Schneider Electric A9F93232 iC60L 2P 32A B Breaker
Description
A9F93232: two-pole 32 A B-curve iC60L breaker
The A9F93232 is a Schneider Electric Acti9 iC60L miniature circuit breaker, listed as iC60L – miniature circuit breaker – 2P – 32A – B curve. The datasheet describes a 2P thermal-magnetic device rated 32 A with a B trip curve for AC and DC networks, standardised to EN/IEC 60947-2 and EN/IEC 60898-1. Its headline breaking capacity is 36 kA Icu in the 220–240 V AC band. Seven Star LLC supplies the A9F93232 in Oman and the GCC as an independent supplier based in Muscat.
The datasheet for the A9F93232 is dated 8 Nov 2026 and shows no lifecycle warning in its header, but availability should still be confirmed before an order is placed. A 32 A rating is usual for sub-board feeders, larger heating loads and equipment fed with 6 or 10 mm² conductors. Add-on residual current protection listed as compatible: Vigi iC60 single terminal add-on residual current device 40/63 A; Quick Vigi iC60 single terminal add-on residual current device 40 A.
Technical specifications of the A9F93232
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / A9F93232 |
| Range / product name | Acti9 / Acti9 iC60 |
| Device short name | iC60L |
| Poles | 2P (2 protected poles) |
| Rated current [In] | 32 A |
| Curve / trip unit | B curve, thermal-magnetic |
| Network type / frequency | AC and DC, 50/60 Hz |
| Magnetic tripping limit | 4 x In ± 20 % |
| Rated operational voltage [Ue] | 12–133 V AC 50/60 Hz; 220–240 V AC 50/60 Hz; 380–415 V AC 50/60 Hz; 440 V AC 50/60 Hz; up to 125 V DC |
| Rated insulation voltage [Ui] | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Impulse withstand [Uimp] | 6 kV conforming to EN/IEC 60947-2 |
| Standards | EN/IEC 60947-2 and EN/IEC 60898-1 |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 / Yes conforming to EN/IEC 60898-1 |
| Dimensions (H x W x D) | 85 mm x 36 mm x 78.5 mm |
| Rail pitches / weight | 4 pitches of 9 mm; 0.25 kg |
| Terminals | Single terminal, top or bottom: 35 mm² rigid and 25 mm² flexible copper |
| Stripping length / torque | 14 mm; 3.5 N.m |
| Durability | 20000 cycles mechanical, 10000 cycles electrical |
| Protection degree | IP20 (IEC 60529); IP40 in modular enclosure |
| Operating temperature / altitude | -35–70 °C; 0–2000 m |
| Storage temperature | -40–85 °C |
| Relative humidity | 95 % at 55 °C |
| Colour | White |
2P construction of the A9F93232
A two-pole device opens two conductors together through one common handle, usually phase and neutral of a single-phase circuit or two phases of a line-to-line load. It takes four 9 mm pitches (36 mm). A fault on either pole opens both, and the pair is more compact than two single-pole breakers joined by a handle tie.
The body is 36 mm wide, 85 mm high and 78.5 mm deep and weighs 0.25 kg. A layout should reserve 36 mm of rail per device. Terminals take 35 mm² rigid or 25 mm² flexible copper, tightened to 3.5 N.m, and the datasheet lists comb busbar and distribution block compatibility at top or bottom.
Reading the B curve and the 32 A rating
The B curve is the most sensitive of the three letters used on this page. With a magnetic trip at 4 times In (±20 %), it reacts early to a short circuit, which is valuable on long cable runs where the fault current at the far end is modest and on circuits that carry resistive loads with almost no inrush. The cost of that sensitivity is that it will not ride through large switching currents, so it is a poor match for transformers or groups of motors.
On the A9F93232 the datasheet states a magnetic tripping limit of 4 x In ± 20 %, which for 32 A corresponds to an instantaneous trip region starting around 128 A, subject to the ±20 % tolerance. The thermal element handles slower overloads. DC use is also listed (20 kA at up to 125 V DC), so check polarity and voltage against the real circuit before using it on a DC supply.
Where the A9F93232 is used in Oman and the GCC
The iC60L family targets places where the available fault current is high, such as main distribution boards close to a transformer, utility auxiliary panels, industrial plant and commercial towers. The A9F93232 fits circuits that need a 32 A two-pole B-curve breaker with a strong breaking capacity in a compact 9 mm module. Gulf installations combine heat, dust and humidity, so compare site conditions with the temperature and humidity limits above, and with the derating practice of the board builder.
Installation and maintenance of the A9F93232
The A9F93232 clips onto a 35 mm DIN rail. Strip conductors to 14 mm and tighten with a calibrated screwdriver to 3.5 N.m. Because heavy fault energy is possible, keep conductors short and supported near the terminals.
