Schneider Electric A9F54340 iC60H 3P 40A C Circuit Breaker

Description

A9F54340: three-pole 40 A C-curve miniature circuit breaker

The A9F54340 is a Schneider Electric Acti9 iC60H miniature circuit-breaker, listed in the datasheet as Acti9 iC60H 3P 40A C Miniature Circuit breaker. The reference describes a 3P device rated 40 A with a C trip curve, built for AC and DC networks with a thermal-magnetic trip unit. The datasheet gives a breaking capacity of 30 kA Icu at 220–240 V AC under EN/IEC 60947-2, which is the headline figure for a 230 V network. Seven Star LLC supplies the A9F54340 in Oman and the GCC as an independent supplier based in Muscat.

The datasheet for this reference carries the date 8 Nov 2026 and does not state a lifecycle status, so confirm availability before ordering. A 40 A rating serves sub-distribution feeders, large heaters and the supply of small motor starters or process cabinets. The datasheet also lists compatibility with add-on residual current devices: Vigi iC60 single terminal add-on residual current device 40/63 A; Quick Vigi iC60 single terminal add-on residual current device 40 A.

Technical specifications of the A9F54340

Parameter Specification
Manufacturer / part number Schneider Electric / A9F54340
Range / product name Acti9 / Disbo iC60
Product type Miniature circuit-breaker
Device short name iC60H
Poles 3P (3 protected poles)
Rated current [In] 40 A
Curve / trip unit Curve C, thermal-magnetic
Network type / frequency AC/DC, 50/60 Hz
Magnetic tripping limit 8 x In ± 20 %
Rated operational voltage [Ue] 12–133 V AC 50/60 Hz; 220–240 V AC 50/60 Hz; 380–415 V AC 50/60 Hz; 440 V AC 50/60 Hz; ≤ 180 V DC
Rated insulation voltage [Ui] 500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand [Uimp] 6 kV conforming to EN/IEC 60947-2
Mounting Clip-on on rail, 6 pitches of 9 mm
Height / width / depth 85 mm / 54 mm / 78.5 mm
Net weight 0.375 kg
Terminals Top or bottom, single terminal: 35 mm² rigid, 25 mm² flexible
Stripping length / torque 14 mm for top or bottom connection; 3.5 N.m top or bottom
Durability 20000 cycles mechanical; 10000 cycles electrical
Handle / indication Toggle, contact position indicator, trip indicator, padlockable
Protection / environment IP20 conforming to IEC 60529; pollution degree 3; overvoltage category IV; tropicalisation 2
Humidity / temperature 95 % at 55 °C; operation -35–70 °C; storage -40–85 °C

The A9F54340 within the iC60H C-curve listing

The closest same-width neighbours in this listing are A9F54332 (32 A) and A9F54350 (50 A), which share the housing and differ in the thermal setting. The same 40 A rating in another pole count is listed as A9F54440 (4P, 72 mm wide). The table lists every reference of this device and curve that appears in our catalogue range.

Reference Poles Rated current Icu at 220–240 V AC
A9F54325 3P 25 A 30 kA
A9F54332 3P 32 A 30 kA
A9F54340 (this page) 3P 40 A 30 kA
A9F54350 3P 50 A 30 kA
A9F54363 3P 63 A 30 kA
A9F54401 4P 1 A 70 kA
A9F54402 4P 2 A 70 kA
A9F54404 4P 4 A 70 kA
A9F54406 4P 6 A 30 kA
A9F54410 4P 10 A 30 kA
A9F54416 4P 16 A 30 kA
A9F54420 4P 20 A 30 kA
A9F54425 4P 25 A 30 kA
A9F54432 4P 32 A 30 kA
A9F54440 4P 40 A 30 kA
A9F54450 4P 50 A 30 kA
A9F54463 4P 63 A 30 kA

Information to send with an RFQ for the A9F54340

  • Full reference (A9F54340) and quantity
  • Supply voltage, frequency and AC or DC use at the installation point
  • Prospective short-circuit current and the load or cable the breaker protects
  • Existing board, rail and neighbouring devices, including any add-on residual current device
  • Delivery location, timing, and whether the order is a spare or a new installation

Where the A9F54340 is used in Oman and the GCC

In Oman and the GCC the iC60 family appears in commercial buildings, industrial distribution boards, utility auxiliary panels and process cabinets. The A9F54340 fits circuits where a 40 A three-pole C-curve breaker with this fault capacity is needed in a compact 9 mm module. Gulf plant rooms combine heat, dust and humidity; the datasheet gives operation from -35–70 °C, relative humidity of 95 % at 55 °C and tropicalisation class 2, so site conditions should be compared against these limits and against the derating practice of the board builder.

