Brand:

Kyoritsu KEW 3125B High Voltage Insulation Tester 5kV

Description

Overview

Kyoritsu KEW 3125B is a battery-powered high-voltage insulation tester that applies up to 5000 V and displays insulation resistance up to 1 TΩ. The maker calls this class the de facto standard for high-voltage insulation testers, and it is a common choice for maintenance teams who need to prove that medium-voltage cables, transformers, generators, switchgear and large motors are fit to be energised. It comes packed in a hard carrying case with its leads and uses eight C-size cells. Seven Star LLC is an independent supplier serving Oman and the GCC; the notes below let a buyer check that the KEW 3125B fits the test plan before an RFQ is raised.

Five test voltages for different assets

The tester offers 250 V, 500 V, 1000 V, 2500 V and 5000 V. Typical practice is to match the test voltage to the rated voltage of the asset: lower steps for low-voltage wiring and control gear, 2500 V for medium-voltage motors and cables, and 5000 V for higher rated equipment where a more searching test is needed. The display scale extends from 0.0 to 100.0 MΩ at 250 V up to 80 to 1000 GΩ at 5000 V, so the same instrument can describe both a marginal winding and a very healthy cable. Accuracy is plus or minus 5 percent of reading plus 3 digits across the stated ranges, widening to plus or minus 20 percent of reading when the 5000 V result is 100 GΩ or higher.

Kyoritsu KEW 3125B ratings and specification

Item KEW 3125B
Test voltages 250, 500, 1000, 2500, 5000 V
Maximum reading Up to 1 TΩ (1000 GΩ at 5000 V)
Short-circuit current 1.5 mA
Rated test current 0.7 to 0.9 mA at 0.25 MΩ, 0.8 to 1 mA at 0.5 MΩ, 1 to 1.2 mA at 1 MΩ and 2.5 MΩ, 1 to 1.2 mA at 5 MΩ
Insulation accuracy Plus or minus 5 percent plus 3 digits
Voltage measurement AC 30 to 600 V (50/60 Hz); DC plus or minus 30 to 600 V; plus or minus 2 percent plus 3 digits
Diagnosis functions Polarization index and dielectric absorption ratio, with a filter function
Safety IEC 61010-1 and 61010-2-030 CAT IV 300 V / CAT III 600 V, pollution degree 2
Power source Eight LR14/R14 cells, 12 V DC
Instrument size 177 x 226 x 100 mm
Case size 300 x 315 x 125 mm hard case
Mass About 1.9 kg with batteries; about 4 kg with accessories

PI and DAR diagnosis with the KEW 3125B

A single spot reading tells you how good the insulation is today; PI and DAR tell you how the insulation is behaving. Polarization index is the resistance after 10 minutes divided by the resistance after 1 minute. The catalogue gives these criteria: 4.0 or more is best, 4.0 to 2.0 is good, 2.0 to 1.0 is a warning and 1.0 or less is bad. Dielectric absorption ratio is the 1 minute value divided by the earlier value, measured at either 15 or 30 seconds as selected by the user: 1.4 or more is best, 1.25 to 1.0 is good and below 1.0 is bad. DAR is useful when a 10 minute test is impractical, for example on a busy shutdown.

Differences within the 3025B/3125B family

  • KEW 3025B tests at 250, 500, 1000 and 2500 V, reads to 100 GΩ and weighs about 1.7 kg; the KEW 3125B adds 5000 V and reads to 1 TΩ at about 1.9 kg.
  • KEW 3127 offers up to 5 mA short-circuit current and 10 TΩ with a rechargeable lead storage battery, while the KEW 3128 offers 35 TΩ and test voltages up to 12 kV.
  • The KEW 3125B uses 1.5 mA short-circuit current, which suits routine cable and winding diagnosis; the 5 mA models listed in the same selection guide are the alternative when a higher test current is required.

Applications in Oman and the GCC

Utilities in the region use this class of tester on 11 kV and 33 kV cable terminations, transformer windings and busbar sections before and after repair. Oil and gas and petrochemical sites use it on high-voltage motor windings for compressors and pumps, particularly before restarting after long outages. Water and power plants use the PI value to track the ageing of generator and motor insulation from one outage to the next, while factories use it on large motors and cables. The robust case and C-size cell power make it practical to transport to remote sites without mains supply.

Leads, guard terminal and field technique

The supplied set includes model 7165B line probe, 7264A earth cord and 7265A guard cord, each 3 m, plus the 8019 hook-type prod and the 9204 hard case. Optional parts include the 7168B line probe with alligator clip, the longer 7253A with alligator clip (15 m) and the 8302A adaptor for a recorder. The maker notes that instruments with serial number W8534022 or earlier use the older A-series leads, so quote the serial number when you order spare leads. Use the guard terminal to divert surface leakage on a dirty or humid insulator so that it does not distort the bulk resistance reading. Always discharge the object under test after the measurement; the instrument also warns of live voltage on the circuit.

Test planning tips

Plan the sequence before the shutdown: isolate and earth the asset, remove surge arresters and potential transformers that cannot take the test voltage, disconnect cable terminations from the switchgear and fit the guard lead where surface tracking is likely. Start with a lower voltage if you suspect damage, then step up. Write down temperature and humidity, since insulation resistance changes with both, and keep the same voltage and duration for each repeat test so the results can be trended. The bar graph on the display helps you watch the resistance rise as the dielectric charges, and the filter function steadies the number when electrical noise from nearby energised equipment is present.

Care and calibration

Keep the tester dry and clean the leads after use. Replace all eight C cells together. Calibration should follow the schedule defined by your quality system, and the manufacturer’s manual warns that measurement should be made only on de-energised, isolated equipment.

