Phoenix Contact QUINT4-PS/1AC/110DC/4 Power Supply 110 V DC

Description

QUINT4-PS/1AC/110DC/4: 110 V DC output power supply, 4 A, from single-phase mains

The Phoenix Contact QUINT4-PS/1AC/110DC/4 (order no. 2904613) is unusual in the QUINT4 family because its output is 110 V DC rather than 24 V DC. It delivers 4 A and is adjustable from 110 V DC up to 135 V DC, from a single-phase input covering 100 to 240 V AC. The datasheet lists 440 W, 550 W and 660 W output classes and a typical efficiency of 93.5 % at 120 V AC and 94.7 % at 230 V AC.

Seven Star LLC supplies the QUINT4-PS/1AC/110DC/4 as an independent supplier in Muscat for projects in Oman and the GCC, quoted against the exact part number shown here.

Technical specifications of the QUINT4-PS/1AC/110DC/4

Parameter Specification
Manufacturer / part number Phoenix Contact QUINT4-PS/1AC/110DC/4 (order no. 2904613)
Nominal input voltage range 100 V AC – 240 V AC -10 % – +10 %
Input frequency 50 Hz – 60 Hz -10 % – +10 %
Nominal output voltage 110 V DC
Output voltage setting range 110 V DC – 135 V DC (constant capacity)
Nominal output current 4 A
Output power 440 W; 550 W; 660 W
Efficiency typ. 93.5 % (120 V AC); typ. 94.7 % (230 V AC)
Mains buffering time typ. 37 ms (120 V AC); typ. 38 ms (230 V AC)
Residual ripple < 600 mVPP (with nominal values)
Output characteristic U/I Advanced; Smart HICCUP; FUSE MODE
Terminal connection Screw connection
MTBF > 1169000 h (25 °C); > 688000 h (40 °C); > 308000 h (60 °C)
Insulation voltage input/output 4 kV AC (type test); 2 kV AC (routine test)
Protection class I

How the QUINT4-PS/1AC/110DC/4 works

The QUINT4-PS/1AC/110DC/4 is a primary-switched converter: the mains input is rectified, power-factor corrected and chopped at high frequency, then transformed and rectified again to give an isolated, regulated DC output. The QUINT4 generation adds a selectable output characteristic, so the unit can be matched to the loads behind it. The Static Boost and Dynamic Boost values in the table show how much short-term current the unit can deliver above its nominal rating, which helps start motors, relay banks and capacitive loads without tripping. Signalling uses LEDs and configurable outputs, and the datasheet lists a signal relay or digital output depending on the type.

The unit includes Selective Fuse Breaking with 24 A for 15 ms, an NFC interface for configuration, and configurable Out1, Out2 and relay signals. The datasheet also lists a SLEEP MODE remote input that switches the output on or off, which can reduce idle losses in standby systems.

Where the QUINT4-PS/1AC/110DC/4 fits in a system

A QUINT4 supply sits at the head of a 24 V (or other DC) control circuit and feeds terminal blocks, electronic circuit breakers, redundancy modules and the loads themselves. Within the family, the same housing style and connection method repeat across sizes, so panel designers can swap power class without redesigning the layout. The datasheet note on mounting distances and derating matters when several units are installed side by side.

Use the QUINT4-PS/1AC/110DC/4 where an installation is built around a 110 V DC bus, for example substation protection, switchgear control and some marine or railway auxiliary circuits. It replaces a battery charger or a larger rectifier where only a modest current is required.

Selection and ordering checklist

  • Confirm the nominal output voltage and that the adjustment range covers any voltage-drop compensation you need.
  • Add up all loads and check that the continuous current is below the nominal output current of the QUINT4-PS/1AC/110DC/4 with a reserve.
  • Check mains input range against the local supply, including DC input if you intend to use it.
  • Compare the housing width with the free rail space in the cabinet.
  • Check ambient temperature against the derating starting point listed in the table.
  • Decide whether the signalling output or relay contact will be wired to a PLC.
  • Confirm that your downstream loads and protective devices are rated for 110 V DC with the adjustment range up to 135 V DC.

Installation, commissioning and maintenance of the QUINT4-PS/1AC/110DC/4

Mount the QUINT4-PS/1AC/110DC/4 on a 35 mm DIN rail in the position described on the datasheet, keep the listed clearances above, below and at the sides, and connect input, output and signal terminals with conductors within the stated cross-sections and tightening torques. Check the polarity and the setting of the output voltage before connecting sensitive loads, then confirm that the status LED signals a healthy output.

Verify the connected devices are rated for the output voltage and the adjustment limit before energising. The output is also fed back with up to 160 V DC resistance, and over-voltage protection operates below 150 V DC, so check downstream insulation ratings.

Typical applications in Oman and the GCC

In Oman and the GCC, control cabinets often run at high ambient temperatures, so the operating range and derating curve in the table are what decide whether a supply is suitable. These supplies are used in oil and gas skids, water treatment and desalination plants, power substations, petrochemical packages and building automation panels.

In the GCC, 110 V DC systems are found in substations and switchyards. A compact 4 A source helps feed closing coils, relays and indication lamps where a battery charger is not needed or is already provided.

