Brand: MTL (Eaton)
MTL TP48-4-G 4-Wire Transmitter Surge Protector
Description
The four-wire member: TP48-4-G
Some transmitters keep both the supply pair and the signal pair separate. These four-wire instruments, such as many flowmeters and level devices, need every conductor protected. The MTL TP48-4-G does that with five flying leads: +ve, -ve, signal +ve, signal -ve and earth. Its G 1/2 inch thread suits transmitters with BSP-threaded conduit entries.
TP48-4-G technical summary
| Model | TP48-4-G (non-certified, G 1/2 BSP, 4-wire) |
|---|---|
| Certified equivalent | TP48-4-G-NDI |
| Leads | 5 flying leads: +ve, -ve, signal +ve, signal -ve, earth |
| Thread | G 1/2 inch (BSP) |
| Working voltage | 35 V dc maximum |
| Rated voltage MCOV | 58 V |
| Maximum surge current | 20 kA (8/20 microseconds) |
| Lightning impulse current | 2.5 kA (10/350 microseconds) |
| Overstressed fault mode | 12 kA at 3 kA |
| Impulse durability | 10 kA |
| AC durability | 1 A rms, 5T |
| Protection level at 1 kV per microsecond | below 76 V |
| Casing | 316 stainless steel, IP66 |
| Weight | 175 g |
| Humidity | 5 to 95 percent RH non-condensing |
| Lead length and size | 250 mm minimum, 1.0 mm2 (18 AWG) |
TP48-4-G in comparison with TP48-3-G and TP48-G
A 4-wire installation has two independent conductor pairs, so a surge can appear between any of the five points. The TP48-4-G protects all of them. The TP48-3-G protects +ve, -ve and signal, which is enough when the return is shared. The plain TP48-G protects a single 2-wire loop. All three share the 20 kA rating, the 1 MHz bandwidth and the 316 stainless housing, so the choice depends on the transmitter’s wiring and on the sensitivity of its output stage.
The IEC 61508 failure rate table is summarised in the datasheet and the full Exida report is available from the manufacturer’s website, so use the report when preparing a safety calculation.
Applications for TP48-4-G in Oman and GCC industry
Field-mounted mains-powered or externally supplied flowmeters on pipelines and water mains, ultrasonic level instruments on sumps and tanks, and analyser outputs in gas facilities frequently use four wires. The TP48-4-G can be fitted to existing instruments as a retrofit when a lightning-related failure history justifies it, without changing the field cabling, since it uses a spare conduit entry.
Instruments with G 1/2 entries are served by this thread option.
Fitting the TP48-4-G
Isolate power, open the transmitter and screw the TP48-4-G into an unused G 1/2 entry, sealing as the instrument’s ingress rating requires. Connect the five leads exactly as in the datasheet diagram, noting that the unit is wired in parallel across the terminals and the earth lead goes to the internal stud. Check insulation resistance after installation to confirm that no lead has been trapped.
The device handles up to 35 V dc working voltage, so verify the supply and signal voltages of the instrument stay within that limit.
Hazardous-area information for TP48-4-G
For classified areas specify the NDI version. It is approved Ex ia IIC T4 for intrinsically safe loops with an open-circuit voltage below 60 V and input power below 1.2 W, and Ex db IIC T4 as flameproof apparatus fitted into an equally approved housing. The datasheet adds Ex nA IIC T5 and T6 approval for Zone 2. Capacitance and inductance parameters are Ceq of zero and Leq of zero in the intrinsically safe case, so it does not add to the cable calculation.
Upkeep of TP48-4-G
Inspect the thread seal and leads regularly. A surge-damaged unit might show as intermittent noise on the signal, so keep a spare for critical instruments. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.
Planning an order for the TP48-4-G
Because the family has nine standard variants, a purchase request should state three things: the wire count (blank, 3 or 4), the thread letter (N, I or G) and whether the NDI certified suffix is needed. The TP48-4-G is the four-wire, G 1/2 BSP, non-certified model, and TP48-4-G-NDI is the same hardware with intrinsically safe and flameproof certification.
For a plant with mixed instruments, an inventory of the entry threads on transmitters helps. Count how many are G 1/2, M20 and 1/2 NPT, and how many have two, three or four wires. A small stock of the most common variants then covers most failures.
The unit weighs 175 g in 316 stainless steel, so its mass at the end of a conduit entry is small compared with the transmitter. The datasheet describes the 316 stainless steel casing as suitable for harsh environments, and the IP66 rating covers dust and strong water jets, which matters on washed-down process skids.
For the commissioning record, note the instrument tag, the wire count, the entry used and the date of fitting. If a plant experiences a lightning strike, compare the loops with a TP48 fitted against those without, because the datasheet intends the unit to reduce exactly this kind of failure. Failure-rate figures for the family are given as FIT values, one FIT being one failure per billion hours, so a handful of FIT implies a very low expected failure rate per device.
