MTL TP48-N 2-Wire Transmitter Surge Protector

Description

Where the TP48-N goes: straight into the transmitter

Instead of mounting a protector in a junction box and hoping the surge stays on the cable, the MTL TP48-N screws into a spare conduit entry on the transmitter housing itself. Its 1/2 inch NPT thread is one of the three entry threads offered across the range. Three flying leads connect to the loop terminals (+ve and -ve) and the internal earth stud, so protection sits right at the instrument electronics.

TP48-N specification sheet

Model TP48-N (non-certified, 1/2 inch NPT, 2-wire)
Certified equivalent TP48-N-NDI
Leads 3 flying leads: line 1, line 2, earth; 250 mm minimum, 1.0 mm2 (18 AWG)
Working voltage 35 V dc maximum
Rated voltage MCOV 58 V
Leakage current less than 10 microamps at working voltage
Maximum surge current 20 kA (8/20 microseconds)
Nominal discharge current 3 kA
Lightning impulse current 2.5 kA (10/350 microseconds)
Voltage protection level at 1 kV per microsecond below 76 V
Bandwidth 1 MHz
Capacitance 100 pF
Casing 316 stainless steel, IP66
Weight 175 g
Ambient temperature -40 to +85 degrees C (specification); -40 to +60 degrees C (ordering table)
Hazardous-area class (certified types) Ex ia IIC T4; temperature class up to T6 for the 2-wire version

How the TP48 protects: common-mode conversion

The manufacturer describes the mechanism as a conversion of surge energy into a common-mode voltage. Any series-mode or common-mode transient is clamped, and the transmitter electronics are momentarily lifted to a higher voltage together with both lines before floating back down to normal, so no damaging voltage appears between the lines or between the lines and the casing. The earth connection is made to the transmitter casing, so no separate ground stake is needed at the instrument.

The protection network comprises high-power solid-state electronics plus a gas-filled discharge tube able to divert 20 kA impulses.

TP48-N versus TP48-3-N, TP48-4-N and the other threads

TP48 devices are named by wire count and thread: no number means 2-wire, 3 means three wires protecting +ve, -ve and signal, and 4 means four wires covering +ve, -ve, signal +ve and signal -ve. N is 1/2 inch NPT, I is 20 mm ISO and G is G 1/2 BSP. So the TP48-N is the 2-wire, NPT, non-certified base model. Adding the suffix NDI selects the certified version of the same hardware.

Choose by checking the transmitter’s conduit thread and the number of wires its terminal block uses. A two-wire loop-powered transmitter needs the TP48-N, a mains-powered flowmeter with a separate output may need the 3- or 4-wire version.

Typical TP48-N uses in Oman and the GCC

Level and pressure transmitters on above-ground storage tanks, flare knock-out drums, pipeline pig launchers and pump skids are exposed to lightning on open terrain. Desert plants have tall structures and dry soil with high earth resistance, which makes induced surges on field cables more severe. The TP48-N can be fitted retrospectively to such instruments without changing wiring or conduit, because it takes up an unused entry.

It is also used on desalination plants and power station yards where transmitters sit on long cable runs to the control building.

Installation procedure for TP48-N

Isolate the loop, remove the plug from a spare entry, screw in the TP48-N, and wrap or seal the thread as required. Terminate the leads in the transmitter terminal block, with line 1 and line 2 on the loop terminals and the green-yellow earth lead on the internal earth stud. The flying leads are at least 250 mm long and 1.0 mm2, so allow slack inside the housing and keep them away from sharp edges.

For hazardous-area installations use only the certified NDI version and keep the certificate with the loop file. Check the transmitter’s own approval allows the added device.

Inspection and spares for TP48-N

There is nothing to adjust. Inspect the thread seal and the lead insulation during routine instrument rounds, and replace after a major strike. The datasheet states a ten-year warranty and provides failure rates according to IEC 61508 for the 2-wire device of 0 FIT safe detected, 23 FIT safe undetected, 12 FIT dangerous detected and 5 FIT dangerous undetected. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

What the TP48-N figures mean in practice

The 35 V working voltage is the maximum dc the device may see in service, so on a 24 V loop there is 11 V of margin. The rated voltage of 58 V is where clamping begins. Below 10 microamps of leakage at the working voltage means a 4 mA signal is not measurably disturbed. The protection level of below 76 V at 1 kV per microsecond is what a transmitter input sees when a fast transient arrives, and the 3 kA nominal discharge current is the repeated duty, while 20 kA is the single-shot capability.

Capacitance of 100 pF is negligible for a 4-20 mA loop and for HART signalling, so smart transmitters keep communicating normally. For fieldbus loops, the datasheet points to a different product, the TP32, which meets IEC 61158-2 for 31.25 kbit/s Foundation fieldbus, PROFIBUS-PA and WorldFIP, so do not use the TP48 on a fieldbus segment.

The ordering table is simple: TP48-N, TP48-I and TP48-G are the non-certified 2-wire types in 1/2 inch NPT, 20 mm ISO and G 1/2 BSP threads, and each has an -NDI suffix for the certified equivalent. Specify the thread and certification together on the purchase request so that the right variant is delivered.

