Brand: MTL (Eaton)
MTL SD07R3 Low-Voltage 3-Terminal Surge Protector
Description
SD07R3 for low-energy three-wire sensors
Pressure transducers that run from a few volts and have three wires are delicate electronics. A heavy-duty protector that leaks several milliamps would corrupt their signal. The MTL SD07R3 is the low-voltage, high-bandwidth, three-terminal member of the SD range: 7 V dc nominal, 5 V ac, 400 mA, 2.7 ohm per line, and a 50 MHz bandwidth. Its voltage protection level of under 12 V at 1 kV per microsecond keeps a transducer far below its damage threshold.
SD07R3 data table
| Model | SD07R3 |
|---|---|
| Terminals | 3 |
| Nominal voltage | 7 V dc / 5 V ac |
| Nominal current | 400 mA |
| Series resistance | 2.7 ohm per line |
| Maximum leakage current | 500 microamps |
| Rated voltage (MCOV) | 7.7 V |
| Voltage protection level at 1 kV per microsecond | below 12 V |
| Residual voltage at isn | 30 V |
| Bandwidth | 50 MHz |
| Maximum discharge current | 20 kA (8/20 microseconds) |
| Lightning impulse current | 2.8 kA (10/350 microseconds) |
| ATEX | Ex ia IIC T4 Ga; Li = 0; Ii = 260 mA for Ui up to 60 V |
| Temperature | -40 to +80 degrees C |
| Mounting | 35 mm DIN rail, 7.5 or 15 mm |
| Weight | about 70 g |
Comparing SD07R3 with SD07, SD07X and SD07R
At 7 V all four share the same working voltage but differ in other respects. The SD07 has 4.2 ohm series resistance and the fuse-disconnect feature; the SD07X has 2.2 ohm and a 25 kHz bandwidth; the SD07R is the two-terminal 50 MHz version, 2.7 ohm; the SD07R3 is that same circuit with a third terminal. The leakage figure of 500 microamps applies to all 7 V models at their working voltage, so the SD07R3 is for circuits where such leakage is tolerable, typically low-impedance bridges and sensors.
Choose it over the SD07R when three conductors need the same protection, and over the SD07 when high bandwidth matters more than the fuse-disconnect function.
Where buyers apply the SD07R3 in the Gulf
Pressure transducers on hydraulic skids, test benches at manufacturing sites, control cabinets at onshore plants and compressor instrumentation often work from low supplies. Because the SD07R3 is certified for intrinsically safe loops in Zones 0, 1 or 2, the same part works in classified areas and safe areas.
The datasheet’s applications table also steers RS422, RS423, RS485 and PROFIBUS DP users toward the SD07R, a close relative, so a plant that already stocks the SD07R family can maintain one range.
Fitting the SD07R3
Mount on the rail as close as possible to the transducer, with the transducer wired to the protected terminals. The rail earth should connect to the cabinet earth bar with a short, heavy conductor, since lightning-induced surges rely on a low-impedance path. Use ISP7000 insulating spacers where the rail must be isolated from a backplane, with ETL7000 earth terminals to restore a controlled earth.
Ensure the IS parameters are added into the loop: Li of zero makes the SD07R3 easy to include, because it contributes no inductance.
Care of SD07R3
Check labels, rail continuity and the earth link at each outage. After any lightning event near the site, swap suspect devices, remembering that a surge-damaged hybrid may still appear normal on the bench. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.
Worked reading of the SD07R3 figures
A 5 V bridge-type pressure transducer drawing a few milliamps sees negligible drop through 2.7 ohm: at 5 mA the loss is 13.5 millivolts per line, which a ratiometric amplifier typically tolerates because it measures the supply at the sensor. The 7.7 V rated voltage leaves a margin of 2.7 V above a 5 V supply, and the protection level below 12 V means the transducer experiences no more than that during fast transients.
The leakage figure of 500 microamps is the one to check. At a 7 V working voltage the module may leak up to that value, but it is the maximum figure at the working voltage. If the sensor has an input impedance of several kilohms the effect is small, while a precision high-impedance amplifier may prefer a higher-voltage module with lower leakage, such as the SD16R3 at 5 microamps.
Because the datasheet applies the same Ex ia IIC certificate to all R3 types, replacing an SD07R3 with an SD16R3 does not change the IS paperwork structure, only the entity calculation.
Accessories and enclosure planning for SD07R3
The SD range has its own accessory list. ISP7000 insulating spacers allow installation on a backplane without upsetting correct earthing practice, ETL7000 earth terminals take the rail earth, and TAG57 tagging strips with TGL57 labels, or BRI7000 identifiers on each unit, keep loops identifiable. Weatherproof DX070 enclosures hold up to 9 SD modules and DX170 enclosures up to 22, with mounting kit included. A tagged, enclosed group of SD07R3 units can therefore be dropped into a junction box beside the transducers.
For safety-instrumented applications the datasheet refers readers to the Safety Manual on the manufacturer’s website. Also confirm that the 50 mm clearance between safe and hazardous terminals is respected by mounting the SD units and any IS interface on separate rails.
Quote the module name exactly. When ordering, state the full module name SD07R3 rather than just SD07, since the two have different construction, bandwidth and certification. A packing slip that reads SD07R3 together with the quantity prevents the wrong two-terminal fuse-disconnect module from arriving.