Ordering Kyoritsu KEW 3125B

Please state quantity, delivery site and any optional leads for your Kyoritsu KEW 3125B enquiry. If your assets need higher short-circuit current or more than 5000 V, tell us and we will compare the KEW 3127 and KEW 3128 with this model.

Related items you may also need: Fluke 116 HVAC True-RMS Multimeter with Temperature and uA | Hioki CM4375-50 1000 A AC/DC True RMS Clamp Meter | Fluke 2AC VoltAlert Non-Contact Voltage Tester | All Kyoritsu products.

Documents and quotation

The catalogue for KEW 3025B and KEW 3125B is provided as the datasheet on this page. To request a quotation, send an RFQ with the part number KEW 3125B and the quantity, and we will respond with availability and lead time for Oman or the GCC.

Datasheets & Documents
  • PDF Datasheet Kyoritsu KEW 3125B High Voltage Insulation Tester 5kV Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Kyoritsu is the Japanese maker of hand-held electrical test and measuring instruments sold worldwide under the KEW name: clamp meters, multimeters, insulation testers, earth testers and multifunction installation testers. The business began in 1940, when Takeo Kuramoto set up the Kyoritsu Electronic Research Institute and started making electrical measuring instruments. It was incorporated in 1950 as Kyoritsu Electrical Instruments Works, Ltd., published an English catalogue the following year to reach overseas buyers, and moved to its present site in Meguro-ku, Tokyo in 1957. Its instruments now reach electricians and maintenance engineers in many countries.

Kyoritsu company profile

Founded 1940, Japan, by Takeo Kuramoto (Kyoritsu Electronic Research Institute); incorporated 1950
Headquarters Meguro-ku, Tokyo, Japan
Company Kyoritsu Electrical Instruments Works, Ltd.; capital 42 million yen; about 200 employees
Core technology Clamp-on current measurement, digital multimeters, insulation and earth resistance testers, installation testers
Typical applications Electrical maintenance, installation inspection, commissioning and periodic testing of power and control systems
Standards Instruments designed to IEC 61010 measurement categories; installation testers to the IEC 61557 series

Milestones

  • 1940: Takeo Kuramoto founds the Kyoritsu Electronic Research Institute in Japan.
  • 1950: The institute is incorporated as Kyoritsu Electrical Instruments Works, Ltd.
  • 1965: The company develops Japan's first clamp meter and starts production and sales.
  • 1968: The compact DC multi-range clamp meter KS-7 is developed, a world first according to the company.
  • 1979: The auto-ranging digital clamp meter with peak hold, KS-777 (MODEL 2001), is developed as a first in Japan.
  • 2015: The company marks 75 years and establishes Kyoritsu Instruments Asia Pte. Ltd. in Singapore.

How a clamp meter works

A clamp meter measures the current in a conductor without breaking the circuit. The jaw opens, closes around one conductor and senses the magnetic field that the current produces, so the circuit stays energised and in service while you read the load. On an AC clamp the jaw works like a current transformer. AC/DC models such as the KEW 2046R and KEW 2056R also respond to direct current, which makes them suitable for battery systems and drives as well as mains circuits. For a valid reading, enclose a single conductor only: placing line and neutral together in the jaw cancels the field and the display falls close to zero. Check the jaw opening against the largest cable or busbar, the current range against the expected load, and the measurement category against the location of the test.

Where these instruments are used in Oman and the GCC

These testers serve the routine work of electrical teams in Oman and across the Gulf: load and imbalance checks on distribution boards, insulation tests on motors and cables in oil, gas and water plants, earth electrode verification at substations and towers, and periodic inspection of commercial and residential installations.

Kyoritsu models we list

Family Examples
AC/DC clamp meters KEW 2046R, KEW 2056R
Digital multimeters KEW 1062
Insulation testers KEW 3552, KEW 3125B
Earth testers KEW 4105A
Installation testers KEW 6516

Ordering Kyoritsu products: what we need

Send the exact model name as printed on the front panel, for example KEW 3552 rather than a general description, together with the quantity and your delivery location. Add the accessories you want, such as temperature probes, USB adapters, carrying cases or extra test leads, because the standard kit differs between models. For spare leads on older units, include the serial number so that we can match the correct lead series. Seven Star LLC is an independent supplier serving Oman and the GCC, and we reply to each RFQ with availability and lead time.

Facts checked against the Kyoritsu Electrical Instruments Works corporate data, company history and product pages, November 2026.

FAQ

Questions about the Kyoritsu KEW 3125B High Voltage Insulation Tester

Answers from our engineering team on installation, compatibility and integration.

01What test voltages does the Kyoritsu KEW 3125B offer?
It provides 250 V, 500 V, 1000 V, 2500 V and 5000 V. The maximum insulation reading is up to 1 TΩ, and the short-circuit current is 1.5 mA.
02Does the KEW 3125B calculate PI and DAR?
Yes, it has a diagnosis function for polarization index (10 minute over 1 minute) and dielectric absorption ratio (1 minute over a 15 or 30 second value selected by the user).
03How is the KEW 3125B powered?
It uses eight LR14/R14 (C size) cells giving 12 V DC. The instrument weighs about 1.9 kg with batteries and is supplied in a hard case with accessories.
04How does KEW 3125B differ from KEW 3025B?
KEW 3025B has test voltages of 250 to 2500 V and reads up to 100 GΩ, while KEW 3125B adds a 5000 V range and reads up to 1 TΩ. Both have 1.5 mA short-circuit current.
05What safety category does the KEW 3125B meet?
It conforms to IEC 61010-1 and 61010-2-030 for CAT IV 300 V and CAT III 600 V at pollution degree 2. It also includes a live voltage warning.