Documents and quotation

Download the TP48 datasheet for the dimensional drawing and approvals schedule. Send an RFQ with TP48-N, the quantity and the delivery location in Oman or the GCC, and state whether the certified NDI version is required.

Other Models in the MTL TP48 Surge Range

Seven Star LLC supplies models from the MTL TP48 Surge range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
MTL TP48-4-G 4-Wire Transmitter Surge ProtectorIsolator & BarrierView details
MTL TP48-N 2-Wire Transmitter Surge ProtectorIsolator & BarrierYou are viewing this model
Datasheets & Documents
  • PDF Datasheet MTL TP48-N 2-Wire Transmitter Surge Protector Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

MTL is a British maker of intrinsic safety interfaces, surge protection and hazardous-area equipment, founded in 1971 in Luton as Measurement Technology Ltd, a spin-off from Kent Instrumentation. In 2008 Cooper Industries bought MTL Instruments for £144 million and placed it in its Crouse-Hinds division; Eaton acquired Cooper in 2012. MTL is now part of Eaton's Crouse-Hinds business, alongside the MEDC signalling range.

Seven Star LLC lists MTL isolators, a fieldbus barrier and the configuration tools for them, and supplies MTL (Eaton) barriers and spare modules to sites in Oman as an independent supplier.

MTL (Eaton) company profile

Founded 1971, Luton, England, as Measurement Technology Ltd
Origin Spin-off from Kent Instrumentation
Headquarters Luton, England
Ownership Eaton (Crouse-Hinds), via Cooper Industries from 2008
Product families MTL5500 and MTL4500 isolators, MTL7700 zener barriers, 9300 fieldbus barriers, surge protection devices, process junction boxes, PCS45 configuration software; MEDC beacons, sounders and call points

Milestones

  • 1971: Measurement Technology Ltd is founded in Luton.
  • 2007: MTL acquires ELPRO Technologies, RTK Instruments and Ocean Technical Systems.
  • 2008: Cooper Industries acquires MTL Instruments for £144 million.
  • 2012: Eaton acquires Cooper Industries.

MTL product families listed here

Most of the listed items are DIN-rail galvanic isolators. The MTL5541 repeater power supply and the MTL5576-THC temperature converter belong to the MTL5500 range, and the MTL 5043 repeater power supply comes from the earlier MTL5000 range that many plants still run. The MTL 9370-FB2 is a fieldbus barrier for intrinsically safe FOUNDATION fieldbus spurs. PCS45 software with the PCL45USB link is the configurator for MTL converter modules. For the listed part CPM08-BN, please send a label photo so the number can be matched to the manufacturer's records. Newer labels show Eaton MTL, older ones Measurement Technology Ltd, and the module numbers are the same. The MTL 9608 is a fieldbus junction box with eight spur outlets plus a trunk-in connection, listed under the Crouse-Hinds series part number FCS-9608.

Where MTL barriers and isolators are used

These interfaces sit in marshalling cabinets wherever instruments are located in Zone 0, 1 or 2 areas: gas plants, refineries, offshore platforms, tank farms and chemical units across the GCC. They power 2-wire transmitters, pass HART, convert thermocouple signals and drive solenoids or alarms while limiting energy to the field circuit.

MTL (Eaton) products we list

Family Examples
Isolator & Barrier Eaton MTL5541 Repeater Power Supply, MTL 5043, MTL 9370-FB2 Intrinsically Safe Fieldbus…, MTL CPM08-BN, MTL5576-THC Temperature Isolator Module
Automation Accessories MTL 9608 Process Junction Box
Automation Software MTL PCS45 Configuration Software and PCL…

Ordering MTL modules: what we need

Send the full module number including every suffix, for example MTL5576-THC and not just MTL5576, and the quantity. Tell us if the module mounts on DIN rail or on a backplane, because MTL5500 and MTL4500 parts are not interchangeable. For a fieldbus barrier give the number of spurs and the enclosure reference. A photo of the side label, which shows the certificate numbers, helps when the certificate for your project file must match.

Facts checked against the Eaton MTL company history and Drives & Controls coverage of the 2008 Cooper offer, October 2026.

FAQ

Questions about the MTL TP48-N 2-Wire Transmitter Surge Protector

Answers from our engineering team on installation, compatibility and integration.

01What does the TP48-N protect?
2-wire field-mounted process transmitters. It is wired in parallel with the loop and has three flying leads: line 1, line 2 and earth.
02What thread does the TP48-N have?
1/2 inch NPT. The datasheet lists the -I version for 20 mm ISO (M20 x 1.5) and the -G version for G 1/2 inch (BSP).
03Is the TP48-N certified for hazardous areas?
The part number TP48-N is the non-certified device. The certified equivalent is TP48-N-NDI, which carries intrinsically safe and flameproof approvals.
04Does the TP48-N add resistance to the loop?
No. The parallel connection means no resistance is introduced into the loop, and it passes ac or dc signals up to 1 MHz bandwidth without attenuation.
05What surge can it divert?
A maximum of 20 kA peak at 8/20 microseconds, using solid-state electronics and a gas-filled discharge tube, with a nominal discharge current of 3 kA.