacts and no handle, while 412544 has two normally open contacts and a three-position handle for forced on, auto and forced off.