Using a 40 A rating: what the A9F54340 protects

The upper ratings carry heavier cables, so the terminal capacity and the tightening torque matter more here. A loose heavy conductor is a classic cause of local overheating, and the fault level on the supply side becomes relevant: the breaker must be able to clear the prospective short-circuit current at its installation point.

The C curve trips magnetically at 8 × In ± 20 %. In general engineering practice a C curve is chosen for mixed loads with moderate starting currents, such as lighting, small motors and power supplies, rather than for loads with extreme inrush.

Breaking capacity of the A9F54340 by voltage band

Breaking capacity is the figure that decides whether a breaker can be installed at a given point of the network. Icu is the ultimate capacity; Ics is the service capacity, expressed as a share of Icu, after which the device is still expected to remain serviceable. For the A9F54340 the datasheet lists the following.

Voltage band Icu Ics
12–133 V AC 50/60 Hz 42 kA 21 kA (50 % of Icu)
220–240 V AC 50/60 Hz 30 kA 15 kA (50 % of Icu)
380–415 V AC 50/60 Hz 15 kA 7.5 kA (50 % of Icu)
440 V AC 50/60 Hz 10 kA 5 kA (50 % of Icu)
≤ 180 V DC 15 kA 15 kA (100 % of Icu)

The datasheet adds a rated short-circuit capacity Icn of 10000 A at 415 V AC 50/60 Hz under EN/IEC 60898-1, the household-standard rating. The limitation class is 3, which describes how strongly the device limits the let-through energy of a short circuit. Compare these values with the prospective fault current at the installation point; if the supply side can exceed them, the design needs a higher-rated device or upstream back-up protection.

3P construction of the A9F54340

As a three-pole device, it opens all three phases with a common handle and occupies six 9 mm pitches (54 mm) of rail. It is intended for three-phase feeders, three-phase equipment and distribution outgoing ways at 380 to 415 V AC. A common trip is important for three-phase loads, because a single-phase condition left unattended can overheat connected motors.

Net weight is 0.375 kg and the body is 54 mm wide, 85 mm high and 78.5 mm deep, so a panel layout should reserve 54 mm of rail per device plus a small gap for heat when several breakers sit side by side.

Installation and maintenance of the A9F54340

The A9F54340 clips onto a rail; the datasheet lists the mounting mode as clip-on. Strip conductors to 14 mm and tighten terminals to 3.5 N.m, using a calibrated screwdriver. Terminals accept 35 mm² rigid and 25 mm² flexible conductors at either the top or the bottom. The handle can be padlocked in the off position for isolation during maintenance; the datasheet also lists a sealable handle with cable of 0.7 mm diameter in the on or off position.

Check periodically that the trip indicator is clear, that the handle moves freely and that terminals have not discoloured. Mechanical durability is 20000 cycles and electrical durability is 10000 cycles. A device that has cleared a heavy fault should be inspected and replaced rather than assumed intact.

Documents and quotation

A datasheet for this unit is attached on this page. It lists the electrical, mechanical and environmental data summarised above and should be read together with the manufacturer’s installation instructions.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.

Other Models in the Se Ic60h 3p C Range

Seven Star LLC supplies models from the Se Ic60h 3p C range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric A9F54325 iC60H 3P 25A C Circuit BreakerCircuit BreakersView details
Schneider Electric A9F54332 iC60H 3P 32A C Circuit BreakerCircuit BreakersView details
Schneider Electric A9F54340 iC60H 3P 40A C Circuit BreakerCircuit BreakersYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Schneider Electric A9F54340 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric A9F54340 iC60H 3P 40A C Circuit

Answers from our engineering team on installation, compatibility and integration.

01What is the rated current of the A9F54340?
The datasheet gives 40 A, with a C curve and a thermal-magnetic trip unit. The magnetic tripping limit is 8 x In plus or minus 20 %.
02What breaking capacity does the A9F54340 have at 230 V AC?
The datasheet lists 30 kA Icu for the 220 to 240 V AC band, with a service capacity Ics of 15 kA. Compare it with the prospective fault current at the installation point.
03How wide is the A9F54340 and how many poles does it have?
It is a 3P device, 54 mm wide, 85 mm high and 78.5 mm deep, occupying 6 pitches of 9 mm on the rail.
04What conductors fit the A9F54340 terminals?
The datasheet lists single terminals at top or bottom for 35 mm2 rigid and 25 mm2 flexible conductors, with a tightening torque of 3.5 N.m.
05Can the A9F54340 be used on DC circuits?
The datasheet lists network type AC/DC with DC ratings in the breaking-capacity table: 15 kA Icu at up to 180 V DC. Check the polarity and voltage of the real circuit against these bands.