Brand:

MTL SD275X 240 V AC High-Current Surge Protector

Description

Mains protection from the SD range: the SD275X

Most of MTL’s SD modules guard low-voltage signal loops. The MTL SD275X is the exception: a 220 to 240 V ac protector for the supply to programmable controllers and I/O systems. It carries up to 3 A with a series resistance of only 0.1 ohm, a nominal rating of 320 V dc or 240 V ac, and a rated voltage of 360 V dc or 275 V ac. Surge capability is stated as 6.5 kA at 8/20 microseconds, against the 20 kA of the low-voltage modules.

SD275X ratings table

Model SD275X
Application 220-240 V ac supplies, PLC and I/O systems
Nominal voltage 320 V dc / 240 V ac
Nominal current 3 A (external 3 A fuses required)
Series resistance 0.1 ohm
Maximum leakage current 50 microamps
Rated voltage (MCOV) 360 V dc / 275 V ac
Protection level at 1 kV per microsecond below 700 V
Residual voltage at isn 850 V
Maximum discharge current 6.5 kA (8/20 microseconds)
Lightning impulse current 1.0 kA (10/350 microseconds)
Overstressed fault mode 9 kA
Impulse durability 6.5 kA
Compliance EN 60950-1 and EN 61010 for LVD
Mounting 35 mm DIN rail
Weight about 70 g

SD275X compared with SD150X

The SD150X is the 110 to 120 V twin: 150 V dc and 120 V ac nominal, a rated voltage of 170 V dc and 130 V ac, a voltage protection level below 400 V and residual voltage of 450 V. The SD275X lifts those figures to 320 V dc, 240 V ac, 360 V dc, 275 V ac, below 700 V and 850 V. Both use 0.1 ohm series resistance, 3 A current, 6.5 kA surge rating and require external 3 A fuses. Install the voltage grade that suits the local supply; 220 to 240 V ac supplies belong to the SD275X, while 110 to 120 V equipment needs the SD150X.

Neither type has the ATEX certificate of the signal-level SD devices, so keep both in the safe area.

Where Oman and GCC plants fit the SD275X

The control-room panel supply is often the entry point for surges: a cabinet fed from a long outdoor cable sees induced transients from nearby lightning. The SD275X protects the mains feed to PLC racks, remote I/O panels in plant substations, instrument power distribution in refineries, and the power input of analyser houses. The datasheet identifies PLC and I/O systems as the example application.

Combine it with SD devices on the signal wiring and TP48 devices on field transmitters so that every route into the system has protection.

Installation advice for SD275X

Fit 3 A fuses ahead of the module, as required. Clip onto the DIN rail and connect to the live and neutral conductors, using the rail as the protective earth connection. The datasheet’s general earthing guidance applies: bring the cabinet earth, instrument 0 V and IS earth to one point so that the voltage difference between systems stays small during a surge.

Check that the cable cross-section and terminal rating match the 3 A duty, and observe the 2.5 mm2 terminal limit.

Maintenance of SD275X

Review the fuse condition and rail earth bond at each shutdown. Replace the unit after a severe surge event, even if the supply continues to function. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Putting numbers on the SD275X protection level

At 240 V ac the peak is about 339 V, which is below the 360 V dc rating, so the module remains idle in normal service. The voltage protection level of below 700 V at 1 kV per microsecond is the level the protected equipment is exposed to when a fast transient arrives. The protector reduces the stress on the supply input rather than eliminating it, so compare the supply’s own surge rating with that figure.

The 0.1 ohm series resistance at 3 A causes a drop of 0.3 V, about 0.1 percent of the supply, and dissipates roughly 0.9 W, which is easily handled on a DIN rail. Leakage at 50 microamps is below the sensitivity of residual-current devices normally used in control panels, but check earth-leakage monitors in installations with many protectors.

Plan for coordination: the SD275X is a point-of-use device, so install it close to the equipment, and use upstream protection at the incoming board to carry the larger lightning currents.

Compliance and environment for SD275X

The SD150X and SD275X are called out in the datasheet for low voltage directive compliance with EN 60950-1:2006 and EN 61010:2010. They are also tested to the IEC 61643-21 surge protection standard and to the ANSI/IEEE C62.41 and C62.45 impulse guides. Operating temperature runs from minus 40 to plus 80 degrees C, humidity from 5 to 95 percent RH non-condensing, and the case is UL94 V-2 flame rated. These details help when documenting the part in a panel build file.

When listing the protector in a bill of materials, record both the device and its required external fuses, because the datasheet makes the 3 A fuses a condition of use. Place a note beside the part on the panel drawing so that site electricians do not leave the fuse position empty.

Keep a mixture of supply voltages in mind when stocking spares. A site that has both 110 V and 240 V panels may carry the SD150X and SD275X, and the two look similar on the rail, so the printed model name should be checked before fitting.

Documents and quotation

The SD range datasheet covers the SD275X within the same table as the signal modules. Send an RFQ with SD275X, quantity and delivery location in Oman or the GCC.

Spares and Lifecycle Considerations

For critical service, many plants hold one MTL SD275X as an operational spare rather than waiting for a failure. When you plan spares, look at how many identical isolator & barrier units are installed, how long a replacement would take to arrive, and the cost of an unplanned stop. Store spare units in their original packaging in a dry, temperature-controlled area and record the part number and serial number in your maintenance system. We can quote single units or a small spares package and confirm the lead time for each item in writing.

