Brand:

Eaton DILM12-10(230V50/60HZ) Contactor 12 A 230 V AC

Description

Eaton DILM12-10(230V50/60HZ) contactor, 12 A, 230 V AC coil

The Eaton DILM12-10(230V50/60HZ) (catalog number 276838) is the 230 V AC version of the compact DILM12-10 contactor. It has three main contacts rated 12 A in AC-3 (5.5 kW at 380/400 V), one normally open auxiliary contact and a 230 V, 50/60 Hz coil that can be driven directly from a single-phase mains control circuit. This coil voltage is the usual choice in starter panels where the control supply is taken from phase and neutral of the 400 V system, and a push-button or relay contact switches the coil. Seven Star LLC supplies the DILM12-10(230V50/60HZ) in Oman and the GCC.

What DILM12-10(230V50/60HZ) means

DILM is the series, 12 the AC-3 current in amperes and 10 the built-in auxiliary contact arrangement of one N/O and no N/C. The bracket gives the coil: 230 V, valid on both 50 Hz and 60 Hz. Compared with the 24 V AC sibling DILM12-10(24V50/60HZ) and the DC sibling DILM12-10(24VDC), the power circuit is identical; the difference lies entirely in the coil, and with it the control wiring and the safety treatment of the control circuit.

DILM12-10(230V50/60HZ) technical specifications

Parameter Specification
Manufacturer / part number Eaton DILM12-10(230V50/60HZ) (catalog number 276838)
Coil voltage Us 230 V, 50/60 Hz AC (dual-frequency coil)
Pick-up voltage 0.8 – 1.1 × Uc
Drop-out voltage 0.6 – 0.3 × Uc
Closing delay (make contacts) 15 – 21 ms
Opening delay (make contacts) 9 – 18 ms
Rated making capacity up to 690 V 144 A
Safe isolation 400 V AC, between coil and contacts and between contacts (EN 61140)
Series Eaton Moeller DILM
Product category Contactor, 3 main contacts (N/O) plus 1 N/O auxiliary contact
Frame size FS1
Rated operational power AC-3, 240 V / 380/400 V / 415 V, 50 Hz 4 kW / 5.5 kW / 7 kW
Rated operational power AC-3, 440 V / 500 V / 690 V, 50 Hz 7.5 kW / 7 kW / 6.5 kW
Rated operational current AC-3, up to 440 V 12 A
Rated operational current AC-3, 500 V / 660–690 V 10 A / 7 A
Rated operational current AC-1, 380–415 V 22 A
Rated operational current AC-4, 220–240 V and 440 V / 500 V / 660–690 V 7 A / 6 A / 5 A
Conventional thermal current Ith, open at 55 °C / enclosed 21 A / 18 A
Rated insulation voltage Ui 690 V
Rated impulse withstand voltage Uimp 8000 V AC
Rated breaking capacity at 220–400 V / 500 V / 660–690 V 120 A / 100 A / 70 A
Short-circuit protection, type 1 coordination, 400 V / 690 V 35 A gG/gL / 25 A gG/gL
Short-circuit protection, type 2 coordination, 400 V / 690 V 20 A gG/gL / 20 A gG/gL
Degree of protection IP20, finger and back-of-hand proof
Connection Screw terminals; solid 1 × 0.75–4 mm² or 2 × 0.75–2.5 mm²; flexible with ferrule 1 or 2 × 0.75–2.5 mm²
Tightening torque / stripping length 1.2 Nm / 10 mm
Dimensions (depth x height x width) 75 x 68 x 45 mm
Mechanical operating frequency 9000 operations per hour
Weight 0.24 kg
Compliance CE marked

The data follows the manufacturer specification sheet for catalog number 276838. For North American ratings the sheet lists 1 HP at 115/120 V and 2 HP at 230/240 V single-phase, and 3 HP at 200/208 V and 230/240 V, 10 HP at 460/480 V and 10 HP at 575/600 V three-phase at 60 Hz.

Why a 230 V coil on the DILM12-10(230V50/60HZ)

A 230 V coil removes the need for a control transformer in many panels. The coil is connected between phase and neutral through the start and stop circuit, and the contactor closes when the coil voltage reaches 0.8 times the rated value or more. It drops out between 0.6 and 0.3 times the coil voltage, so a weak supply or a voltage dip can open the contactor, a behaviour that is useful for undervoltage protection but should be considered for sites with unstable power.

