Brand:

Eaton DILM12-10(24V50/60HZ) Contactor 12 A 24 V AC

Description

Eaton DILM12-10(24V50/60HZ) contactor, 12 A, 24 V AC coil

The Eaton DILM12-10(24V50/60HZ) (catalog number 276834) is a three-pole contactor from the Moeller DILM series with a 24 V, 50/60 Hz AC coil. It is rated for 12 A in utilisation category AC-3, which corresponds to 5.5 kW at 380/400 V, and it includes one normally open auxiliary contact. The 24 V coil lets a PLC output or a low-voltage control transformer energise the contactor directly, without a 230 V control circuit in the panel. Seven Star LLC supplies the DILM12-10(24V50/60HZ) in Oman and the GCC for panel builders, OEMs and maintenance teams.

Reading the DILM12-10(24V50/60HZ) model code

DILM is the contactor series. The number 12 is the AC-3 rated operational current in amperes. The suffix 10 describes the contact arrangement of the built-in auxiliary contact: one normally open and no normally closed contact. The part in brackets is the coil, here 24 V at 50/60 Hz AC. The same contactor is offered with other coil voltages, for example the DILM12-10(230V50/60HZ) for 230 V control and the DILM12-10(24VDC) with a DC coil.

DILM12-10(24V50/60HZ) technical specifications

Parameter Specification
Manufacturer / part number Eaton DILM12-10(24V50/60HZ) (catalog number 276834)
Coil voltage Us 24 V, 50/60 Hz AC (dual-frequency coil)
Pick-up voltage 0.8 – 1.1 × Uc
Drop-out voltage 0.6 – 0.3 × Uc
Closing delay (make contacts) 15 – 21 ms
Opening delay (make contacts) 9 – 18 ms
Rated making capacity up to 690 V 144 A
Resistance per pole 2.5 mΩ
Series Eaton Moeller DILM
Product category Contactor, 3 main contacts (N/O) plus 1 N/O auxiliary contact
Frame size FS1
Rated operational power AC-3, 240 V / 380/400 V / 415 V, 50 Hz 4 kW / 5.5 kW / 7 kW
Rated operational power AC-3, 440 V / 500 V / 690 V, 50 Hz 7.5 kW / 7 kW / 6.5 kW
Rated operational current AC-3, up to 440 V 12 A
Rated operational current AC-3, 500 V / 660–690 V 10 A / 7 A
Rated operational current AC-1, 380–415 V 22 A
Rated operational current AC-4, 220–240 V and 440 V / 500 V / 660–690 V 7 A / 6 A / 5 A
Conventional thermal current Ith, open at 55 °C / enclosed 21 A / 18 A
Rated insulation voltage Ui 690 V
Rated impulse withstand voltage Uimp 8000 V AC
Rated breaking capacity at 220–400 V / 500 V / 660–690 V 120 A / 100 A / 70 A
Short-circuit protection, type 1 coordination, 400 V / 690 V 35 A gG/gL / 25 A gG/gL
Short-circuit protection, type 2 coordination, 400 V / 690 V 20 A gG/gL / 20 A gG/gL
Degree of protection IP20, finger and back-of-hand proof
Connection Screw terminals; solid 1 × 0.75–4 mm² or 2 × 0.75–2.5 mm²; flexible with ferrule 1 or 2 × 0.75–2.5 mm²
Tightening torque / stripping length 1.2 Nm / 10 mm
Dimensions (depth x height x width) 75 x 68 x 45 mm
Mechanical operating frequency 9000 operations per hour
Weight 0.24 kg

The data follows the manufacturer specification sheet for catalog number 276834. For North American ratings the sheet lists 1 HP at 115/120 V and 2 HP at 230/240 V single-phase, and 3 HP at 200/208 V and 230/240 V, 10 HP at 460/480 V and 10 HP at 575/600 V three-phase at 60 Hz.

How the DILM12-10(24V50/60HZ) switches a motor

A contactor is an electrically operated switch. When the coil is energised, the magnet pulls the contact carrier in, closing the three main contacts and the N/O auxiliary contact together. When the coil is de-energised, a spring opens them again. The DILM12-10(24V50/60HZ) has a dual-frequency AC coil, which means the same coil works on 50 Hz and 60 Hz supplies without a change of part, and its pick-up range of 0.8 to 1.1 times the coil voltage defines the control voltage tolerance within which it will reliably close. It drops out between 0.6 and 0.3 times the coil voltage.