Inspect periodically for discoloured terminals, a free-moving handle and a clear trip indicator. Mechanical life is 20000 cycles and electrical life 10000 cycles. A breaker that has cleared a large fault should be inspected and normally replaced instead of assumed intact. As a stocked reference, keeping a spare is prudent for critical boards.
Environmental and logistics data for the A9F93232
The datasheet lists operation from -35–70 °C, storage from -40–85 °C, relative humidity of 95 % at 55 °C and tropicalisation class 2, with pollution degree 3. Country of origin is shown as FR and the contractual warranty as 18 months. A total lifecycle carbon footprint of 33 kg CO2 eq. is declared, with a recyclability potential of 54 %. A single unit packs at about 249.000 g, with 6 units in the intermediate carton.
The A9F93232 among iC60L 2P references
The closest neighbours by rating are A9F94232 (C 32 A) and A9F94240 (C 40 A); they share the housing and differ in thermal setting and, in some cases, in curve and breaking-capacity figures. The table lists the 2P references of this iC60L batch.
| Reference | Curve / rating | Icu at 220–240 V AC | Status in datasheet |
|---|---|---|---|
| A9F93232 (this page) | B / 32 A | 36 kA | Active |
| A9F94204 | C / 4 A | 100 kA | Discontinued |
| A9F94206 | C / 6 A | 50 kA | Discontinued |
| A9F94216 | C / 16 A | 50 kA | Active |
| A9F94220 | C / 20 A | 50 kA | Discontinued |
| A9F94232 | C / 32 A | 36 kA | Active |
| A9F94240 | C / 40 A | 36 kA | Active |
Breaking capacity of the A9F93232 across voltage bands
Icu is the ultimate breaking capacity and Ics the service capacity, quoted as a share of Icu. The iC60L is the high-breaking-capacity member of the iC60 family, and the table shows how the figure changes with voltage for this 2P 32 A reference. The first listed band is 12–133 V AC 50/60 Hz at 70 kA Icu, while the 380–415 V AC band gives 20 kA.
| Voltage band | Icu | Ics |
|---|---|---|
| 12–133 V AC 50/60 Hz | 70 kA | 35 kA (50 % of Icu) |
| 220–240 V AC 50/60 Hz | 36 kA | 18 kA (50 % of Icu) |
| 380–415 V AC 50/60 Hz | 20 kA | 10 kA (50 % of Icu) |
| 440 V AC 50/60 Hz | 15 kA | 7.5 kA (50 % of Icu) |
| up to 125 V DC | 20 kA | 20 kA (100 % of Icu) |
The datasheet also gives a household-standard Icn of 15000 A at 400 V AC 50/60 Hz under EN/IEC 60898-1, and limitation class 3, which describes how strongly the device limits let-through energy. Compare every figure with the prospective fault current at the installation point; if the supply can exceed the band that applies, a different device or upstream back-up is required.
Documents and quotation
A datasheet for the A9F93232 is attached on this page. It lists the electrical, mechanical and environmental data summarised above and should be read with the manufacturer’s installation instructions.
Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.
Other Models in the Se Ic60l 2p B Range
Seven Star LLC supplies models from the Se Ic60l 2p B range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric A9F93220 iC60L 2P 20A B Circuit Breaker | Circuit Breakers | View details |
| Schneider Electric A9F93232 iC60L 2P 32A B Breaker | Circuit Breakers | You are viewing this model |
Datasheets & Documents
- Datasheet Schneider Electric A9F93232 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric A9F93232 iC60L 2P 32A B Breaker
Answers from our engineering team on installation, compatibility and integration.
01What is the rated current and curve of the A9F93232?
The datasheet gives 32 A with a B curve and a thermal-magnetic trip unit. The magnetic tripping limit is 4 x In plus or minus 20 %.
02What breaking capacity does the A9F93232 have at 230 V AC?
The datasheet lists 36 kA Icu in the 220 to 240 V AC band, with a service capacity of 18 kA. Compare it with the prospective fault current at the installation point.
03How wide is the A9F93232 and how many poles does it have?
It is a 2P device, 36 mm wide, 85 mm high and 78.5 mm deep, using 4 pitches of 9 mm on the rail.
04What conductors fit the A9F93232 terminals?
Single terminals at top or bottom accept 35 mm2 rigid and 25 mm2 flexible copper, with a tightening torque of 3.5 N.m.
05Can the A9F93232 be used on DC circuits?
The datasheet lists AC and DC network types. DC ratings: 20 kA Icu at up to 125 V DC. Verify polarity and voltage against the real circuit.