Retain the order confirmation with the loop folder for future reference.
Documents and quotation
The SD range datasheet lists each module and the approvals. Send your RFQ with the part number SD07R3, quantity and delivery location in Oman or the GCC.
Other Models in the MTL SD Surge Range
Seven Star LLC supplies models from the MTL SD Surge range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| MTL SD07R3 Low-Voltage 3-Terminal Surge Protector | Isolator & Barrier | You are viewing this model |
| MTL SD32T3 Three-Terminal Surge Protection Device | Isolator & Barrier | View details |
| MTL SD275X 240 V AC High-Current Surge Protector | Isolator & Barrier | View details |
| MTL SDPSTN Telephone Line Surge Protector | Isolator & Barrier | View details |
| MTL SDRTD 3-Wire RTD Surge Protection Device | Isolator & Barrier | View details |
Datasheets & Documents
- Datasheet MTL SD07R3 Low-Voltage 3-Terminal Surge Protector Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
MTL is a British maker of intrinsic safety interfaces, surge protection and hazardous-area equipment, founded in 1971 in Luton as Measurement Technology Ltd, a spin-off from Kent Instrumentation. In 2008 Cooper Industries bought MTL Instruments for £144 million and placed it in its Crouse-Hinds division; Eaton acquired Cooper in 2012. MTL is now part of Eaton's Crouse-Hinds business, alongside the MEDC signalling range.
Seven Star LLC lists MTL isolators, a fieldbus barrier and the configuration tools for them, and supplies MTL (Eaton) barriers and spare modules to sites in Oman as an independent supplier.
MTL (Eaton) company profile
| Founded | 1971, Luton, England, as Measurement Technology Ltd |
|---|---|
| Origin | Spin-off from Kent Instrumentation |
| Headquarters | Luton, England |
| Ownership | Eaton (Crouse-Hinds), via Cooper Industries from 2008 |
| Product families | MTL5500 and MTL4500 isolators, MTL7700 zener barriers, 9300 fieldbus barriers, surge protection devices, process junction boxes, PCS45 configuration software; MEDC beacons, sounders and call points |
Milestones
- 1971: Measurement Technology Ltd is founded in Luton.
- 2007: MTL acquires ELPRO Technologies, RTK Instruments and Ocean Technical Systems.
- 2008: Cooper Industries acquires MTL Instruments for £144 million.
- 2012: Eaton acquires Cooper Industries.
MTL product families listed here
Most of the listed items are DIN-rail galvanic isolators. The MTL5541 repeater power supply and the MTL5576-THC temperature converter belong to the MTL5500 range, and the MTL 5043 repeater power supply comes from the earlier MTL5000 range that many plants still run. The MTL 9370-FB2 is a fieldbus barrier for intrinsically safe FOUNDATION fieldbus spurs. PCS45 software with the PCL45USB link is the configurator for MTL converter modules. For the listed part CPM08-BN, please send a label photo so the number can be matched to the manufacturer's records. Newer labels show Eaton MTL, older ones Measurement Technology Ltd, and the module numbers are the same. The MTL 9608 is a fieldbus junction box with eight spur outlets plus a trunk-in connection, listed under the Crouse-Hinds series part number FCS-9608.
Where MTL barriers and isolators are used
These interfaces sit in marshalling cabinets wherever instruments are located in Zone 0, 1 or 2 areas: gas plants, refineries, offshore platforms, tank farms and chemical units across the GCC. They power 2-wire transmitters, pass HART, convert thermocouple signals and drive solenoids or alarms while limiting energy to the field circuit.
MTL (Eaton) products we list
Ordering MTL modules: what we need
Send the full module number including every suffix, for example MTL5576-THC and not just MTL5576, and the quantity. Tell us if the module mounts on DIN rail or on a backplane, because MTL5500 and MTL4500 parts are not interchangeable. For a fieldbus barrier give the number of spurs and the enclosure reference. A photo of the side label, which shows the certificate numbers, helps when the certificate for your project file must match.
Facts checked against the Eaton MTL company history and Drives & Controls coverage of the 2008 Cooper offer, October 2026.
Browse MTL (Eaton) products by category: Isolator & Barrier, Automation Software.
FAQ
Questions about the MTL SD07R3 Low-Voltage 3-Terminal Surge Protector
Answers from our engineering team on installation, compatibility and integration.
01Which circuits is the SD07R3 recommended for?
The datasheet recommends it for 3-wire pressure transducers on low-power circuits, with a nominal voltage of 7 V dc.
02What is its bandwidth?
50 MHz, which is typical of the R and R3 high-bandwidth types, compared with 25 kHz for the standard SD07.
03What series resistance does it add?
2.7 ohm per line, with a maximum leakage current of 500 microamps at the working voltage.
04What clamping figures does it give?
Rated voltage MCOV 7.7 V, protection level below 12 V at 1 kV per microsecond and a residual voltage of 30 V at nominal discharge current.
05Is the SD07R3 intrinsically safe certified?
Yes, ATEX Ex ia IIC T4 Ga with Li of zero and Ii of 260 mA for Ui up to 60 V, which also applies to the other R, R3 and RTD types.


















Reviews