- Automation & ControlView all 2,895 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- Safety Switches & Guard Locking
- Motor Soft Starters
- CCTV & Security
- Encoders
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: MTL (Eaton)
MTL MTL5525 Low-Power Solenoid/Alarm Driver, SIL3, IIC
Description
MTL5525 overview
The MTL5525 lets an on/off device in the hazardous area be controlled by a volt-free contact or logic signal in the safe area. It is meant for low-power loads such as solenoids, alarms and LEDs that are certified as intrinsically safe or classed as non-energy-storing simple apparatus.
The MTL5525 is part of the MTL5500 range of DIN-rail mounted intrinsically safe isolators from MTL, a brand of Eaton. As a single-channel module, it is a switch-operated solenoid/alarm driver, low power that clips onto a standard 35 mm rail, with plug-in terminals for the hazardous-area and safe-area wiring. Because many MTL5500 numbers look alike, this page repeats the facts taken from the manufacturer datasheet so that engineers can confirm that the MTL5525 matches their loop before sending an enquiry.
Key features of the MTL MTL5525
- Control from a switch contact, open-collector transistor or logic signal
- Hazardous-area output of at least 7.8 V at 48 mA, up to 24 V from 300 ohm
- Current limit of 48 mA minimum
- SIL3 capable for a single device (HFT=0) for the MTL5525
- Supply current of 100 mA at 24 V
- Fully galvanic isolation: 250 V rms between safe-area and hazardous-area terminals, and 250 V rms between safe-area circuits and the power supply
- Powered from 20 to 35 V dc, with an optional Powerbus system to share the supply across a row of modules
MTL5525 technical specifications
| Parameter | Value |
|---|---|
| Model | MTL5525 |
| Range | MTL5500 DIN-rail isolators |
| Supply voltage | 20 to 35 V dc |
| Isolation | 250 V rms tested at 1500 V rms minimum between safe and hazardous terminals; 250 V rms between safe-area circuits and supply |
| Terminals | accept conductors up to 2.5 mm squared, stranded or single-core |
| Mounting | 35 mm T-section DIN rail (7.5 or 15 mm) to EN 50022 |
| Ambient temperature | minus 20 to plus 60 C operating; minus 40 to plus 80 C storage |
| Humidity | 5 to 95 percent relative humidity |
| Weight | approximately 150 g |
| EMC | to EN 61326 and NE21 |
| Location of module | safe area |
| Number of channels | One |
| Minimum output voltage | 7.8 V at 48 mA |
| Maximum output voltage | 24 V from 300 ohm |
| Maximum off-state output voltage | 4 V from 300 ohm |
| Current limit | 48 mA minimum |
| Control input | 0 = switch closed, transistor on or below 1.4 V; 1 = switch open, transistor off or above 4.5 V |
| Output ripple | less than 0.5 percent of maximum output, peak to peak |
| Response time | output within 10 percent of final value within 100 ms |
| Supply current | 100 mA at 24 V dc |
| Power dissipation | 1.3 W with typical solenoid, output on; 1.9 W worst case |
| Safety description | Uo 25 V, Io 83.3 mA, Po 0.52 W, Um 253 V rms or dc |
| Functional safety | SIL3 capable single device (HFT=0); SIL3 capable HFT=1 |
The module must be installed in the safe area, while the field device it serves may be located as the datasheet allows: Zone 0, IIC, T4 to T6 hazardous area where the connected device is suitably certified, or a Division 1, Group A hazardous location. Always read the current approval certificate on the manufacturer website for entity parameters, since the datasheet states that safety approvals can be revised.
Typical applications of the MTL5525 in Oman and the GCC
The manufacturer describes the MTL5525 as a switch-operated low-power solenoid and alarm driver. In Gulf plants this duty usually means low-power IS solenoids, pilot valves, beacons and LED indication in classified areas.
- Oil and gas: wellsites, gathering stations, gas plants and pipeline terminals
- Utilities and power: turbine skids, fuel gas systems and boiler auxiliaries
- Water and desalination: chemical dosing, treatment and pumping areas with flammable vapour risk
- Petrochemical and manufacturing: solvent storage, loading bays and process units
Many older Gulf installations carry MTL5000 or MTL4000 series isolators. The datasheet states that the MTL5500 can replace MTL5000 units, so the MTL5525 is often requested as a like-for-like spare during shutdowns.
Selection and compatibility notes for the MTL5525
The second override input described in the datasheet belongs to the MTL4525 of the backplane family, so do not plan an override switch on the MTL5525. For loads that need more drive current, such as larger solenoids, compare the MTL5523 with its 13.6 V at 48 mA output.
Check the certificate of the field device against the safety description of the MTL5525: the field device must tolerate the module output parameters, and the cable capacitance and inductance must stay within the permitted limits. The maximum safe-area voltage Um for the range is 253 V rms or dc.
Installation and commissioning of the MTL5525
Clip the module onto the DIN rail and fit the supplied connectors. The hazardous-area plugs are the blue-labelled terminals, and the safe-area plugs and the power connector are separate parts. When crimp ferrules are used, the manufacturer recommends a metal tube length of 12 mm and a wire trim length of 14 mm. Keep intrinsically safe wiring segregated from other wiring as required by the installation code, and record the loop tag on the optional TH5000 tag holder. Check the supply is within 20 to 35 V dc before energising, and verify the loop with the module fitted before connecting the field cable.
