Brand:

GESTRA MK 45-2 Thermostatic Steam Trap PN 40 Single Seat

Description

Choosing the GESTRA MK 45-2: single-seat thermostatic trap for larger condensate flow

If a small steam trap keeps backing up condensate, the usual cure is more orifice area rather than a bigger body. The GESTRA MK 45-2 is the single-seat sibling of the tandem-seat MK 45-1 in the same PN 40 / Class 300 forged body, and the datasheet states it is intended for larger condensate flowrates. Sizes are DN 15, 20 and 25 (½, ¾ and 1 inch).

Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. The facts below come from the MK 45-2 datasheet, so you can check a purchase against line conditions before requesting a quote.

MK 45-2 at a glance

Parameter Value
Type GESTRA MK 45-2, thermostatic steam trap, single seat
Sizes DN 15, 20, 25
Rating PN 40 / Class 300
Capsule options 5N2 standard; 5U2 and 5H2 special
Capsule behaviour N: about 10 K below boiling; U: about 30 K; H: about 5 K
Max. differential pressure 32 bar / 465 psi (PN 40, Class 300); 19.6 bar / 284 psi (Class 150)
Body and cover 1.0460 / SA 105
Cap screws 1.7225 / A 193 B7
Gasket Graphite/CrNi
Internals Y-strainer, nozzle insert with non-return cone, high-grade steel
Flanged length L 150 / 150 / 160 mm
Flanged weight 3.7 / 4.3 / 4.8 kg
Screwed or socket-weld length 95 mm, 2.2 / 2.1 / 2.0 kg
Butt-weld length 200 mm, 2.5 kg
Flange PN 40 temperature 420 °C at 17.1 barg; 300 °C at 27.6 barg

What a single seat changes

With one seat the nozzle passage is larger, so the MK 45-2 discharges more per second at a given differential pressure than the tandem-seat MK 45-1. The price is one sealing line rather than two. On lines that pass a steady flow, such as a main-header drip, a heat exchanger outlet or a separator drain, the single seat is the better balance. The capsule codes carry the digit 2 (5N2, 5U2, 5H2) to show they match this seat; spare regulator stock codes are 375110 for 5N2, 375112 for 5U2 and 377589 for 5H2.

Where the MK 45-2 is used

  • Steam mains and branch drip legs in utility plants and district energy systems.
  • Shell-and-tube heater outlets where condensate has to leave without banking up and flooding tubes.
  • Process skids in refineries and petrochemical plants that use saturated steam at moderate pressure.
  • Laundry, kitchen and pharmaceutical utility loops in hotels and hospitals across the GCC.

Because the capsule reacts to temperature, the MK 45-2 also vents air automatically during start-up, which shortens warm-up of cold lines and speeds restarts after a planned shutdown. Compared with a thermodynamic disc trap, the capsule design discharges continuously rather than in bursts, and compared with a float trap it needs no float and has no ball to be damaged by water hammer.

Picking the capsule for MK 45-2

N, U or H?

The N capsule is the all-round choice, releasing condensate about 10 K below boiling. Capsule U makes the trap wait until condensate is about 30 K cooler, which recovers more sensible heat but needs room for condensate to back up in the pipe ahead of the trap. Capsule H opens at about 5 K undercooling, for cases such as heated process piping where condensate must not be allowed to cool noticeably.

Whatever you choose, the datasheet cautions that the control membrane capsule must not see superheat above 5 °C.

Installation notes for MK 45-2

Mount the trap below the equipment it drains and keep 30 mm free above the cover for withdrawal of the cover and capsule. Use the flanged version where the line already carries PN 40 or Class 300 flanges, the screwed version where a union and short nipple are standard, and the butt-weld version through transition pieces if the line is welded. Pipe stress at the weld-in version is lowest when the 200 mm face-to-face length is respected.

Ratings and limits that matter for MK 45-2

The datasheet gives pressure and temperature ratings for each flange standard. On the EN 1092-1 PN 40 flange the trap is good for 40.0 barg at -10 to 20 °C, 37.1 barg at 100 °C, 33.3 barg at 200 °C, 30.4 barg at 250 °C, 27.6 barg at 300 °C, 25.7 barg at 350 °C, 23.8 barg at 400 °C and 17.1 barg at 420 °C. On ASME B16.5 Class 150 flanges the limit starts at 19.6 barg and falls to 5.5 barg at 425 °C, while Class 300 flanges, screwed sockets and weld ends start at 51.1 barg. In every case the admissible service temperature is the saturated steam temperature, so the pressure rating is not a statement that superheated steam is permitted.

The datasheet adds a warning for the whole MK 45 family: above 300 °C intercrystalline corrosion can occur in the capsule region, and the equipment should not be run hotter unless that can be ruled out. The equipment is designed for group 2 fluids under the Pressure Equipment Directive. As an ATEX note, the trap has no ignition source of its own, but static charge and hot surfaces from the fluid remain the responsibility of the plant operator.

Servicing the MK 45-2

Cap screws are M 10 x 25. After undoing them, lift the cover, then the capsule can be changed in the field. Keep a strainer set (375113) and the two gaskets (375159 and 375162) as a minimum spares kit. Because the capsule packs ten per box and gaskets fifty per box, the manufacturer asks for smaller quantities to be arranged through local suppliers.