The main contacts are rated for 12 A in AC-3 up to 440 V, falling to 10 A at 500 V and 7 A at 660 to 690 V. In AC-1, for resistive loads such as heaters, the rating is 22 A at 380 to 415 V. Heavy switching duties such as plugging and inching fall under AC-4, where the sheet gives 7 A up to 440 V.

Where the DILM12-10(24V50/60HZ) fits in a starter

The contactor pairs with a motor-protective breaker such as the PKZM0-10, PKZM0-16 or an electronic PKE12 device to form a direct-on-line starter: the breaker provides short-circuit and overload protection, and the contactor carries the switching duty. The sheet gives type 2 coordination with a 20 A gG/gL fuse at 400 V, and type 1 coordination with 35 A gG/gL, so the short-circuit protective device must be chosen to match the coordination class required. The built-in N/O auxiliary contact is commonly used as a seal-in contact for push-button control or as a feedback signal to a PLC.

Selection checklist for the DILM12-10(24V50/60HZ)

  • Confirm the motor current at the actual voltage does not exceed 12 A (10 A at 500 V, 7 A at 690 V).
  • Make sure the control voltage is really 24 V AC at 50 or 60 Hz; a 24 V DC supply needs the DC coil version.
  • Check the control transformer or PLC interface can supply the coil, and the tolerance 0.8 to 1.1 times Uc.
  • Decide the short-circuit coordination class and fuse size.
  • Check whether a normally closed auxiliary contact is needed, since this version has one N/O only.

Installation and maintenance of the DILM12-10(24V50/60HZ)

The contactor is 45 mm wide, 75 mm deep and 68 mm high. Strip conductors by 10 mm and tighten the screw terminals to 1.2 Nm; solid conductors of up to 4 mm² and flexible conductors of up to 2.5 mm² with ferrules are accepted. Keep the coil circuit separated from power cables in the panel. During maintenance, check for contact noise, coil hum and discolouration of terminals. Contactors that chatter often have too low a control voltage or a weak connection.

Typical applications in Oman and the GCC

A 24 V AC control circuit is common in machine control panels, building automation and package units delivered by OEMs to Oman and the GCC. The DILM12-10(24V50/60HZ) switches pumps, fans, compressors and conveyor motors up to 5.5 kW at 400 V, and heaters up to about 22 A in AC-1. High ambient temperatures call for attention to enclosure temperature: the sheet gives a conventional thermal current of 21 A open at 55 °C and 18 A in an enclosure.

Eaton DILM12-10 coil variants

Model Catalog number Coil
DILM12-10(24V50/60HZ) 276834 24 V, 50/60 Hz AC coil
DILM12-10(230V50/60HZ) 276838 230 V, 50/60 Hz AC coil
DILM12-10(24VDC) 276845 24 V DC coil, varistor suppressor fitted

Further coil voltages of the same contactor exist, among them 42 V, 110 V, 220 V, 380 V and 12 V DC; confirm the coil voltage you need against the exact model code.

Information to send with an RFQ for DILM12-10(24V50/60HZ)

  • Exact model DILM12-10(24V50/60HZ) (catalog number 276834) and the quantity, including spares.
  • Motor nameplate current and voltage, or load type.
  • Coil voltage and frequency of the control circuit.
  • Overload relay or motor-protective breaker to be combined.
  • Delivery location (Muscat, Sohar, Salalah or elsewhere in the GCC) and the date you need the goods.
  • Any documents you need with the quotation, such as an installation leaflet or declaration of conformity.

Documents and quotation

The manufacturer specification sheet for DILM12-10(24V50/60HZ) is attached on this page, so you can check the ratings, dimensions and approvals against your project before you order. Installation leaflets and declarations of conformity can be requested separately.

Seven Star LLC supplies Eaton industrial control products in Oman and the GCC. To request a quotation, send model DILM12-10(24V50/60HZ), the quantity and your delivery location, and we will confirm availability and lead time for your order.