Comparison with related QUINT POWER fourth-generation devices

Device Distinguishing data
QUINT4-PS/1AC/24DC/1.3/SC (2904597) 1.3 A, 22.5 mm wide, screw terminals, 30 W nominal
QUINT4-PS/1AC/24DC/2.5/SC (2904598) 2.5 A, 32 mm wide, screw terminals, 60 W nominal
QUINT4-PS/1AC/24DC/10 (2904601) 10 A single-phase, on our site as a separate page
QUINT4-PS/1AC/24DC/20/+ (2904617) 20 A with integrated decoupling MOSFET, 70 mm wide
QUINT4-PS/1AC/110DC/4 (2904613) 110 V DC output, 4 A, 440 W peak class
QUINT4-PS/3AC/24DC/40/CO (1783052) 3-phase input, 24 V DC, 40 A

Information to send with an RFQ

  • Full part number QUINT4-PS/1AC/110DC/4 and quantity.
  • Mains supply voltage, phases and frequency at site.
  • Total connected load and the largest single load current including inrush.
  • Cabinet temperature at the hottest point and the mounting altitude.
  • Whether redundancy, parallel operation or a monitoring signal is needed.
  • Delivery location and required date.

Documents and quotation

Send us the part number QUINT4-PS/1AC/110DC/4 and the quantity you need, and we will confirm which official documents are available for this device. Seven Star LLC is an independent supplier in Muscat and quotes for projects across Oman and the GCC; we do not act on behalf of the manufacturer.

Please also tell us the delivery location and required timeline so that availability can be checked before you commit to a project schedule.

Other Models in the Phoenix Quint4 Range

Seven Star LLC supplies models from the Phoenix Quint4 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Phoenix Contact QUINT4-PS/1AC/24DC/1.3/SC Power SupplyPower ModulesView details
Phoenix Contact QUINT4-PS/1AC/24DC/2.5/SC Power SupplyPower ModulesView details
Phoenix Contact QUINT4-PS/1AC/110DC/4 Power Supply 110 V DCPower ModulesYou are viewing this model
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Phoenix Contact is a German, family-owned manufacturer of electrical connection technology and industrial automation, founded in 1923 in Essen by Hugo Knümann. It began as a sales company, and in 1928 Knümann developed the modular terminal block mounted on a rail, the product the company is still best known for. Phoenix Contact is headquartered in Blomberg, North Rhine-Westphalia.

Seven Star LLC lists Phoenix Contact surge protection, power supplies and safety relays, and sources these components by order number for panel builders and maintenance teams in Oman.

Phoenix Contact company profile

Founded 1923, Essen, Germany, by Hugo Knümann, as Phönix Elektro- und Industrie-Bedarfsgesellschaft
Headquarters Blomberg, Germany
Ownership Family-owned (Eisert and Stührenberg families)
Key invention The modular terminal block on a DIN rail, 1928
Product families CLIPLINE terminal blocks, PCB terminals and connectors, QUINT and TRIO power supplies, relay modules, surge protection, signal conditioners, Ethernet switches and PLCnext controllers

Milestones

  • 1923: Hugo Knümann founds the company in Essen.
  • 1928: The first modular terminal block is developed.
  • Later: Headquarters move to Blomberg, Ostwestfalen-Lippe.

Phoenix Contact parts listed on this page

The TTC-6-2X1-24DC-UT (order number 2906799) is a surge protection device with screw connection for two 24 V DC signal wires that share a common reference potential. The QUINT-PS/1AC/24DC/10 is a single-phase DIN rail power supply delivering 24 V DC at 10 A. The PSR-SCP-24DC/ESP4/2X1/1X2 (order number 2981020) is a single-channel PSR safety relay for emergency stop and safety door monitoring, with two enabling current paths and plug-in screw terminals.

Phoenix Contact products we list

Family Examples
Isolator & Barrier 2906799 TTC-6-2X1-24DC-UT Surge Protector, MACX MCR-EX-SL-RPSSI-I Signal Isolator, MINI MCR-2-UI-UI 3-Way Signal Conditione…, PLT-SEC-T3-230-FM Type 3 Surge Protectio…
Power Modules QUINT-PS/1AC/24DC/10 QUINT Power Supply, QUINT4-PS/1AC/24DC/10 Power Supply, TRIO-PS-2G/1AC/24DC/10 Power Supply, UNO-PS/1AC/24DC/100W Power Supply
Automation Accessories PLC-RSC-24DC/21 Relay Module, PSR-SCP-24DC/ESP4/2X1/1X2 Safety Relay (…

Ordering Phoenix Contact components: what we need

Phoenix Contact items are ordered by a seven-digit order number together with the type designation, both printed on the side of the module. Send both, plus the quantity. If the number is unreadable, send the type text and a photo. For power supplies, state input voltage, output current and whether the unit runs in parallel or with a redundancy module. For buyers in the GCC replacing an older unit, we check the manufacturer's documentation for the listed successor type.

Facts checked against Phoenix Contact's own company history (phoenixcontact.com), October 2026.

FAQ

Questions about the Phoenix Contact QUINT4-PS/1AC/110DC/4 Power Supply

Answers from our engineering team on installation, compatibility and integration.

01What is the output voltage?
The nominal output is 110 V DC, adjustable from 110 to 135 V DC.
02What is the nominal output current?
The nominal output current is 4 A.
03What is the SFB current?
The datasheet lists a Selective Fuse Breaking current of 24 A for 15 ms.
04Does it have a sleep mode?
Yes. A control input can switch the output on and off for SLEEP MODE.
05What is the overvoltage protection level?
The output overvoltage protection acts below 150 V DC according to the technical data.