Documents and quotation

The MK 45-2 datasheet is attached to this page. Send your RFQ with part number MK 45-2, quantity, connection standard, capsule code and the pressure and temperature of the line. We will respond with availability for Oman and the GCC.

Documentation and Compliance

Industrial buyers often need more than the hardware. When you order the GESTRA MK 45-2, tell us which documents your project or quality team requires, such as certificates of origin, conformity declarations, calibration or test records, or hazardous-area certificates where the variant carries them. Mentioning these at the enquiry stage avoids delays at customs and at goods receipt on site. For tenders and project packages, we can also align the quotation with your line-item format so that GESTRA steam traps & steam specialties items can be checked against the bill of materials quickly.

Datasheets & Documents
  • PDF Datasheet GESTRA MK 45-2 Thermostatic Steam Trap PN 40 Single Seat Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

GESTRA is the German steam and condensate specialist behind the UNA ball float steam traps, the MPA blowdown valves and a long line of boiler level and conductivity controls. It was founded in Bremen in 1902 by Gustav F. Gerdts, and has been part of Spirax Sarco since 2017.

Seven Star LLC is an independent supplier in Muscat. We list GESTRA steam traps, blowdown valves and boiler control equipment, and supply GESTRA parts and spares to boiler houses and process plants in Oman and the GCC.

GESTRA company profile

Established 29 October 1902, Bremen, Germany, by Gustav Friedrich Gerdts; renamed Gustav F. Gerdts KG in 1907
Ownership history Became a stock corporation (GESTRA AG) in 1987, was taken over by Flowserve in 2002, and has been part of the Spirax Sarco group since 2017
Product families Steam traps, non-return and check valves, boiler blowdown valves, control valves, and boiler control electronics for level, conductivity and temperature
Applications Steam boilers, steam distribution and condensate return in process plants, power stations, hospitals, food and textile plants

Milestones

  • 1902: Gustav Friedrich Gerdts founds the company in Bremen on 29 October.
  • 1907: The company is renamed Gustav F. Gerdts KG.
  • 1987: It becomes a stock corporation, GESTRA AG.
  • 2002: Flowserve takes over GESTRA.
  • 2017: GESTRA becomes part of the Spirax Sarco group.

GESTRA products we list

Series Type What it does
UNA 45, UNA 16, UNA 38 Ball float steam traps Continuous condensate discharge from heat exchangers and process equipment; the UNA 38 is the high-pressure version (PN 100)
BK 45 Bimetallic steam trap Robust trap for steam main drainage and tracing, resistant to water hammer
MK 45, TK 23, SMK 22-81 Thermostatic steam traps Air venting and condensate discharge; the SMK 22-81 is the sanitary version for clean steam
MPA 46 Rapid-action blowdown valve Short, intermittent bottom blowdown that removes sludge from the boiler
NRS 1-54, NRR 2-50, NRR 2-60, NRGT 26-2 Boiler level controls Water level limiting, feedwater control and continuous level measurement
LRGT 16-1, LRR 1-50 Conductivity measurement and control Keeps boiler water conductivity in range through continuous blowdown
TRS 5-50 Safety temperature limiter SIL 3 temperature limiting for boilers and hot water systems

The type of steam trap follows the duty. Ball float traps discharge condensate as soon as it forms, which suits heat exchangers with changing loads. Thermostatic and bimetallic traps hold condensate back slightly and suit steam mains, tracing and air venting. On the boiler itself, GESTRA level and conductivity electronics work as a system: electrodes or transmitters in the boiler, controllers in the panel, and the feedwater and blowdown valves they drive.

Where GESTRA products are used

In Oman and the GCC, GESTRA equipment is used in boiler houses of refineries, petrochemical and fertiliser plants, power and desalination stations, food and beverage plants, laundries, hotels and hospitals.

Ordering GESTRA parts: what we need

Send the type designation, pressure rating (PN) and connection size (DN), the end connection (flanged, screwed or socket weld), the operating pressure and condensate load for steam traps, and the supply voltage and bus type (CAN bus, 4-20 mA) for control equipment. For electrodes, add the insertion length.

Facts checked against GESTRA company history and Bremen city records, October 2026.

FAQ

Questions about the GESTRA MK 45-2 Thermostatic Steam Trap PN 40 Single

Answers from our engineering team on installation, compatibility and integration.

01How does the MK 45-2 differ from the MK 45-1?
The MK 45-2 has a single seat for larger condensate flowrates and 5N2, 5U2 or 5H2 capsules; the MK 45-1 has a tandem seat for low flowrates.
02Which spare regulator codes does the datasheet give for the MK 45-2?
Complete membrane regulators are listed as 375110 for 5N2, 375112 for 5U2 and 377589 for 5H2; the strainer set is 375113.
03What flange standards does the MK 45-2 support?
EN 1092-1 PN 40 and ASME B16.5 Class 150 or Class 300 flanges, plus screwed, socket-weld and butt-weld ends.
04What is the flanged face-to-face length of the MK 45-2?
150 mm for DN 15 and DN 20 and 160 mm for DN 25, with weights of 3.7, 4.3 and 4.8 kg.
05Is the MK 45-2 suitable for superheated steam?
No. The datasheet says the capsule must not be exposed to superheat above 5 degrees C, so use it on saturated steam and condensate.