Other Models in the Eaton Dilm12 10 Range

Seven Star LLC supplies models from the Eaton Dilm12 10 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Eaton DILM12-10(24V50/60HZ) Contactor 12 A 24 V ACContactors & Overload RelaysYou are viewing this model
Eaton DILM12-10(230V50/60HZ) Contactor 12 A 230 V ACContactors & Overload RelaysView details
Eaton DILM12-10(24VDC) Contactor 12 A with 24 V DC CoilContactors & Overload RelaysView details
Datasheets & Documents
  • PDF Datasheet Eaton DILM12-10(24V50/60HZ) Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Eaton is a power management company that began in 1911, when Joseph O. Eaton started a truck axle business in New York and moved it to Cleveland, Ohio, in 1914. It grew from vehicle components into electrical equipment, hydraulics and aerospace systems. Since buying Cooper Industries in 2012, Eaton has been incorporated in Ireland with its head office in Dublin, and it is listed on the New York Stock Exchange.

Seven Star LLC lists Eaton NZM molded case circuit breakers, PKZM0 motor-protective circuit breakers and Bussmann series Class J fuses, and supplies them to panel builders and maintenance teams in Oman and the GCC.

Eaton company profile

Founded 1911, New York, USA, by Joseph O. Eaton
Early move Cleveland, Ohio, 1914
Headquarters Dublin, Ireland, since the 2012 Cooper Industries acquisition
Listing New York Stock Exchange (ETN)
Brands Eaton, Moeller, Bussmann, Crouse-Hinds, MTL and MEDC
Product families FAZ and PL miniature circuit breakers, NZM moulded-case breakers, DILM contactors, PowerXL variable frequency drives, 9PX and 93PM UPS, Bussmann fuses, hazardous-area enclosures and signalling

Milestones

  • 1911: Joseph O. Eaton starts an axle business in New York.
  • 1914: The business moves to Cleveland.
  • 2012: Eaton acquires Cooper Industries and redomiciles in Ireland.

Eaton circuit protection listed here

The NZMN1-A80 is a frame size 1 molded case circuit breaker rated 80 A with a thermomagnetic release for cable and system protection. The PKZM0-1,6 is a motor-protective circuit breaker whose overload release is adjustable from 1 to 1.6 A, used as a manual motor starter. The LPJ-35SP is a Bussmann series Low-Peak Class J time-delay fuse rated 35 A at 600 V AC. Older NZM and PKZ devices carry the Moeller name on the nameplate, and the type designations are the same.

Where Eaton breakers and fuses are used

Motor control centers, feeder panels, machine control cabinets and UL-style fused disconnects.

Eaton products we list

Family Examples
Circuit Breakers LPJ-35SP Class J Time-Delay Fuse, NZMN1-A80 Molded Case Circuit Breaker, NZMN2-A250 Molded Case Circuit Breaker, NZMN3-AE400 Molded Case Circuit Breaker, PKZM0-1
AC Drives DA1-342D2FB-A20C AC Drive, PowerXL DG1-34140FN-C21C Variable Freque…

Ordering Eaton parts: what we need

Send the full type and article number, the number of poles, the current rating or setting range, and any accessories such as auxiliary contacts, trip releases or rotary handles.

Facts checked against Eaton's corporate history and investor materials, October 2026.

FAQ

Questions about the Eaton DILM12-10(24V50/60HZ) Contactor 12 A 24 V AC

Answers from our engineering team on installation, compatibility and integration.

01What coil does the DILM12-10(24V50/60HZ) have?
A 24 V dual-frequency AC coil for 50 and 60 Hz. Pick-up is between 0.8 and 1.1 times the coil voltage and drop-out between 0.6 and 0.3 times the coil voltage.
02What motor can the DILM12-10(24V50/60HZ) switch?
It is rated for 12 A in AC-3 up to 440 V, which is 5.5 kW at 380/400 V and 7.5 kW at 440 V. At 500 V the rating is 10 A and at 690 V 7 A.
03How many auxiliary contacts does the DILM12-10(24V50/60HZ) have?
It has one built-in normally open auxiliary contact and no normally closed one. The model code suffix 10 refers to this arrangement.
04What is the thermal current of the DILM12-10(24V50/60HZ)?
The conventional thermal current is 21 A open at 55 degrees C, 20 A at 60 degrees C and 18 A when enclosed, and 50 A for a single pole open.
05What size is the DILM12-10(24V50/60HZ)?
The sheet gives 75 mm depth, 68 mm height and 45 mm width, with a weight of 0.24 kg and a frame size of FS1.