Brand: Bently Nevada
Bently Nevada 136711-01 3500/60 RTD/TC Barrier I/O Module
Description
Bently Nevada 136711-01 3500/60 RTD/TC I/O module with internal barriers
The Bently Nevada 136711-01 is the 3500/60 RTD/thermocouple I/O module with internal barriers and internal terminations, not isolated. The manufacturer ordering table lists it as I/O type 05 for the 3500/60 temperature monitor. It carries six temperature channels, each configured for an RTD or a thermocouple, with barrier circuitry built in for sensors that sit in hazardous areas.
It is the version for the 3500/60 monitor, the model without recorder outputs. Seven Star LLC supplies it in Oman and the GCC as a spare for existing racks.
136711-01 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Bently Nevada 136711-01 |
| Description | 3500/60 RTD/TC I/O module, internal barriers, internal terminations, non-isolated |
| Ordering option | 3500/60-05-BB |
| Channels | 6, RTD or thermocouple, configured by software |
| Power consumption | 7 W nominal (monitor) |
| Recorder outputs | no |
| Input impedance | 10 MΩ per lead |
| Thermocouple types | Type E from -100°C to +1000°C (the datasheet lists further TC types) |
| RTD ranges | 100 Ω platinum (0.00385) -200°C to +850°C; 120 Ω nickel -80°C to +260°C; 10 Ω copper -100°C to +260°C |
| Operating temperature | -30°C to +65°C with internal/external terminations; 0°C to +65°C for internal-barrier I/O with internal terminations |
| Isolated TC option | 250 Vdc channel-to-channel isolation (other I/O types) |
| Compatible monitor | 3500/60 temperature monitor (6 channels) |
Values are from the 3500/60 and 3500/61 datasheet (141540 Rev. L).
How the 3500/60 temperature monitor works
The monitor reads six temperature sensors, linearises them for the configured sensor type, and compares each reading with user-set Alert and Danger limits. Typical uses are bearing metal temperatures, motor winding RTDs, and lube oil or process thermocouples. Alarm logic is programmed with the 3500 Rack Configuration software, and each channel can be a different type, so RTDs and thermocouples can be mixed on the same module.
In Triple Modular Redundant systems temperature monitors are installed in adjacent groups of three and vote on each channel. The barrier I/O module is an option for sensors in classified areas; the datasheet gives a lower minimum temperature range for the sensors when external barriers are used.
What makes 136711-01 different
Compared with the plain internal-termination modules this module adds barriers, which require checking the installation drawing and the 0°C minimum rack temperature. It is non-isolated, unlike the TC isolated I/O modules that give 250 Vdc channel isolation for thermocouples. No recorder outputs are provided with the 3500/60.
| Ordering option | I/O module type |
|---|---|
| 3500/60-05 | RTD/TC non-isolated, internal barriers (this module) |
| 3500/60-01 / -02 | RTD/TC non-isolated, internal / external terminations |
| 3500/60-03 / -04 | TC isolated, internal / external terminations |
| Agency options | 00 none, 01 CSA/NRTL/C Class 1 Div 2, 02 ATEX/IECEx/CSA Class 1 Zone 2 |
Selection and ordering checklist for 136711-01
- Count the sensors and decide RTD or thermocouple for each channel.
- Check which RTD type: 100 ohm platinum (alpha 0.00385 or 0.00392), 120 ohm nickel or 10 ohm copper.
- Confirm the hazardous-area drawing and agency option.
- Verify that the minimum 0°C operating temperature suits the rack location.
- Choose the 3500/60 when you do not need 4-20 mA recorder signals.
- Decide on external termination blocks only for non-barrier modules; barrier I/O has internal terminations.
Installation and maintenance
Wire each channel with the correct lead count: 3-wire or 4-wire for RTDs, extension cable of the right thermocouple type for TCs. Use shielded cable and ground the shield at one end. After insertion, check live readings against a calibrated reference and confirm the Alert and Danger setpoints. Open-circuit and sensor-fault detection should be tested by lifting a lead during commissioning.
