KFU8-CRG2-Ex1.D: universal-supply transmitter barrier with relays

A plant that has only 24 V DC in one cabinet and 230 V AC in the next would need two spare types for the same function. The Pepperl+Fuchs KFU8-CRG2-Ex1.D removes that headache with a universal supply of 20 to 90 V DC or 48 to 253 V AC. The module is an intrinsically safe transmitter supply: it energises a 2-wire or 3-wire transmitter in a hazardous area, isolates the signal and outputs a scaled current plus two alarm relays.

Its feature set is that of the CRG2 family, including a display in physical units, linearisation with up to 20 points, adjustable delays and PACTware configuration.

Main features

  • Supply on terminals 23 and 24; 2 W / 3 VA dissipation, 2.2 W / 4 VA consumption
  • Ex ia input on terminals 1, 2, 3 with Uo 25.8 V, Io 93 mA and Po 0.603 W
  • Output III: 0 to 20 mA or 4 to 20 mA, up to 650 ohm; relay I on 10, 11, 12 and relay II on 16, 17, 18
  • Fault signal downscale 3.6 mA or less, upscale 21.5 mA or more (NAMUR NE43)
  • Reinforced insulation between output III and supply, interface and supply

KFU8-CRG2-Ex1.D specification

Parameter Value
Supply 20 to 90 V DC or 48 to 253 V AC
Input signal 0/4 to 20 mA; available voltage above 15 V at 20 mA
Open-circuit voltage / short-circuit current 24 V / 33 mA
Line fault limits breakage below 0.2 mA; short circuit above 22 mA
Accuracy input under 30 microamps; output under 20 microamps
Delay range 0 to 250 s
Relay contacts 250 V AC / 2 A / cos phi 0.7 or better; 40 V DC / 2 A
Reaction time under 650 ms at a step of 0 to 20 mA (90 percent)
ATEX certificate TUV 01 ATEX 1701, marking [Ex ia Ga] IIC
Second entity set Uo 25.8 V, Io 112 mA, Po 720 mW
Dimensions, mass 40 x 119 x 115 mm, housing C2, 300 g
Ambient -20 to 60 degrees C

Why a universal supply helps

Brownfield sites in the Gulf frequently mix control voltages: 24 V DC for new skids, 110 V DC for switchgear batteries, 230 V AC for lighting panels. A single module covering 20 to 90 V DC and 48 to 253 V AC reduces spare-parts variety to one article, and it can be moved between panels without checking the label. No Power Rail is used; the collective error output of the DIN-rail system is not available, and faults are indicated by LEDs.

Differences between KFU8-CRG2-Ex1.D and the 24 V DC versions

The rail-powered KFD2-CRG2-Ex1.D takes 20 to 30 V DC and reports faults on the Power Rail, while KFU8-CRG2-Ex1.D has a wide-range supply, uses reinforced insulation to the supply and signals faults only by LED. The non-Ex KFD2-CRG2-1.D lacks the hazardous-area certificate and its Uo, Io, Po values altogether. Mechanical size is identical at 40 mm width.

Entity parameters and wiring

Terminals 1, 2 and 3 carry the intrinsically safe loop. Combine the transmitter and cable capacitance and inductance with the Uo, Io and Po values and compare with the IIC limits on the certificate. A second parameter set with 5 V, 0.3 mA and 0.3 mW applies to the programming interface circuit. Observe the mains safety instructions for the supply terminals.

Commissioning

Configure by keypad or PACTware with the K-ADP-USB adapter: input range, display unit, output range, relay set points, hysteresis, delay and fault direction. Verify with a loop calibrator.

Upkeep

Annual relay and output check; re-tighten terminals after heat cycles; keep a PACTware backup of each configuration.

When to select this variant

Choose it where the available supply is not 24 V DC bus or where one spare must cover several supply types; select the rail version where collective error reporting is required.

Safety-related use and documentation

The datasheet states that relay contacts and the current output can be integrated in safety-relevant circuits and gives a capability of up to SIL 2 under IEC/EN 61508 and IEC/EN 61511. As with any such statement, the claim depends on the complete loop and the safety manual, which provides failure rates and proof-test guidance. Record the unit’s serial number, the configuration file and the date of the last functional test in the safety dossier. For plants in Oman operating to IEC 61511, this documentation trail is what an auditor will inspect first. Include the supply type in the record, because replacing the module with a different supply variant may change the insulation concept.