Other Models in the MTL SD Surge Range

Seven Star LLC supplies models from the MTL SD Surge range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
MTL SD07R3 Low-Voltage 3-Terminal Surge ProtectorIsolator & BarrierView details
MTL SD32T3 Three-Terminal Surge Protection DeviceIsolator & BarrierView details
MTL SD275X 240 V AC High-Current Surge ProtectorIsolator & BarrierYou are viewing this model
MTL SDPSTN Telephone Line Surge ProtectorIsolator & BarrierView details
MTL SDRTD 3-Wire RTD Surge Protection DeviceIsolator & BarrierView details
Datasheets & Documents
  • PDF Datasheet MTL SD275X 240 V AC High-Current Surge Protector Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

MTL is a British maker of intrinsic safety interfaces, surge protection and hazardous-area equipment, founded in 1971 in Luton as Measurement Technology Ltd, a spin-off from Kent Instrumentation. In 2008 Cooper Industries bought MTL Instruments for £144 million and placed it in its Crouse-Hinds division; Eaton acquired Cooper in 2012. MTL is now part of Eaton's Crouse-Hinds business, alongside the MEDC signalling range.

Seven Star LLC lists MTL isolators, a fieldbus barrier and the configuration tools for them, and supplies MTL (Eaton) barriers and spare modules to sites in Oman as an independent supplier.

MTL (Eaton) company profile

Founded 1971, Luton, England, as Measurement Technology Ltd
Origin Spin-off from Kent Instrumentation
Headquarters Luton, England
Ownership Eaton (Crouse-Hinds), via Cooper Industries from 2008
Product families MTL5500 and MTL4500 isolators, MTL7700 zener barriers, 9300 fieldbus barriers, surge protection devices, process junction boxes, PCS45 configuration software; MEDC beacons, sounders and call points

Milestones

  • 1971: Measurement Technology Ltd is founded in Luton.
  • 2007: MTL acquires ELPRO Technologies, RTK Instruments and Ocean Technical Systems.
  • 2008: Cooper Industries acquires MTL Instruments for £144 million.
  • 2012: Eaton acquires Cooper Industries.

MTL product families listed here

Most of the listed items are DIN-rail galvanic isolators. The MTL5541 repeater power supply and the MTL5576-THC temperature converter belong to the MTL5500 range, and the MTL 5043 repeater power supply comes from the earlier MTL5000 range that many plants still run. The MTL 9370-FB2 is a fieldbus barrier for intrinsically safe FOUNDATION fieldbus spurs. PCS45 software with the PCL45USB link is the configurator for MTL converter modules. For the listed part CPM08-BN, please send a label photo so the number can be matched to the manufacturer's records. Newer labels show Eaton MTL, older ones Measurement Technology Ltd, and the module numbers are the same. The MTL 9608 is a fieldbus junction box with eight spur outlets plus a trunk-in connection, listed under the Crouse-Hinds series part number FCS-9608.

Where MTL barriers and isolators are used

These interfaces sit in marshalling cabinets wherever instruments are located in Zone 0, 1 or 2 areas: gas plants, refineries, offshore platforms, tank farms and chemical units across the GCC. They power 2-wire transmitters, pass HART, convert thermocouple signals and drive solenoids or alarms while limiting energy to the field circuit.

MTL (Eaton) products we list

Family Examples
Isolator & Barrier Eaton MTL5541 Repeater Power Supply, MTL 5043, MTL 9370-FB2 Intrinsically Safe Fieldbus…, MTL CPM08-BN, MTL5576-THC Temperature Isolator Module
Automation Accessories MTL 9608 Process Junction Box
Automation Software MTL PCS45 Configuration Software and PCL…

Ordering MTL modules: what we need

Send the full module number including every suffix, for example MTL5576-THC and not just MTL5576, and the quantity. Tell us if the module mounts on DIN rail or on a backplane, because MTL5500 and MTL4500 parts are not interchangeable. For a fieldbus barrier give the number of spurs and the enclosure reference. A photo of the side label, which shows the certificate numbers, helps when the certificate for your project file must match.

Facts checked against the Eaton MTL company history and Drives & Controls coverage of the 2008 Cooper offer, October 2026.

FAQ

Questions about the MTL SD275X 240 V AC High-Current Surge Protector

Answers from our engineering team on installation, compatibility and integration.

01Which supplies is the SD275X meant for?
220 to 240 V ac systems such as PLC and I/O power. The datasheet pairs the SD150X with 110 to 120 V ac systems.
02What load current can the SD275X carry?
Up to 3 A, and the unit requires external 3 A fuses according to the footnote in the specification table.
03What surge ratings apply to the SD275X?
6.5 kA maximum surge current, 1.0 kA lightning impulse current at 10/350 microseconds, 9 kA overstressed fault mode and 6.5 kA impulse durability.
04Is the SD275X certified for intrinsically safe circuits?
No. The ATEX Ex ia certificate covers the X, R, R3, RTD and T3 types of low-voltage SD units, but not the SD150X and SD275X, which are mains-voltage devices.
05What clamping levels does the SD275X give?
MCOV 360 V dc or 275 V ac, voltage protection level below 700 V at 1 kV per microsecond and a residual voltage of 850 V.