Legrand 412536 CX3 4-Pole 25 A Contactor 4NC 230 V

Description

412536: Legrand CX3 4-pole 25 A contactor, 4 NC, 230 V coil

The Legrand 412536 is a CX3 modular power contactor with four normally closed (NC) poles, a continuous rated current of 25 A at 400 V AC and a 230 V AC coil. It is two modules wide (35.6 mm), is supplied without a front-face manual handle and mounts on a DIN rail. The catalogue lists utilisation categories AC7a/AC1 at 25 A and AC7b/AC3 at 10 A under IEC/EN 61095. Seven Star LLC supplies 412536 in Oman and the GCC as an independent supplier in Muscat.

All four contacts of this version are closed at rest and open when the coil is energised. That is the opposite of the usual NO contactor and it matters for the application: the load stays on when control power is absent and switches off when the coil is energised, a common scheme for loads that should be off during the day, for example street or facade lighting controlled by a timer.

Decoding the description of 412536

Element Value Meaning
CX3 Range Legrand modular contactors for building and light industrial boards
4 pole, 25 A Poles and rating Four power poles rated 25 A in AC7a/AC1
4NC Contact type Four normally closed contacts, open when the coil is energised
230 V coil Control Coil excitation voltage range 195 to 253 V AC
Without handle Operation No front-face manual override
Ref. 412536 Catalogue number Reference to quote

Technical specifications for 412536

Parameter Specification
Manufacturer / part number Legrand / 412536 (CX3 contactor 4P 25 A 4NC 230 V coil)
Contacts 4 NC (0 NO)
Rated operating voltage / current 400 V AC / 25 A (AC7a/AC1); AC7b/AC3 at 10 A
Coil excitation voltage 230 V AC (195–253 V); operating range 0.85 to 1.1 x Uc, drop-out 0.2 to 0.75 x Uc
Lamp loads 3000 W incandescent; 2100 VA fluorescent; 2200 VA duo circuit; 1000 VA parallel compensated
Insulation / impulse Ui 440 V; Uimp 4 kV; pollution degree 2
Short-circuit protection Conditional current 6000 A; protect with an MCB or gG fuse up to 25 A
Coil consumption at 230 V About 20 mA holding and 90 mA inrush; 1.2 W holding (2NC data sheet value)
Width / height / depth 35.6 mm / 94.9 mm / 67.3 mm; two modules
Protection IP2X terminals, IP3XD front panel, IK04, class II with faceplate
Terminals Cage terminals, rigid 0.75–4 mm² (6 mm² accepted), flexible 0.75–6 mm²
Accessories Auxiliary contact reference 412430, prong busbar entry on the top side
Mounting 35 mm DIN rail with two plastic clips, any operating position

How the 412536 switches a load

The contactor is an electromagnetic monostable relay. A coil moves an armature against a spring; in this NC version the spring holds the four contacts closed, and applying 230 V to terminals A1 and A2 pulls them open. When the coil is released, they close again. The coil operates between 0.85 and 1.1 times its rated voltage and drops out between 0.2 and 0.75 times, so a sagging supply does not cause chatter within the normal range. A minimum control pulse of 100 ms is listed in the data sheet.

The holding power is low, about 1.2 W for NC versions at 230 V. An NC contactor draws coil current whenever the load is switched off, so a board that keeps loads off for long periods will see a small continuous consumption. The data sheet gives an annual figure of about 2 kWh for a 4NC device under its standard usage assumptions, which is modest but should be known when a design includes many such devices.

Where 412536 fits and related CX3 parts

Use 412536 for three-phase loads such as lighting groups, resistive heaters and small fans that should be on by default, or where a failure of the control circuit must leave the load energised. For the opposite behaviour, normally open versions of the same CX3 family exist. The 1-module contactors in the same data sheet, such as 412524 (2NC) and 412544 (2NO with handle), cover single-phase duty. Remember that this contactor is a switching device without overload protection; supply it through a circuit breaker such as a DX3 four-pole MCB, and add a thermal relay for motors.

Selection checklist for 412536

  • Load type: resistive or lighting; for motors the AC3 rating is only 10 A (4 kW for 4NO versions per the data sheet).
  • Contact logic: NC means load on at rest; check that this suits the control scheme.
  • Coil: 230 V AC only; the control circuit does not work on DC.
  • Lamp loads: 3000 W incandescent, 2100 VA fluorescent; derate for high inrush LED drivers.
  • Protection: MCB or gG fuse up to 25 A upstream.
  • Altitude and frequency: no derating up to 2000 m; 50/60 Hz, not 400 Hz.