Use in Oman and the GCC
Temperature monitoring of bearings and windings is standard on large motors, generators, compressors and turbines in the region. High ambient temperatures make baseline logging important, because a bearing running warm at the start of summer may be normal for that site but still needs a trend to prove it.
Typical RTD and thermocouple arrangements with 136711-01
On a motor, the 136711-01 channels often take six stator winding RTDs, while on a pump or compressor the same six channels cover bearing metal temperatures, thrust pad sensors and oil drain thermocouples. Since each channel is set to RTD or TC by software, one module can read a mixture, and spare channels can be added without new hardware. The 3500/60 monitor has no recorder output, so signals that must reach a DCS are normally taken over the 3500 Modbus or relay modules.
Write down the sensor type, wire count and range for every channel at commissioning and keep the list in the module file. Without it, a replacement 136711-01 is difficult to verify.
Information to send with your RFQ
- Part number 136711-01 and quantity
- Monitor part number and number of channels used
- Sensor types and area classification
- Delivery location in Oman or the GCC
Commissioning checks for a 3500/60 with 136711-01
After installing the module, confirm in the 3500 Rack Configuration Software that each of the six channels is set to the sensor actually wired to it: RTD type and wiring, or thermocouple type. A thermocouple configured as the wrong type still gives a reading, but the value is wrong, so this check matters more than it looks.
Because the module has internal barriers, the hazardous-area loop documentation should be updated with the barrier and cable parameters, and field cabling should be checked against it. Inject known values from a calibrated RTD or thermocouple simulator at the field end of each loop, compare the displayed temperature, and then test the Alert and Danger setpoints so that the relays and the DCS alarms respond as designed.
Related Bently Nevada products: Bently Nevada 125680-01 3500/40M Proximitor I/O Module, Bently Nevada 128240-01 3500/42M Prox/Seismic I/O Module, Bently Nevada 135489-04 3500/40M Proximitor Internal Barrier I/O, Bently Nevada 3500/50 Tachometer Module, Bently Nevada 3500/50M Tachometer Module and Bently Nevada 3500/20 Rack Interface Module.
Documents and quotation
The manufacturer datasheet for the 3500/60 and 3500/61 temperature modules is attached on this page; read it together with your rack configuration and the site specification before confirming an order.
Seven Star LLC is an independent supplier in Muscat serving Oman and the GCC. Stock position, lead time, condition and the certificates that travel with the shipment are confirmed in the written quotation.
Other Models in the 3500 6x Temp Io Range
Seven Star LLC supplies models from the 3500 6x Temp Io range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Bently Nevada 136711-01 3500/60 RTD/TC Barrier I/O Module | Vibration Monitoring | You are viewing this model |
| Bently Nevada 136711-02 3500/61 RTD/TC Barrier I/O Module | Vibration Monitoring | View details |
Datasheets & Documents
- Datasheet Bently Nevada 3500/60 61 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Bently Nevada is the American machinery protection and condition monitoring brand behind the 3500 rack, the 3300 XL proximity probe and the System 1 software. It was founded in 1961 in Minden, Nevada, and is today a Baker Hughes business.
Seven Star LLC is an independent supplier in Muscat. We list Bently Nevada monitors, I/O modules, probes, proximitors, velocity transducers and transmitters for rotating equipment in Oman and the GCC, and source them by full part number.
Bently Nevada company profile
| Established | 1961, Minden, Nevada, USA, by Donald E. Bently. The business started earlier as Bently Scientific in Berkeley, California (1956). |
|---|---|
| Known for | The first commercial eddy-current proximity transducers for measuring shaft vibration and position on high-speed turbomachinery |
| Ownership | Acquired by GE Energy in 2002; part of Baker Hughes since GE Oil & Gas combined with Baker Hughes in 2017 |
| Rack generations | 5000 series (from 1965), 3300 series (from 1988), 3500 series (from 1995), Orbit 60 (current platform) |
| Product families | Machinery protection racks, proximity probes and proximitors, Keyphasor sensors, velocity and acceleration transducers, 2-wire vibration transmitters, general-purpose monitors, portable analyzers, wireless sensors and System 1 condition monitoring software |
| Typical machines | Steam and gas turbines, centrifugal and reciprocating compressors, pumps, motors, generators, fans and gearboxes |
Milestones
- 1956: Donald E. Bently starts Bently Scientific in Berkeley, California.