The sheet lists safe isolation of 400 V AC between the coil and the contacts, according to EN 61140, which allows the 230 V coil circuit to be separated from the 400 V motor circuit. Closing takes 15 to 21 ms and opening 9 to 18 ms, short enough for normal motor starters.

Using the DILM12-10(230V50/60HZ) in a direct-on-line starter

In a standard starter the DILM12-10(230V50/60HZ) is placed between a motor-protective breaker such as the PKZM0-10 or PKZM0-16 and the motor. The breaker handles overload and short circuit; the contactor handles repeated starts and stops, with a mechanical operating frequency up to 9000 operations per hour. For a reversing starter two contactors with a mechanical interlock are used. The built-in N/O auxiliary contact serves as the seal-in contact for a push-button start, which is the main reason the 10 version suits this application.

For motors above 5.5 kW at 400 V the next contactor size is required. For resistive loads such as heaters the contactor can carry 22 A in AC-1 at 380 to 415 V.

Choosing the DILM12-10(230V50/60HZ)

  • Check that the motor current does not exceed 12 A at the operating voltage.
  • Confirm the control supply is 230 V and that its stability is adequate for the 0.8 to 1.1 times Uc tolerance.
  • Plan overload protection separately, using a motor-protective breaker or overload relay.
  • Decide the coordination class and back-up fuse: 20 A gG/gL for type 2, 35 A gG/gL for type 1 at 400 V.
  • Verify whether a second auxiliary contact is needed, as this version has one N/O only.

Installation and maintenance of the DILM12-10(230V50/60HZ)

Mount the contactor on a 35 mm rail or screw-fix it. Connect the main conductors to terminals at 1.2 Nm, with a stripping length of 10 mm. The coil terminals are A1 and A2. Isolate the panel before working on the coil circuit, which carries 230 V. Maintenance consists of listening for chatter or hum, checking terminals for heat marks and replacing the contactor when contacts are worn.

Typical applications in Oman and the GCC

The DILM12-10(230V50/60HZ) is a standard component in starter panels for pumps, fans, compressors and conveyors in Oman and the Gulf, where 230/400 V supplies are used at 50 Hz. It also appears in lighting and heater contactor panels for loads up to 22 A in AC-1. Since mains disturbances and heat are common on industrial sites, panel temperature and supply quality should be checked.

Eaton DILM12-10 coil variants

Model Catalog number Coil
DILM12-10(24V50/60HZ) 276834 24 V, 50/60 Hz AC coil
DILM12-10(230V50/60HZ) 276838 230 V, 50/60 Hz AC coil
DILM12-10(24VDC) 276845 24 V DC coil, varistor suppressor fitted

Further coil voltages of the same contactor exist, among them 42 V, 110 V, 220 V, 380 V and 12 V DC; confirm the coil voltage you need against the exact model code.

Information to send with an RFQ for DILM12-10(230V50/60HZ)

  • Exact model DILM12-10(230V50/60HZ) (catalog number 276838) and the quantity, including spares.
  • Motor current and voltage, or load type.
  • Confirmation that the control supply is 230 V AC.
  • Protective device or overload relay to be combined.
  • Delivery location (Muscat, Sohar, Salalah or elsewhere in the GCC) and the date you need the goods.
  • Any documents you need with the quotation, such as an installation leaflet or declaration of conformity.

Documents and quotation

The manufacturer specification sheet for DILM12-10(230V50/60HZ) is attached on this page, so you can check the ratings, dimensions and approvals against your project before you order. Installation leaflets and declarations of conformity can be requested separately.

Seven Star LLC supplies Eaton industrial control products in Oman and the GCC. To request a quotation, send model DILM12-10(230V50/60HZ), the quantity and your delivery location, and we will confirm availability and lead time for your order.