Installation, wiring and maintenance of 412536

Clip the contactor on the rail with the two plastic clips and connect the power terminals 1 to 8 and the coil terminals A1 and A2. Cage terminals take 0.75 to 4 mm² rigid conductors (6 mm² accepted) or up to 6 mm² flexible, with a recommended torque of 0.8 Nm. The data sheet allows long control lines, up to 400 m with 230 V coils on 2-module contactors. Leave a gap beside contactors that run continuously, because coil and contact heat add to the board temperature. Label the circuit in the front holder and record 412536 on the circuit schedule. Check for contact noise and discoloured terminals at each annual inspection.

Typical applications in Oman and the GCC

Timer-controlled lighting, advertising and facade circuits, heating elements and auxiliary loads in commercial buildings and camps use this kind of contactor. In hot cabinets, check the ambient temperature around the coil, and in dusty sites keep the enclosure closed. A four-pole contactor also helps where the neutral must be switched with the phases.

Information to send with an RFQ for 412536

  • Reference 412536 and the quantity, including spares for panel maintenance.
  • Contact configuration (4NC here), rated current and coil voltage (230 V AC).
  • Type of load and its inrush or power factor.
  • Accessories such as auxiliary contact 412430.
  • Delivery location (Muscat, Sohar, Salalah or elsewhere in the GCC) and the date you need the goods.
  • Any documents you need with the quotation, such as a technical data sheet or a compliance statement.

Documents and quotation

The Legrand technical data sheet that covers 412536 is attached on this page. It gives the range table, dimensions, curves and accessories, so check its notes against your design before you order.

To request a quotation, send reference 412536, the quantity and your delivery location. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer; we will confirm availability and lead time for your order.

Other Models in the Legrand Cx3 Contactor Range

Seven Star LLC supplies models from the Legrand Cx3 Contactor range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Legrand 412536 CX3 4-Pole 25 A Contactor 4NC 230 VContactors & Overload RelaysYou are viewing this model
Legrand 412544 CX3 2-Pole 25 A Contactor with HandleContactors & Overload RelaysView details
Legrand 412524 CX3 2-Pole 25 A Contactor 2NC 230 VContactors & Overload RelaysView details
Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Legrand is a French maker of electrical and digital building infrastructure, headquartered in Limoges. Its roots lie in a nineteenth-century porcelain workshop in Limoges, and it grew into one of the largest makers of wiring devices, circuit protection, cable management and data centre products. Legrand is listed on Euronext Paris and sells under brands including Legrand, Bticino and Cablofil.

Seven Star LLC, an independent supplier in Muscat, lists Legrand circuit breakers for electrical contractors and panel builders in Oman and the GCC, at present a DX3 4-pole miniature circuit breaker rated C32.

Legrand company profile

Headquarters Limoges, France
Listing Euronext Paris
Brands Legrand, Bticino, Cablofil, Zucchini
Product families DX3 miniature circuit breakers and RCDs, wiring devices, cable trays, busbar trunking, UPS

Legrand DX3 circuit breakers

DX3 is the Legrand family of modular protection devices for DIN rail mounting. The item on our site is a 4-pole MCB with a C tripping curve and a 32 A rated current. Three things besides the pole count define a breaker of this kind: the curve, the rated current and the breaking capacity printed on the front. Legrand catalogs DX3 breakers in 6000 A and 10000 A versions under separate references.

Ordering Legrand breakers: what we need

Send the Legrand catalog number printed on the device, a six-digit reference, where it is legible. Otherwise give the number of poles, the curve, the rated current, the breaking capacity and the voltage. Mention any auxiliary contact or residual current add-on module fitted beside the breaker, and the board type.

Facts checked against Legrand's published corporate information, October 2026.

FAQ

Questions about the Legrand 412536 CX3 4-Pole 25 A Contactor 4NC 230 V

Answers from our engineering team on installation, compatibility and integration.

01What is 412536?
It is a Legrand CX3 modular power contactor with four normally closed contacts, 25 A at 400 V AC, a 230 V AC coil and a two-module DIN rail body.
02What does 4NC mean for 412536?
All four contacts are closed when the coil is not energised and open when it is. The load stays on without control power and switches off when the coil is energised.
03What utilisation categories does 412536 support?
The product page and data sheet list AC7a/AC1 at 25 A and AC7b/AC3 at 10 A under IEC/EN 61095, so motor duty is limited compared with resistive duty.
04What coil voltage range does 412536 accept?
The excitation range is 195 to 253 V AC for a 230 V coil. The data sheet gives 0.85 to 1.1 times Uc for operation and 0.2 to 0.75 times Uc for drop-out.
05Can 412536 be fitted with auxiliary contacts?
Yes, the product page lists auxiliary contact 412430 for extra signalling or control, and the contactor is two modules wide with a prong busbar entry on top.