Brand:

GESTRA BK 46 Alloy Steel Bimetallic Steam Trap PN 40

Description

BK 46: the alloy-steel step up from the BK 45

When plant steam moves beyond what a plain carbon steel trap is designed for, the GESTRA BK 46 is the member of the BK 4x group built for it. It keeps the same PN 40 flange pattern and DN 15, 20 and 25 sizes as the BK 45, but its body and cover are 1.5415 (A 182 F1) alloy steel, and the datasheet gives it a higher admissible differential pressure and a higher temperature ceiling.

Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. The summary below is based on the manufacturer’s datasheet, so you can compare the BK 46 with your own requirements before requesting a quotation.

BK 46 data summary

Parameter Value
Type GESTRA BK 46, bimetallic steam trap
Sizes DN 15, 20, 25 (½, ¾, 1 inch)
Body and cover 1.5415 / A 182 F1
PN 40 flange pressure 40.0 barg at 20 °C; 39.0 at 250 °C; 34.2 at 300 °C; 32.3 at 350 °C; 29.9 at 400 °C; 27.6 at 450 °C
Class 150 20.0 barg at -10/50 °C; 14.0 at 200 °C; 10.2 at 300 °C; 4.7 at 450 °C
Class 300 and weld/threaded ends 51.7 barg at -10/50 °C; 44.2 at 200 °C; 35.0 at 300 °C; 29.8 at 450 °C
Differential pressure limit 32 bar
Regulator Stainless steel Duo (bimetallic) plates, Thermovit
Spare regulator with gasket Stock code 375464
Strainer set 375113
Flange length 150, 150, 160 mm; 3.7 to 4.8 kg

How BK 46 differs from BK 45 and BK 45-U

There are three numeric differences to note. First, differential pressure: 32 bar for the BK 46 against 22 bar for the BK 45. Second, temperature: the PN 40 table runs to 450 °C at 27.6 barg, where the BK 45 stops at 420 °C and 17.1 barg. Third, the spare regulator code is 375464 for the BK 46, so a regulator from a BK 45 (375234) is not the right spare. The ratings are based on EN 1759-1 for the BK 46, against EN 1092-1 for the BK 45, because the flanges are for the alloy material.

Plants where BK 46 fits

Higher-temperature steam appears in power stations, in cogeneration systems on gas fields and in refinery process units with heated superheater drains. In those places, the BK 46 suits drip legs after pressure-reducing stations and condensate drains from heaters where the pressure drop is large. For starts after shutdown, the trap opens fully for air and cold condensate and then closes close to saturation. Its design handles water hammer, which is common in start-up conditions in long headers in Oman’s hot climate where condensate forms after long idle periods.

Fitting BK 46

End connections are the same as for the BK 45: EN 1092-1 B1 PN 40 flanges, ASME B16.5 Class 150 and 300 flanges, G or NPT threads, socket-weld ends, and butt-weld ends through transition pieces. Because the alloy body and the flange pattern follow the pipe, weld procedures must suit 1.5415 where weld ends are specified. The trap has an internal strainer; keep 30 mm free over the cover.

In practice, the best time to choose the BK 46 is during design review of a steam network, because the heavier alloy body and the higher differential rating remove the need to use two traps in series or a pressure-reducing valve ahead of a drain. The datasheet makes no claim about specific plant types, so match the trap against the written conditions rather than against general experience. When the line is moved or the steam parameters are raised, re-check the PN 40 table before keeping an old trap in service, since the temperature falls off the allowable pressure curve from 39.0 barg at 250 °C to 27.6 barg at 450 °C.

Maintaining BK 46

Replace the Thermovit regulator and gasket as one set, and refit the strainer after cleaning. With cover screws M 10 x 25 in 1.7225, tighten evenly. For records, remember that the BK 46 uses an ASTM material described by the manufacturer as only similar to the EN grade, so keep EN documentation if you need certificates.

Dimensions and conditions of use for BK 46

The BK 46 shares the dimensional table of the BK 45 family. Flanged versions are 150 mm long for DN 15 and DN 20 and 160 mm long for DN 25, weighing 3.7, 4.3 and 4.8 kg. Threaded and socket-weld versions are 95 mm long at 2.2, 2.1 and 2.0 kg, and butt-weld versions are 200 mm long at 2.5 kg. Because the dimensions match the BK 45, an existing BK 45 position can be upgraded to the BK 46 without changing the pipe layout, provided the flange standard is the same.

The datasheet classes the equipment for fluids of group 2 under the Pressure Equipment Directive and notes that chemical and corrosive influences must be considered. Like the other traps in the family, the BK 46 has no ignition source of its own under ATEX. The operator must prevent excessive surface temperatures and static charge in hazardous zones, and must take possible leakage at threaded joints into account when dividing zones.

Selecting BK 46 against the alternatives

Use a BK 45 when the temperature is no higher than 420 °C and the differential pressure no higher than 22 bar. Choose the BK 46 if either value is exceeded. If the system is much higher in pressure, for example PN 63 to PN 160, the BK 37, BK 28 and BK 29 group applies instead.

Documents and quotation

The BK 46 datasheet is available on this page. To request a quotation, send an RFQ stating part number BK 46, quantity, flange or thread standard and operating data; we will reply for Oman and the GCC.