Other Models in the Eaton Dilm12 10 Range

Seven Star LLC supplies models from the Eaton Dilm12 10 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Eaton DILM12-10(24V50/60HZ) Contactor 12 A 24 V ACContactors & Overload RelaysView details
Eaton DILM12-10(230V50/60HZ) Contactor 12 A 230 V ACContactors & Overload RelaysYou are viewing this model
Eaton DILM12-10(24VDC) Contactor 12 A with 24 V DC CoilContactors & Overload RelaysView details
Datasheets & Documents
  • PDF Datasheet Eaton DILM12-10(230V50/60HZ) Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Eaton is a power management company that began in 1911, when Joseph O. Eaton started a truck axle business in New York and moved it to Cleveland, Ohio, in 1914. It grew from vehicle components into electrical equipment, hydraulics and aerospace systems. Since buying Cooper Industries in 2012, Eaton has been incorporated in Ireland with its head office in Dublin, and it is listed on the New York Stock Exchange.

Seven Star LLC lists Eaton NZM molded case circuit breakers, PKZM0 motor-protective circuit breakers and Bussmann series Class J fuses, and supplies them to panel builders and maintenance teams in Oman and the GCC.

Eaton company profile

Founded 1911, New York, USA, by Joseph O. Eaton
Early move Cleveland, Ohio, 1914
Headquarters Dublin, Ireland, since the 2012 Cooper Industries acquisition
Listing New York Stock Exchange (ETN)
Brands Eaton, Moeller, Bussmann, Crouse-Hinds, MTL and MEDC
Product families FAZ and PL miniature circuit breakers, NZM moulded-case breakers, DILM contactors, PowerXL variable frequency drives, 9PX and 93PM UPS, Bussmann fuses, hazardous-area enclosures and signalling

Milestones

  • 1911: Joseph O. Eaton starts an axle business in New York.
  • 1914: The business moves to Cleveland.
  • 2012: Eaton acquires Cooper Industries and redomiciles in Ireland.

Eaton circuit protection listed here

The NZMN1-A80 is a frame size 1 molded case circuit breaker rated 80 A with a thermomagnetic release for cable and system protection. The PKZM0-1,6 is a motor-protective circuit breaker whose overload release is adjustable from 1 to 1.6 A, used as a manual motor starter. The LPJ-35SP is a Bussmann series Low-Peak Class J time-delay fuse rated 35 A at 600 V AC. Older NZM and PKZ devices carry the Moeller name on the nameplate, and the type designations are the same.

Where Eaton breakers and fuses are used

Motor control centers, feeder panels, machine control cabinets and UL-style fused disconnects.

Eaton products we list

Family Examples
Circuit Breakers LPJ-35SP Class J Time-Delay Fuse, NZMN1-A80 Molded Case Circuit Breaker, NZMN2-A250 Molded Case Circuit Breaker, NZMN3-AE400 Molded Case Circuit Breaker, PKZM0-1
AC Drives DA1-342D2FB-A20C AC Drive, PowerXL DG1-34140FN-C21C Variable Freque…

Ordering Eaton parts: what we need

Send the full type and article number, the number of poles, the current rating or setting range, and any accessories such as auxiliary contacts, trip releases or rotary handles.

Facts checked against Eaton's corporate history and investor materials, October 2026.

FAQ

Questions about the Eaton DILM12-10(230V50/60HZ) Contactor 12 A 230 V AC

Answers from our engineering team on installation, compatibility and integration.

01What coil voltage does the DILM12-10(230V50/60HZ) have?
230 V AC for both 50 Hz and 60 Hz supplies. Pick-up is between 0.8 and 1.1 times the coil voltage and drop-out between 0.6 and 0.3 times.
02What is the rated current of the DILM12-10(230V50/60HZ)?
The contactor is rated 12 A in AC-3 up to 440 V, 10 A at 500 V and 7 A at 660 to 690 V, and 22 A in AC-1 at 380 to 415 V.
03How fast does the DILM12-10(230V50/60HZ) switch?
The sheet lists a closing delay of 15 to 21 ms and an opening delay of 9 to 18 ms for the make contacts.
04What isolation does the DILM12-10(230V50/60HZ) offer between coil and contacts?
The sheet lists safe isolation of 400 V AC between the coil and the contacts and between the contacts, according to EN 61140.
05Does the DILM12-10(230V50/60HZ) include an auxiliary contact?
Yes, one built-in normally open auxiliary contact, which is commonly used as a seal-in contact for push-button control.