Questions buyers ask about KFU8-CRG2-Ex1.D

What supply range does KFU8-CRG2-Ex1.D accept? It accepts 20 to 90 V DC or 48 to 253 V AC on terminals 23 and 24.

What are the intrinsically safe values of KFU8-CRG2-Ex1.D? One parameter set lists Uo 25.8 V, Io 93 mA and Po 0.603 W, under certificate TUV 01 ATEX 1701.

How many relays does KFU8-CRG2-Ex1.D have? It has two relay outputs on terminals 10, 11, 12 and 16, 17, 18, rated 250 V AC at 2 A or 40 V DC at 2 A.

Does KFU8-CRG2-Ex1.D support linearisation? Yes, a linearisation function with a maximum of 20 points is listed.

Can KFU8-CRG2-Ex1.D be configured with a PC? Yes, it is configured with the keypad or with the PACTware configuration software through the programming socket.

Documents and quotation

The manufacturer datasheet for KFU8-CRG2-Ex1.D accompanies this listing as a PDF so your engineers can verify terminals, ratings and approvals before purchase. Give the supply voltage available at your cabinet. To request a quotation, send the RFQ with the exact part number KFU8-CRG2-Ex1.D, the quantity, the delivery location in Oman or the GCC and any project reference. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Spares and Lifecycle Considerations

For critical service, many plants hold one Pepperl+Fuchs KFU8-CRG2-Ex1.D as an operational spare rather than waiting for a failure. When you plan spares, look at how many identical isolator & barrier units are installed, how long a replacement would take to arrive, and the cost of an unplanned stop. Store spare units in their original packaging in a dry, temperature-controlled area and record the part number and serial number in your maintenance system. We can quote single units or a small spares package and confirm the lead time for each item in writing.

Datasheets & Documents
  • PDF Datasheet Pepperl+Fuchs KFU8-CRG2-Ex1.D Transmitter Barrier Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.

Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.

Pepperl+Fuchs company profile

Founded 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs
Headquarters Mannheim, Germany
Ownership Privately owned (Pepperl+Fuchs SE)
Origins Radio repair workshop that began making replacement transformers
Product families Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures

Milestones

  • 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
  • 1958: The first proximity switch is developed (some company sources say 1959).

Pepperl+Fuchs product families on this page

On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.

Where Pepperl+Fuchs equipment is used

Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.

Pepperl+Fuchs products we list

Family Examples
Isolator & Barrier HiD2030 SMART Transmitter Power Supply w…, KFD2-SR2-Ex2.W K-System Isolated Switch…, KFD2-UT2-Ex2 Universal Temperature Conve…
Industrial Computers Tab-Ex 05 DZ1 WWAN Hazardous Area Tablet, Smart-Ex® 03 DZ2 smartphone for Zone 2/2…
Inductive Proximity Sensors NJ2-12GK-SN NAMUR Inductive Sensor
Power Modules PS1000-A6-24.20 Power Supply 24 VDC 20 A
Photoelectric Sensors R101 Retro-Reflective Photoelectric Sensor
Laser Distance, LiDAR & Radar Sensors R2000 2-D LiDAR Laser Scanner

Ordering Pepperl+Fuchs parts: what we need

Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.

Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.

FAQ

Questions about the Pepperl+Fuchs KFU8-CRG2-Ex1.D Transmitter Barrier

Answers from our engineering team on installation, compatibility and integration.

01What supply range does KFU8-CRG2-Ex1.D accept?
It accepts 20 to 90 V DC or 48 to 253 V AC on terminals 23 and 24.
02What are the intrinsically safe values of KFU8-CRG2-Ex1.D?
One parameter set lists Uo 25.8 V, Io 93 mA and Po 0.603 W, under certificate TUV 01 ATEX 1701.
03How many relays does KFU8-CRG2-Ex1.D have?
It has two relay outputs on terminals 10, 11, 12 and 16, 17, 18, rated 250 V AC at 2 A or 40 V DC at 2 A.
04Does KFU8-CRG2-Ex1.D support linearisation?
Yes, a linearisation function with a maximum of 20 points is listed.
05Can KFU8-CRG2-Ex1.D be configured with a PC?
Yes, it is configured with the keypad or with the PACTware configuration software through the programming socket.