Brand: Weidmüller
Weidmuller 1176030000 ACT20M-UI-AO-S Temperature Converter
Description
Weidmuller 1176030000 ACT20M-UI-AO-S: universal temperature and signal converter
Weidmuller 1176030000 is the ACT20M-UI-AO-S, a universal isolating converter that reads thermocouples, RTDs, potentiometers, resistance and standard voltage or current signals and turns them into a standard analogue output. It is the most capable member of the ACT20M family: one 6.1 mm wide module can replace separate temperature transmitters for Pt100 and thermocouple inputs, which makes it a useful stocked spare in plants with mixed sensors. The datasheet calls it a temperature converter and analogue isolating amplifier with universal U, I, R and temperature input.
Input capabilities of 1176030000
Thermocouple types are B, C, E, J, K, L, N, R, S, T, U, W3, W5 and LR, with ranges up to minus 200 to plus 2300 C depending on the type. RTD types include PT10, PT20, PT50, PT100, PT250, PT300, PT400, PT500, PT1000, Ni50, Ni100, Ni120 and Ni1000 in 2-, 3- and 4-wire connection. For example, PT100 covers minus 200 to 850 C, Ni100 minus 60 to 250 C, type K minus 180 to 1372 C and type J minus 100 to 1200 C. Potentiometers of 10 to 100 kilohm and resistances up to 10 kilohm can also be measured, together with voltage inputs 0(2) to 10 V, 0(1) to 5 V, 0 to 1 V and 0.2 to 1 V, and current inputs 0 to 20 mA and 4 to 20 mA. The minimum measurement span is 10 C for RTD and 50 C for thermocouples.
Specification table for 1176030000
| Parameter | Value |
|---|---|
| Order No. / Type | 1176030000 / ACT20M-UI-AO-S |
| Version | Temperature converter, analogue isolating amplifier, universal input |
| Thermocouples | B, C, E, J, K, L, N, R, S, T, U, W3, W5, LR |
| RTD | PT10 to PT1000, Ni50 to Ni1000; 2-, 3-, 4-wire |
| Potentiometer / resistance | 10 to 100 kilohm / 0 to 10 kilohm |
| Voltage in | 0(2) to 10 V; 0(1) to 5 V; 0 to 1 V; 0.2 to 1 V |
| Current in | 0 to 20 mA; 4 to 20 mA |
| Sensor supply | more than 15 V DC at 20 mA |
| Output | 1; voltage or current, with downscale and upscale on sensor error |
| Load | 600 ohm or less at 28 mA; 10 kilohm or more voltage |
| Accuracy | less than 0.1 percent of range |
| Step response | 400 ms at U/I; 1 s at temperature |
| Wire break detection | yes for RTD, potentiometer and thermocouple |
| Supply | 24 V DC plus or minus 30 percent |
| Configuration | FDT/DTM software |
| Dimensions / weight | 6.1 x 112.5 x 114.3 mm / 80 g |
| Ex marking | II 3 G Ex nA IIC T4 Gc |
| Approvals | cULus E337701 |
How 1176030000 differs from the other ACT20M modules
- It is configured with FDT/DTM software and requires configuration, whereas the CI-CO-S types need none and the AI-AO-S uses DIP switches.
- Its step response is 400 ms for voltage and current inputs and 1 s for temperature inputs, far slower than the 7 ms of the pure current isolators because of linearisation and filtering.
- It signals sensor errors: the output goes to a downscale of 0 V or 3.5 mA, or an upscale of 11 V or 23 mA.
- Its current output can drive 600 ohm up to 28 mA, compared with 23 mA on the simpler modules.
Application of 1176030000 in plants
Use it for temperature measurement from thermocouples in furnaces, boiler skin and exhaust gas, from Pt100 sensors in bearings and process lines, and for converting potentiometer position signals. In Omani refineries and power stations the module is mounted in cabinets that receive raw sensor wiring and delivers a clean 4 to 20 mA to the DCS.
Configuring and installing 1176030000
Connect the module to a PC with the FDT/DTM tool, select the sensor type, set the measuring range and decide the error behaviour of the output. Wire the sensor to the screw terminals (0.4 to 0.6 Nm), supply 24 V DC or use the CH20M rail bus, and check wire-break detection by disconnecting a lead.
Maintenance
Keep the configuration file on record because the module has no DIP switches to read. A replacement module must be loaded with the same range file before being put into service.
Selecting the sensor range for 1176030000
The minimum measurement span is 10 C for RTDs and 50 C for thermocouples, so choose a range wide enough to respect these spans. A Pt100 reading minus 50 to 150 C gives a 200 C span and produces a high resolution on a 4 to 20 mA output, whereas a thermocouple type K from 0 to 1200 C uses most of its range. The 1 s response is acceptable for slowly changing temperatures. If an alarm is needed on sensor failure, set the upscale value of 23 mA or the downscale value of 3.5 mA so the control system recognises a fault.