- 1961: The company moves to Minden, Nevada, as Bently Nevada.
- 1965: The 5000 series monitoring system is introduced.
- 1988: The 3300 series follows.
- 1995: The 3500 machinery protection system is launched.
- 2002 and 2017: GE Energy acquires Bently Nevada; it becomes part of Baker Hughes in 2017.
Bently Nevada product series
| Series | Type | What it does |
|---|---|---|
| 3500 | Machinery protection rack | Continuous online protection with alarm and danger relays. Modules include the 3500/15 power supply, 3500/20 rack interface, 3500/25 Keyphasor, 3500/42M proximitor/seismic, 3500/50 tachometer, 3500/60 temperature, 3500/33 relay and 3500/92 communication gateway |
| 3500 recip modules | Reciprocating compressor monitoring | 3500/70M impulse velocity, 3500/72M rod position and 3500/77M cylinder pressure |
| Orbit 60 | Protection and monitoring platform | The current Bently Nevada platform for protection, condition monitoring and data integration with System 1 |
| 3300 XL 8 mm | Proximity transducer system | Probe, extension cable and proximitor sensor for radial vibration, thrust position and Keyphasor reference on fluid-film bearing machines; also 5 mm and 25 mm versions |
| 330500 Velomitor, 190501 Velomitor CT | Piezo-velocity sensors | Casing velocity on rolling-element bearing machines and low-speed cooling tower fans |
| 990 and 991 | 2-wire transmitters | 4-20 mA vibration (990) and thrust position (991) signals straight into a PLC or DCS, without a monitor rack |
| 1900/65A, 2300 | Compact monitors | Protection for balance-of-plant pumps, fans and motors where a full 3500 rack is not justified |
A proximity probe measures the gap to the shaft, so it sees shaft movement inside a fluid-film bearing directly. A velocity or acceleration sensor sits on the casing and suits rolling-element bearing machines. Critical turbomachinery usually carries two X-Y probes per bearing, two axial probes for thrust position and a Keyphasor probe for speed and phase.
Where Bently Nevada systems are used
In Oman and the GCC, Bently Nevada racks and probes protect gas turbines, compressors and steam turbines in gas processing, LNG, refining, petrochemical, power and desalination plants. Many installations are 3500 racks that have run for years, so most requests are for like-for-like module, probe, extension cable and proximitor replacements, plus upgrades to newer monitors.
Ordering and replacement: what we need
For probes and proximitors, send the full part number with all option digits (for example 330101-00-27-10-02-05). The digits set the probe length, cable length, connector and approvals, and the probe, cable and proximitor must match in total system length. For 3500 modules, send the module and I/O part numbers from the rack and say whether the I/O is internal or external termination, or barrier type. If a module is obsolete, we quote the replacement that Bently Nevada names and point out any configuration or firmware change.
Facts checked against Baker Hughes Bently Nevada pages and published company history, October 2026.
Browse Bently Nevada products by category: Vibration.
Related products
Frequently Asked Questions
It is the 3500/60 RTD/thermocouple I/O module with internal barriers and internal terminations, not isolated.
Yes. Each of the six channels can be set to RTD or thermocouple, and both can be mixed on the one module.
0°C to +65°C when used with the internal-barrier I/O module, instead of -30°C to +65°C with other I/O types.
No. The 3500/60 has no recorder outputs; the 3500/61 does, one per channel.
No. It is a non-isolated RTD/TC module. Isolated thermocouple modules are separate I/O types.


















Reviews