Finally, think about the cable gland and the housing seal. Screwing in a TP48 changes nothing about the ingress protection of the transmitter as long as the thread is sealed correctly, and the IP66 body does not itself leak. Use a suitable thread sealant on parallel G threads where the instrument manufacturer allows it.
Keep spare units in a dry store until needed.
Documents and quotation
Use the TP48 range datasheet when preparing your order. Send an RFQ naming TP48-4-G, quantity and delivery location in Oman or the GCC, and say if the certified NDI version is wanted.
Other Models in the MTL TP48 Surge Range
Seven Star LLC supplies models from the MTL TP48 Surge range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| MTL TP48-4-G 4-Wire Transmitter Surge Protector | Isolator & Barrier | You are viewing this model |
| MTL TP48-N 2-Wire Transmitter Surge Protector | Isolator & Barrier | View details |
Datasheets & Documents
- Datasheet MTL TP48-4-G 4-Wire Transmitter Surge Protector Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
MTL is a British maker of intrinsic safety interfaces, surge protection and hazardous-area equipment, founded in 1971 in Luton as Measurement Technology Ltd, a spin-off from Kent Instrumentation. In 2008 Cooper Industries bought MTL Instruments for £144 million and placed it in its Crouse-Hinds division; Eaton acquired Cooper in 2012. MTL is now part of Eaton's Crouse-Hinds business, alongside the MEDC signalling range.
Seven Star LLC lists MTL isolators, a fieldbus barrier and the configuration tools for them, and supplies MTL (Eaton) barriers and spare modules to sites in Oman as an independent supplier.
MTL (Eaton) company profile
| Founded | 1971, Luton, England, as Measurement Technology Ltd |
|---|---|
| Origin | Spin-off from Kent Instrumentation |
| Headquarters | Luton, England |
| Ownership | Eaton (Crouse-Hinds), via Cooper Industries from 2008 |
| Product families | MTL5500 and MTL4500 isolators, MTL7700 zener barriers, 9300 fieldbus barriers, surge protection devices, process junction boxes, PCS45 configuration software; MEDC beacons, sounders and call points |
Milestones
- 1971: Measurement Technology Ltd is founded in Luton.
- 2007: MTL acquires ELPRO Technologies, RTK Instruments and Ocean Technical Systems.
- 2008: Cooper Industries acquires MTL Instruments for £144 million.
- 2012: Eaton acquires Cooper Industries.
MTL product families listed here
Most of the listed items are DIN-rail galvanic isolators. The MTL5541 repeater power supply and the MTL5576-THC temperature converter belong to the MTL5500 range, and the MTL 5043 repeater power supply comes from the earlier MTL5000 range that many plants still run. The MTL 9370-FB2 is a fieldbus barrier for intrinsically safe FOUNDATION fieldbus spurs. PCS45 software with the PCL45USB link is the configurator for MTL converter modules. For the listed part CPM08-BN, please send a label photo so the number can be matched to the manufacturer's records. Newer labels show Eaton MTL, older ones Measurement Technology Ltd, and the module numbers are the same. The MTL 9608 is a fieldbus junction box with eight spur outlets plus a trunk-in connection, listed under the Crouse-Hinds series part number FCS-9608.
Where MTL barriers and isolators are used
These interfaces sit in marshalling cabinets wherever instruments are located in Zone 0, 1 or 2 areas: gas plants, refineries, offshore platforms, tank farms and chemical units across the GCC. They power 2-wire transmitters, pass HART, convert thermocouple signals and drive solenoids or alarms while limiting energy to the field circuit.
MTL (Eaton) products we list
Ordering MTL modules: what we need
Send the full module number including every suffix, for example MTL5576-THC and not just MTL5576, and the quantity. Tell us if the module mounts on DIN rail or on a backplane, because MTL5500 and MTL4500 parts are not interchangeable. For a fieldbus barrier give the number of spurs and the enclosure reference. A photo of the side label, which shows the certificate numbers, helps when the certificate for your project file must match.
Facts checked against the Eaton MTL company history and Drives & Controls coverage of the 2008 Cooper offer, October 2026.
Browse MTL (Eaton) products by category: Isolator & Barrier, Automation Software.
FAQ
Questions about the MTL TP48-4-G 4-Wire Transmitter Surge Protector
Answers from our engineering team on installation, compatibility and integration.
01What does the 4 in TP48-4-G mean?
It is the four-wire version, protecting +ve, -ve, signal +ve and signal -ve, with five flying leads including the earth lead.
02What thread is the G version?
G 1/2 inch, the BSP parallel pipe thread common on transmitters made to British and Commonwealth conventions.
03Is TP48-4-G certified?
No. The certified equivalent is TP48-4-G-NDI, which is the one shown on the label in the datasheet photograph.
04What bandwidth does the TP48 pass?
1 MHz, and it passes ac or dc signals without attenuation because it is connected in parallel and adds no loop resistance.
05What failure data is available?
The datasheet gives IEC 61508 failure rates in FIT and refers to an Exida report that can be downloaded from the manufacturer's site.