For RTDs prefer a 3-wire or 4-wire connection to compensate lead resistance; the datasheet lists 2-, 3- and 4-wire connection options. Potentiometer inputs of 10 to 100 kilohm are useful for valve position feedback and old damper actuators.
Typical project data for 1176030000
When documenting this unit in an instrument index, list the sensor type, the configured range, the output signal, the error action and the tag number. Because the module is configured by software, add the configuration file to the project folder. The operating temperature range of minus 25 to 70 C, the 24 V DC supply with plus or minus 30 percent tolerance, the power consumption and the insulation voltage of 2.5 kV rms should be recorded for the engineering contractor. The unit also lists a 3-way isolation between supply, input and output, which supports use in plants with separate earthing systems.
Documents and quotation
The datasheet for 1176030000 accompanies this page. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Send an RFQ with 1176030000, quantity and delivery location to receive a quotation.
Ordering Checklist for the Weidmüller 1176030000
Before you ask for a quotation for the Weidmüller 1176030000, check the full order code on the nameplate of the unit you are replacing, the supply voltage, and the process or signal ranges your system expects. If this is an upgrade rather than a like-for-like swap, tell us the existing make and model so that mounting, wiring and connection details can be checked against the isolator & barrier already installed. For multi-unit orders, list the quantity per site and the delivery location in Oman or the wider GCC, so packing, paperwork and lead time can be confirmed in a single quotation.
Other Models in the Act20m Range
Seven Star LLC supplies models from the Act20m range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Weidmuller 1175980000 ACT20M-CI-CO-S Signal Isolator | Isolator & Barrier | View details |
| Weidmuller 1176030000 ACT20M-UI-AO-S Temperature Converter | Isolator & Barrier | You are viewing this model |
Datasheets & Documents
- Datasheet Weidmuller 1176030000 ACT20M-UI-AO-S Temperature Converter Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Weidmüller is a German family-owned maker of electrical connection and industrial electronics products, headquartered in Detmold. The company dates from 1850 and was re-established in Detmold in 1948; it specialised in terminal blocks from the 1940s onward. Weidmüller makes Klippon terminal blocks, power supplies, remote I/O and enclosures, and reported over one billion euros in revenue in 2023.
Seven Star LLC lists Weidmüller PRO MAX power supplies and SAK terminal blocks, and supplies Weidmüller components to panel shops and plants in Oman and the GCC.
Weidmüller company profile
| Founded | 1850, Germany |
|---|---|
| Headquarters | Detmold, Germany (since 1948) |
| Ownership | Family-owned |
| Revenue | Over €1 billion (2023) |
| Product families | Klippon Connect terminal blocks, PRO MAX and PRO TOP power supplies, u-remote I/O and fieldbus couplers, Klippon enclosures, connectors and tools |
Milestones
- 1850: Weidmüller is founded.
- 1948: The company is re-established in Detmold.
Weidmüller products listed here
The listed power supplies are DIN rail switch-mode units with 24 V DC output: a PRO MAX single-phase unit rated 180 W and 7.5 A (85 to 277 V AC input), and a PRO MAX3 three-phase unit rated 240 W and 10 A (320 to 575 V AC input). The SAK series is the screw clamp feed-through terminal block family found in many existing panels. Weidmüller now flags several SAK types as being phased out and names a replacement for some of them.
Weidmüller products we list
Ordering Weidmüller parts: what we need
Weidmüller identifies every item by a ten-digit order number, and that number is the surest way to quote. Without it, send the type printed on the part. For power supplies add input voltage and phases, output voltage and current. For terminal blocks add the conductor cross-section, color, and the end plates, cross-connections and markers you need, since accessories are specific to each series.
Facts checked against Weidmüller milestone lists and distributor profiles, October 2026.
Browse Weidmüller products by category: Electrical & Power Modules.
FAQ
Questions about the Weidmuller 1176030000 ACT20M-UI-AO-S Temperature
Answers from our engineering team on installation, compatibility and integration.
01Which sensors can 1176030000 read?
Thermocouples B, C, E, J, K, L, N, R, S, T, U, W3, W5, LR, RTDs from PT10 to PT1000 and Ni50 to Ni1000, potentiometers and standard signals.
02How is it configured?
With FDT/DTM software; the module requires configuration before use, and the configuration is stored in the module.
03What happens on a sensor fault?
Wire break detection is active for RTD, potentiometer and thermocouple; the output goes downscale or upscale to 0 V or 3.5 mA and 11 V or 23 mA.
04How fast is the response?
400 ms for voltage and current inputs and 1 s for temperature inputs.
05What is the sensor supply?
More than 15 V DC at 20 mA, with accuracy of less than 0.1 percent of the measuring range.