Maintenance and spare parts
An isolator has no user-serviceable parts. Routine checks are limited to terminal tightness, LED status, supply voltage and a periodic loop test according to the plant procedure. A failed module should be replaced as a whole, and the plug-in connectors can be moved to the replacement. Related accessories listed in the datasheet include the HAZ and SAF connector plugs, the PWR5000 power connector, the PB-8T, PB-16T, PB-24T and PB-32T Powerbus kits and the THR2 rail.
Related products and ordering notes for the MTL5525
Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. The MTL5500 range is the DIN-rail version of the family and the MTL4500 range is the backplane-mounted version, so quote the exact number MTL5525 when ordering, and mention any suffix, because a letter such as S, A, B, C, D or Y changes the function.
MTL5525 FAQ summary
Typical questions concern the function, the safety description and the supply of the MTL5525. It is a switch-operated low-power solenoid and alarm driver, powered from 20 to 35 V dc, with the figures listed in the table above.
Documents and quotation
The range datasheet for the MTL5525 is attached to this page. To request a quotation, send an RFQ with the part number MTL5525, the quantity and your delivery location in Oman or the GCC, and we will reply with availability and lead time.
Other Models in the MTL5500 Range
Seven Star LLC supplies models from the MTL5500 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
Datasheets & Documents
- Datasheet MTL MTL5525 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
MTL is a British maker of intrinsic safety interfaces, surge protection and hazardous-area equipment, founded in 1971 in Luton as Measurement Technology Ltd, a spin-off from Kent Instrumentation. In 2008 Cooper Industries bought MTL Instruments for £144 million and placed it in its Crouse-Hinds division; Eaton acquired Cooper in 2012. MTL is now part of Eaton's Crouse-Hinds business, alongside the MEDC signalling range.
Seven Star LLC lists MTL isolators, a fieldbus barrier and the configuration tools for them, and supplies MTL (Eaton) barriers and spare modules to sites in Oman as an independent supplier.
MTL (Eaton) company profile
| Founded | 1971, Luton, England, as Measurement Technology Ltd |
|---|---|
| Origin | Spin-off from Kent Instrumentation |
| Headquarters | Luton, England |
| Ownership | Eaton (Crouse-Hinds), via Cooper Industries from 2008 |
| Product families | MTL5500 and MTL4500 isolators, MTL7700 zener barriers, 9300 fieldbus barriers, surge protection devices, process junction boxes, PCS45 configuration software; MEDC beacons, sounders and call points |
Milestones
- 1971: Measurement Technology Ltd is founded in Luton.
- 2007: MTL acquires ELPRO Technologies, RTK Instruments and Ocean Technical Systems.
- 2008: Cooper Industries acquires MTL Instruments for £144 million.
- 2012: Eaton acquires Cooper Industries.
MTL product families listed here
Most of the listed items are DIN-rail galvanic isolators. The MTL5541 repeater power supply and the MTL5576-THC temperature converter belong to the MTL5500 range, and the MTL 5043 repeater power supply comes from the earlier MTL5000 range that many plants still run. The MTL 9370-FB2 is a fieldbus barrier for intrinsically safe FOUNDATION fieldbus spurs. PCS45 software with the PCL45USB link is the configurator for MTL converter modules. For the listed part CPM08-BN, please send a label photo so the number can be matched to the manufacturer's records. Newer labels show Eaton MTL, older ones Measurement Technology Ltd, and the module numbers are the same. The MTL 9608 is a fieldbus junction box with eight spur outlets plus a trunk-in connection, listed under the Crouse-Hinds series part number FCS-9608.
Where MTL barriers and isolators are used
These interfaces sit in marshalling cabinets wherever instruments are located in Zone 0, 1 or 2 areas: gas plants, refineries, offshore platforms, tank farms and chemical units across the GCC. They power 2-wire transmitters, pass HART, convert thermocouple signals and drive solenoids or alarms while limiting energy to the field circuit.
MTL (Eaton) products we list
Ordering MTL modules: what we need
Send the full module number including every suffix, for example MTL5576-THC and not just MTL5576, and the quantity. Tell us if the module mounts on DIN rail or on a backplane, because MTL5500 and MTL4500 parts are not interchangeable. For a fieldbus barrier give the number of spurs and the enclosure reference. A photo of the side label, which shows the certificate numbers, helps when the certificate for your project file must match.
Facts checked against the Eaton MTL company history and Drives & Controls coverage of the 2008 Cooper offer, October 2026.
Browse MTL (Eaton) products by category: Isolator & Barrier, Automation Software.
FAQ
Questions about the MTL MTL5525 Low-Power Solenoid/Alarm Driver, SIL3,
Answers from our engineering team on installation, compatibility and integration.
01What is the MTL5525 used for?
The datasheet describes the MTL5525 as a switch-operated low-power solenoid and alarm driver.
02What supply does the MTL5525 need?
It is powered from 20 to 35 V dc and is installed in the safe area, with 250 V rms isolation between the safe-area circuits and the supply.
03How is the MTL5525 mounted?
It clips onto a 35 mm T-section DIN rail and uses plug-in terminals that accept conductors up to 2.5 mm squared.
04Can the MTL5525 replace an older MTL5000 module?
The manufacturer states that the MTL5500 range can replace MTL5000 units, but check the function, suffix and certificate before ordering.
05How do I request a quotation for the MTL5525?
Send an RFQ with the part number MTL5525, quantity and delivery location in Oman or the GCC, and we will reply with availability and lead time.


















Reviews
There are no reviews yet.