Documentation and Compliance

Industrial buyers often need more than the hardware. When you order the GESTRA BK 46, tell us which documents your project or quality team requires, such as certificates of origin, conformity declarations, calibration or test records, or hazardous-area certificates where the variant carries them. Mentioning these at the enquiry stage avoids delays at customs and at goods receipt on site. For tenders and project packages, we can also align the quotation with your line-item format so that GESTRA steam traps & steam specialties items can be checked against the bill of materials quickly.

Ordering Checklist for the GESTRA BK 46

Before you ask for a quotation for the GESTRA BK 46, check the full order code on the nameplate of the unit you are replacing, the supply voltage, and the process or signal ranges your system expects. If this is an upgrade rather than a like-for-like swap, tell us the existing make and model so that mounting, wiring and connection details can be checked against the steam traps & steam specialties already installed. For multi-unit orders, list the quantity per site and the delivery location in Oman or the wider GCC, so packing, paperwork and lead time can be confirmed in a single quotation.

Other Models in the BK 4x Range

Seven Star LLC supplies models from the BK 4x range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
GESTRA UBK 46 Steam Tracing Trap with Adjustable Discharge TemperatureSteam Traps & Steam SpecialtiesView details
GESTRA BK 46 Alloy Steel Bimetallic Steam Trap PN 40Steam Traps & Steam SpecialtiesYou are viewing this model
Datasheets & Documents
  • PDF Datasheet GESTRA BK 46 Alloy Steel Bimetallic Steam Trap PN 40 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

GESTRA is the German steam and condensate specialist behind the UNA ball float steam traps, the MPA blowdown valves and a long line of boiler level and conductivity controls. It was founded in Bremen in 1902 by Gustav F. Gerdts, and has been part of Spirax Sarco since 2017.

Seven Star LLC is an independent supplier in Muscat. We list GESTRA steam traps, blowdown valves and boiler control equipment, and supply GESTRA parts and spares to boiler houses and process plants in Oman and the GCC.

GESTRA company profile

Established 29 October 1902, Bremen, Germany, by Gustav Friedrich Gerdts; renamed Gustav F. Gerdts KG in 1907
Ownership history Became a stock corporation (GESTRA AG) in 1987, was taken over by Flowserve in 2002, and has been part of the Spirax Sarco group since 2017
Product families Steam traps, non-return and check valves, boiler blowdown valves, control valves, and boiler control electronics for level, conductivity and temperature
Applications Steam boilers, steam distribution and condensate return in process plants, power stations, hospitals, food and textile plants

Milestones

  • 1902: Gustav Friedrich Gerdts founds the company in Bremen on 29 October.
  • 1907: The company is renamed Gustav F. Gerdts KG.
  • 1987: It becomes a stock corporation, GESTRA AG.
  • 2002: Flowserve takes over GESTRA.
  • 2017: GESTRA becomes part of the Spirax Sarco group.

GESTRA products we list

Series Type What it does
UNA 45, UNA 16, UNA 38 Ball float steam traps Continuous condensate discharge from heat exchangers and process equipment; the UNA 38 is the high-pressure version (PN 100)
BK 45 Bimetallic steam trap Robust trap for steam main drainage and tracing, resistant to water hammer
MK 45, TK 23, SMK 22-81 Thermostatic steam traps Air venting and condensate discharge; the SMK 22-81 is the sanitary version for clean steam
MPA 46 Rapid-action blowdown valve Short, intermittent bottom blowdown that removes sludge from the boiler
NRS 1-54, NRR 2-50, NRR 2-60, NRGT 26-2 Boiler level controls Water level limiting, feedwater control and continuous level measurement
LRGT 16-1, LRR 1-50 Conductivity measurement and control Keeps boiler water conductivity in range through continuous blowdown
TRS 5-50 Safety temperature limiter SIL 3 temperature limiting for boilers and hot water systems

The type of steam trap follows the duty. Ball float traps discharge condensate as soon as it forms, which suits heat exchangers with changing loads. Thermostatic and bimetallic traps hold condensate back slightly and suit steam mains, tracing and air venting. On the boiler itself, GESTRA level and conductivity electronics work as a system: electrodes or transmitters in the boiler, controllers in the panel, and the feedwater and blowdown valves they drive.

Where GESTRA products are used

In Oman and the GCC, GESTRA equipment is used in boiler houses of refineries, petrochemical and fertiliser plants, power and desalination stations, food and beverage plants, laundries, hotels and hospitals.

Ordering GESTRA parts: what we need

Send the type designation, pressure rating (PN) and connection size (DN), the end connection (flanged, screwed or socket weld), the operating pressure and condensate load for steam traps, and the supply voltage and bus type (CAN bus, 4-20 mA) for control equipment. For electrodes, add the insertion length.

Facts checked against GESTRA company history and Bremen city records, October 2026.

FAQ

Questions about the GESTRA BK 46 Alloy Steel Bimetallic Steam Trap PN 40

Answers from our engineering team on installation, compatibility and integration.

01What is the material of the BK 46?
Body and cover are 1.5415 (A 182 F1 equivalent), with 1.7225 screws, graphite/CrNi gasket and a stainless steel Duo regulator.
02What differential pressure can the BK 46 handle?
The datasheet states 32 bar, compared with 22 bar for the BK 45.
03What is the maximum temperature of the BK 46 on PN 40?
The PN 40 table runs to 450 degrees C, where the admissible pressure is 27.6 barg.
04Which spare regulator is listed for the BK 46?
The Thermovit regulator with gasket is listed as 375464, with the common strainer set 375113.
05Which sizes does the BK 46 come in?
DN 15, 20 and 25, with the same PN 40 and Class 150/300 flange and weld options as the BK 45.